Professional Documents
Culture Documents
Coupler Circuit
Injection
Digital
Signal
Processor
Square Wave
Generator ± 15V.
Isolation &
Amplification
Signal
+ Brushes
GEN.
-
ROTOR
Measurement
Analog Isolation Signal (Vf )
Subsystem Amplifier
Machine
See Fig. 7 Frame
Ground
Fig. 4 Field Ground Protection Using an Injection Voltage Signal
Voltage across the rotor earth resistance (Vf)
amplifier. The analog subsystem samples this signal and operator to determine that the field circuitry is free of a ground
converts it to a digital signal using an analog-to-digital converter. before start-up. The above described injection scheme cannot
be used as a second scheme in conjunction with existing volt-
The injection frequency is made programmable and is age schemes described in Fig. 2 and Fig. 3. These voltage
selected by the user based on the rotor capacitance. This gives schemes interfere with the injection voltage field ground method.
more accurate measurement of the rotor earth resistance and
minimizes the errors due to rotor capacitance charging time. III. BRUSH LIFT-OFF DETECTION
The gain of the isolation amplifier and its associated circuit is
not linear. Field measured test data was used to construct the The use of the injection method for field ground detection pro-
model shown in Fig. 5. It can be seen from this figure that the vides a means of detecting how well the brushes of a generator are
non-linearity can introduce large errors in the measurement making contact with the rotor shaft. This is done by analyzing the
of rotor earth resistance. A piece-wise quadratic approximation return voltage signal. Brushes on older generators are a constant
to the gain characteristic is implemented within the relay for a maintenance headache for plant personnel. If brushes open on an
resistance measurement range of 5k to 100k ohms. The earth in-service generator, they can cause substantial arcing damage to
resistance (R) is given by the equation below: the brush mounting structure and eventually result in unit tripping
by loss of field protection. Knowing when brushes should be
R=A()+A1Vf+A2Vf2 replaced or readjusted is important diagnostic information for plant
maintenance personnel. Relay monitoring that provides such infor-
Where A() A1 and A2 are the polynomial coefficients which mation can greatly reduce the changes of brush open circuit during
are obtained using a least-squares approximation technique for generator operation. Analysis of the return voltage signal (Vf) within
each of the segments. Vf is the injection voltage measured the injection field ground relay can provide an indication that the
across the rotor earth fault resistance. The resulting measure- brushes on a generator are not making good contact with the rotor.
ment errors, after the above approximation, are within 10%.
Fig. 7 shows the method used to analyze the return voltage
The relay setpoints are in ohms typically with a 20 KΩ alarm signal. The front of the return voltage signal is rounded due to
and 5 KΩ trip or critical alarm. The injection scheme provides a the field winding capacitance. When the brushes begin to open,
major improvement over traditional voltage schemes in terms the capacitance seen by the injection signal reduces, and the
of both sensitivity as well as security. In addition, digital relays return signal will rise very quickly. The level of voltage is mea-
can provide real-time monitoring (Fig. 6) of field insulation re- sured at a fixed point on the return voltage signal (Vf). The
sistance so deterioration with time can be monitored. The scheme voltage is measured during each square wave cycle. When the
can also detect grounds on an off-line generator allowing the voltage rises above its normal level for a suitable time, an alarm
Brush Lift-
Off Voltage
Field Insulation
Real-Time
Fig. 6 Field Ground Fault Protection— Real Time Measurements Monitoring
is initiated to alert the operator that the brushes should be relay. Fig. 9 illustrates the basic connections. For long-shielded
inspected. The lower the field circuit capacitance, the less of a wire runs between the coupler and the relay, errors can be
voltage rise occurs. For field capacitance of 0.5 µF or less, the introduced in the field insulation measurement. To overcome
brush lift-off voltage will not rise enough to allow the scheme this problem, the relay software allows calibration to compen-
to operate properly. This is a very low value of capacitance not sate for the long wiring runs. A decade box is connected as
typical of most generators. A high brush contact resistance shown in Fig. 10. The decade box resistance is varied from 1-
also prevents the injection signal from entering the field wind- 100 KΩ. The software guides the user in selecting the proper
ings, impairing the field ground resistance measurement. The decade box resistance.
brush lift-off voltage will also rise if the ground brushes on the
generator begin to open. If the ground brushes are allowed to The injection frequency is programmed per the table shown
open, the only path to ground for stray ground current is in Table 1. The injection frequency is based on the field wind-
through the machine bearings. Fig. 8 illustrates this point. Sus- ing to ground capacitance. In most applications, the shunt
tained current flow through the generator bearings will result in capacitance is measured with a standard capacitance meter.
pitting and will require the bearing to be changed. The metering screen in the relay (Fig. 6) provides a real time
measurement of field ground insulation. As a final test on a
IV SETTING & COMMISSIONING de-energized generator, the decade box is connected from
positive or negative to frame ground simulating a field ground
To date, well over 150 digital injection field ground relays fault. The generator field breaker is closed. Grounds ranging
have been installed on generators of all sizes as well as prime from 5-50 KW are simulated with the decade box and read
movers (steam, gas turbines and hydro). The settings and through the relay metering screen. Accuracy is ± 10%, or ±1
commissioning time have been greatly reduced through the KW—whichever is larger.
use of real-time metering, which allows data measured by the
relay to be used in the commissioning process. The field ground The brush lift-off feature provides the means to detect how
coupler is typically installed at a convenient point where the well the brushes on a generator are making contact with the
positive and negative of the field and machine frame ground are rotor. This is an alarm feature to alert the operator that the
available. The installation location is typically at the excitation machine brushes (positive and negative or ground) are not
cubicle. Shielded cable is used to connect the coupler to the making good contact with the rotor. Typically for healthy
VALARM
Voltage Rise
Due to Brush Resistance
VNORMAL Increasing
Exciter
PROTECTIVE RELAY + _
Squarewave 3 Brushes
Vout
Generator Gen.
Rotor
Vin
Return Signal 2
Measurement
Coupling
Vf Network
GROUND
GND
1
Shield
Ground/Machine Frame
Field Ground
Detection