Professional Documents
Culture Documents
2
Connection to the Power System
1. Direct :
2. Via Transformer :
3
Typical Generator Installations
Generator Generator
Transformer Transformer
Station
Trans-
Earthing former
Transformer
Unit / Unit
Station Trans-
Transformer former
1(b) 1(c)
4
Generator Protection Requirements
5
Generator Faults
Faults include :-
Insulation Failure
Stator
Rotor
Excitation system failure
Prime mover / governor failure
Bearing Failure
Excessive vibration
Low steam pressure
etc.
6
System Conditions
Short circuits
Overloads
Loss of load
Unbalanced load
Loss of synchronism
7
Generator Protections to be Considered
8
Stator Earth Fault Protection
9
Method of Earthing (1)
Damage resulting from a stator earth fault will depend upon the earthing
arrangement
0 10
Method of Earthing (2)
1 11
Method of Earthing (3)
limits damage
reduces possibility of developing into phase-phase
fault
connected machines)
2 12
Method of Earthing : Limitation of Earth Fault Current (1)
Less than 5A :
20A :
3 13
Method of Earthing : Limitation of
Earth Fault Current (2)
100A :
As for 20A, but higher current allows better discrimination and sensitivity.
4 14
Stator Earth Fault Protection and Protection Against
Earth Faults on Generator Connections
Depending on the Generator arrangement this can be provided by :-
5 15
Overcurrent Protection (1)
51
6 16
Overcurrent Protection (2)
51
7 17
Stator Earth Fault Protection
51N
50N 51N
xV
xV
ΙF
250/1A IS R
For operation
Ι S(PRIMARY) ΙF
R 33 xV
R
x.6600
x.200
33
1
Ι S(SECONDARY) x.200 x 0.8x
250
For protection of 90% of winding; x = 1-0.9 = 0.1
Relay setting = 0.8 x 0.1 = 0.08A = 8% of 1A
9 19
Stator Earth Fault Protection (1)
Generators connected via step-up transformer (resistance earthed) :
51N 50N
System earth faults ARE not seen by generator earth fault protection
instantaneous relay may be used.
Advantage : Fast
0 20
Stator Earth Fault Protection (2)
Advantage : Sensitive
1 21
Stator E/F Protection for Generator with High
Resistance Earthing via Distribution Transformer (1)
RSTAB
High Impedance Principle
64
Instantaneous Protection
5 x CT’s required
RSTAB
64
4 24
Restricted Earthfault Protection for Generators on 4 Wire L.V.
Systems (2)
Earthing at Busbars
RSTAB
64
4 x CT’s required
5 25
Differential Protection (1)
Stabilising
Resistors
Relay
6 26
Differential Protection (2)
BIAS BIAS
OPERATE
INTERPOSING
C.T.
Two methods :
9 29
100% Stator Earth Fault Protection
For Large Machines Only
Two methods :-
Low frequency injection Third harmonic voltage - various
Earthing
Trans- 59
former
Complete protection during start-up if source is
independent of generator, e.g. derived from
Injection station battery.
Transformer Independent of system V, f and load current.
High cost due to injection equipment.
51 Alternative
Injection
Points
0 30
Third Harmonic Neutral Voltage Scheme
Relies on >1%
generated 3rd
harmonic volts
59 27
59P
27 - 3rd harmonic under voltage relay.
59
59P - Terminal Voltage Check
Allows trip if circuit breaker is open
but terminal voltage present.
TRIP
59P 27 59 - Conventional neutral over voltage
protection.
27 OVERLAP
0 50 100
Earth Fault Position
1 31
Stator Phase-Phase Fault Protection (1)
Insulation failure
Flashover in terminal box
2 32
Stator Phase-Phase Fault Protection (2)
Single Generator
3 33
Stator Phase-Phase Fault Protection (3)
Type types :
4 34
Stator Phase-Phase Fault Protection (4)
Stabilising
Resistors
Relay
5 35
Stator Phase-Phase Fault Protection
Small machines :
Star connection made inside machine
Winding neutral ends are not brought out
6 36
Stator Interturn Fault Protection (1)
7 37
Stator Interturn Fault Protection (2)
VA
VB
VC
VA VB VC VR
FAULT
R
VR = VA + VB + VC
8 38
Stator Interturn Fault Protection (3)
Transverse Differential Protection
(Double Wound Machines) :
Bias
Coils
Operate
Coils
9 39
Prime Mover Failure (1)
Isolated Generators :
Machine slows down and stops. Other protection initiates shut down.
Parallel Sets :
0 40
Prime Mover Failure (2)
Gas Turbines :
Motoring power 100% rated for single shaft machine, 10% to 15% rated for
double shaft.
Hydro Sets :
1 41
Prime Mover Failure (3)
2 42
Reverse Power Protection (1)
Leading P.F.
Operate Restrain
-MW +MW
87.1
Operate Restrain
Lagging P.F.
+MVARLAG
Exporting lagging VAR’s
3 43
Loss of Excitation (1)
EFFECTS
Single Generator :
Loses output volts and therefore load.
Parallel Generators :
Operate as induction motor (> synch speed)
Flux provided by reactive stator current drawn from
system-leading pf
Slip frequency current induced in rotor - abnormal
heating
4 44
Loss of Excitation (2)
Simple Protection Scheme
Field Exciter
Winding
Shunt Requires access to
Ie
field connections.
DC relay Not suitable if
(setting < Ie min) generator operates
Aux Supply normally with low
excitation (large
T1
machines).
Alternative scheme
monitors impedance
T2
at generator
0.2 - 1 sec
Overcomes Alarm or terminals.
Slip Frequency Trip
Effects
2 - 10 secs
5 45
Loss of Excitation (3)
Alternative Scheme
XG XT XS
EG ES
6 46
Loss of Excitation (4)
Load Impedance
R
Impedance Offset – Prevents
Locus operation
on pole slips
Diameter
Typically : Relay Characteristic
Offset 50-75%X’d
Diameter 50-100% XS Time Delayed
7 47
Impedance Locus of Generator Operating Out of
Synchronism
+jX
EG/ES = 1.5
2.0
LOAD POINT
5.0
5
A
EG/ES = 1
G
0.2 0.5 0.7
-jX
9 49
Rotor and Power Factor Angles
Relay Location
Xd
I
E V
IXd
= Rotor Angle
V Ø = Power Factor Angle
I
Ø
0 50
Power Limit Impedance Diagram
jx
Z
VΙ.COS C
Ø V2/C Ι C
COS
R
V V2
V2
Z COS
C
1 51
Loci of Constant Rotor Angle
jx
=
Xd 120 90 30
2 52
Relay Characteristic Req’d to Allow Generator
Operation with Rotor Angles up to ''
jx Constant Power
Offset R
0.75X’d
Limiting
Generation
Point
Diameter
Constant
Relay
Characteristic
3 53
Unbalanced Loading (1)
Effects
Gives rise to negative phase sequence (NPS) currents - results
in contra-rotating magnetic field.
4 54
Unbalanced Loading (2)
Protection
Machines are assigned NPS current withstand values :
6 56
Rotor Earth Fault Protection (2)
Potentiometer Method
Exciter
7 57
Rotor Earth Fault Protection (3)
AC Injection Method
AC Auxiliary
Supply
R
Brushless Machines
No access to rotor circuit
Require special slip rings for measurement
If slip rings not present, must use telemetering techniques
(expensive)
8 58
Overload Protection (1)
Governor Setting
9 59
Overload Protection (2)
Overcurrent Protection
0 60
Generator Back-Up Protection (1)
Over current Protection
Typical use :
Very or extremely inverse for LV machines
Normal inverse for HV machines
10 x
FL
with AVR
Full
Load
no AVR
Cycles
1 61
Generator Back-Up Protection (2)
Voltage Restrained
Voltage Controlled
F
2 62
Voltage Controlled Overcurrent Protection
Overload
Characteristic
Is
Current Pick - up
t
Fault
Characteristic
Vs
I Voltage
3 63
Voltage Restrained Overcurrent Protection
Equivalent to impedance
Current Pick-up
devices I>
KI>
VS2 VS1
Voltage
4 64
Impedance Relay
jx
RELAY
CHARACTERISTI
C
MZTU
Set to operate at 70% rated load impedance when voltage drops to zero,
current required to operate relay is 10% rated current. Built-in timer for
co-ordination purposes.
5 65
Under & Over Frequency Conditions (1)
Over Frequency
6 66
Under & Over Frequency Conditions (2)
Under Frequency
7 67
Under & Over Voltage Conditions (1)
Protection
8 68
Under & Over Voltage Conditions (2)
Over Voltage
Under Voltage
9 69
Other Protection Considerations
0 70
Pole Slipping Protection
Rotor Stator
X
EG
ES
ZG9356
1 71
Pole Slipping Detection
E E = 2.8 (max) X
G S
R
E E = 1.2
G S
E E =1
G S
E E = 0.8
G S
E E = 0.19 (min)
G S
MIS9357
2 72
Pole Slipping Protection
3 73
7 77
Overfluxing
Often applied to :-
Generator transformers
Grid transformers
Flux Ø V / f
Caused by either :-
Increase in voltage
Reduction in frequency
Combination of both
Usually only a problem :-
during run-up or shut down
can be caused by loss of load / load shedding
9 79
Transformer Magnetising
Characteristic
Twice
Normal
Flux
Normal
Flux
Normal
No
Load No Load Current
Current at Twice Normal
Flux
0 80
Magnetising Current with
Transformer Overfluxed
ZG0780C
1 81
Overfluxing
Effects of overfluxing :-
Increase in magnetising current
Increase in winding temperature
Increase in noise and vibration
Overheating of laminations and metal parts
(caused by stray flux)
2 82
Over-Fluxing Relay
Ex
G
VT
AVR R
L
3 83
Low Forward Power Interlocking
Urgent Trip
Trip Directly to Circuit Breaker and Initiate shut down
Risk of overspeed
Examples :-
Generator Differential
stator ground fault
negative phase sequence.
4 84
Low Forward Power Interlocking
Non-Urgent Trip
Trip governor
Use low forward power interlocking to determine when main Circuit Breaker is
tripped
Reduced risk of overspeed, and consequential damage to the machine
Examples :-
Over voltage
Over load
Loss of synchronism
Field failure
5 85
Unintentional Energisation at Standstill
Scheme
Typical Approach
50
27 & Trip
tPU
&
tDO
VTS
6 86
VT Fuse Failure Protection
ZG7965D
7 87
Synchronising Relays
Often applied to :-
Synchronising of Generators
Transmission line auto-reclose schemes
Synchronising of Generators
Check voltage magnitudes
Check slip frequency
Check phase angle difference
Synchroscope
Speed of rotation depends on slip frequency
If frequencies matched, phase angle displacement indicated
Does not indicate voltage magnitude
8 88
Voltage Checking & Comparators
Voltage monitors :-
9 89
Auto-Synchronising Relays
Controls :-
Filed current to adjust voltage magnitude
Governor to adjust slip frequency
Governor to correct constant phase displacement
0 90
Typical Schemes
1 91
Tripping Modes
Class C HV breaker
2 92