Professional Documents
Culture Documents
Week-01
Introductory Concepts
Instructor: Dr. Wahab Ali
Lecture Layout for First Week
2
Lecture Layout for First Week
3
Background
Electrical power system has three principle divisions
1. Generating station
2. Transmission system
3. Distribution system
4
5
Why Electrical transients/over-voltages in power system happens
External Overvoltage
1. Lightning phenomenon
2. Lightning strike to transmission lines
3. Lightning strike to substations
6
Internal Overvoltage
Switching Overvoltage (due to short circuit incidents, rejection of no-
load lines…)
Insulation Failure
Arcing ground, resonance
7
8
Dependence of modern society on Electric Supply
9
Construction of a Power system : Primary system
10
Secondary systems in a Power system
Protection
Auto control for voltage, frequency, reactive power compensation, power
flow, network configuration and stability
Metering for Billings, operational control and statistical data
Local manual control (plant status, voltage level reactive power support,
network configuration)
Remote manual control via communications links (SCADA)
Plant condition monitoring and alarming (temperature,
malfunction, maintenance need, operating duty)
Communications infrastructure
Instrument Transformers - current and voltage transformer
11
What is Protection System
12
Purpose of Protection System
13
Basic Type of Protection
14
Relay Protection System
15
Different Types of Protection
1. By Object
Line protection
Feeder protection
Transformer protection
Generator protection
Bus bar protection
Motor protection
2. By Principle
• Distance protection
• Impedance protection
• Differential protection
• Pilot wire protection
• Over current protection
• Residual current protection
• Directional earth fault
• Over/under frequency protection & Over/under voltage protection 16
17
18
19
Single line-to-ground fault due to
flashover of insulating string
20
Faults and Abnormal Operating Conditions (Shunt Faults)
21
In low voltage systems up to three reclosures are attempted after which the
breaker is locked out. Multiple reclosure attempts sometimes helps to
burnout the object causing short circuit. The reclosure may be done
automatically.
In EHV systems, where the damage due to short circuit may be very large
and the system stability is at stake; only one reclosure is allowed.
Type of Short Circuit:
Dead Short Cct.: A fault which bypasses the entire load current through
itself is called a metallic fault (dead short). It presents a very low, practically
zero fault resistance.
Partial Short Cct.: It can be modeled as non-zero resistance (or impedance)
in parallel with the intended path of current. Most of the times it is the
resistance of the arc which is highly non-linear.
22
Faults and Abnormal Operating Conditions (Shunt Faults)
23
Causes of Shunt Fault
The insulation may fail because of its own weakening, or it may fail due to
over voltage (internal due to switching or external due to lightening). There
may be the following reasons of insulation failure;
Ageing
Temperature
Rain, hail, snow
Chemical pollution
Foreign objects
Other causes
24
Effects of Shunt Fault
The steady fault current is not of much concern for isolated alternators. But
in the Interconnected power system all the generators will contribute
towards the fault current, thus building up the value to couple of tens of time
the normal full load current. If these fault current persist even for a short
time, they will cause extensive damage to the equipment that carry these
currents. In general they cause;
Overheating and danger of fire
Deterioration/weakening of insulation
Mechanical damage due to excessive mechanical forces during over
currents (specially in transformers windings).
Effects the system stability and may trip the alternators due to
increased relative swing caused by increased rotor angle δ.
Thus in an interconnected system, faults need to be isolated as
selectively and as speedily as possible.
25
Classification of Shunt Fault
26
Probability of Occurrence of Faults on Different Elements of Power
System
27
Power System Structural Considerations
1. Power Apparatus
Main function is to generate, transforms and distribute power to load
2. Control Equipment
Load center Functions and Central Functions
It helps to maintain the P/S at normal V & F, it generates
sufficient power as per demand & maintain economy &
security in the interconnected network.
Control Function: this act continuously to adjust system
variables. (V & F, Power flow)
3. protection Equipment
This act as a open-closed CBs, due to this the structure of
P/S changes.
Response time = High (as compare to Control Ftn)
What is Grounding or Earthing
32
The primary winding of a distribution transformer connected between
the line and neutral of a 11 kV line.
There is capacitance C1 between primary and secondary and
capacitance C2 between secondary and ground.
This capacitance coupling can produce a high voltage between the
secondary lines and the ground.
If a person touches either one of the secondary wires, the resulting
capacitive current IC flowing through the body could be dangerous
even in case of small transformers.
The secondary conductors are ungrounded.
Let us now turn to a more serious situation.
Suppose that the high voltage line (11 kV in this case) touches the 230 V
conductor as shown in previous slide.
Under these circumstances, a very high voltage is imposed between the
secondary conductors & ground.
• If one of the secondary lines is grounded as shown in Fig.
(ii), the accidental contact between a 11 kV conductor and
a 230 V conductor produces a dead short.
• The short-circuit current (i.e. fault current) follows the
dotted path shown in Figure (ii).
• This large current will blow the fuse on the 11 kV side, thus
disconnecting the transformer and secondary distribution
system from the 11 kV line.
What are the Methods of Neutral Grounding
37
Solid Grounding
End