Professional Documents
Culture Documents
Systems Dukelsky
1
1.1.4. Effect of Faults and Faults Statistics
1.2. Function Characteristics of Relays
1.3. Role of Protections
1.4. Types of Protections
1.4.1. Primary Protection
1.4.2. Secondary Protection
1.5. Characteristic of Relays
1.6. Over Current Relays
1.7. Electromagnetic Relays
INTRODUCTION Chapter-1
and distribution lines, etc. Short circuits and other abnormal conditions often
occur on a power system. The heavy currents associated with short circuits likely
are not provided for the protection of each section of the power system.
device is needed to isolate the faulty element as quickly as possible to keep the
healthy section of the system in normal operation. The fault must be cleared
period, it may cause damage to some important sections of the system. A heavy
short circuit current may cause a fire. It may spread in the system and damage a
part of it. The system voltage may reduce to a low level and individual
A protective scheme includes circuit breaker and protective relays to isolate the
faulty section of the system from the healthy sections. A circuit breaker can
disconnect the faulty element of the system when it is called upon to do so by the
protective relay. The function of a protective relay is to detect and locate a fault
and issue a command to the circuit breaker to disconnect the faulty element of
normal and abnormal condition. The basic electrical quantities which are likely to
Protection is needed not only against short circuit but also against any other
abnormal conditions which may arise on a power system. A few examples of other
alternator, etc. Protective relays are also provided to detect such abnormal
conditions and issue alarm signals to alert operators or trip circuit breaker.
rather it takes action only after a fault has occurred. However, one exception to
this is the Buchholz relay, a gas actuated relay, which is used for the protection of
3
switching surges, or by external conducting object falling on overhead lines.
Overvoltage due to lighting or switching surges cause flashover on the surface of
insulators resulting in short circuits. Sometimes, insulators get punctured or break.
Sometimes, certain foreign particles such as fine cement dust or soot in industrial
areas or salt in coastal areas or any dirt, in general, accumulates on the surface of
string and pin insulators. These reduce their insulation strength and causes
flashovers. Short circuit is also caused by tree branches or other conducting
object falling on the overhead lines.
Birds also may cause faults on overhead lines if their bodies touch on of the
phases and earth wire (or the metallic support structure which is at earth
potential). If the conductors are broken, there is a failure of the conducting path
and the conductor becomes open-circuited. If the broken conductor falls to the
ground, it results in a short circuit. Joint failure on the cable or overhead lines are
also a cause of failure of the conducting path. The opening of one or two of the
three phases makes the system unbalanced. Unbalanced currents flowing in the
rotating machines set up harmonics, thereby, heating the machines in the short
periods of time. Therefore, unbalancing of the lines is not allowed in the normal
operation of a power system. Other causes of faults on overhead lines are direct
lightning strokes, aircraft, snakes, ice and snow loading, abnormal loading, storms,
earthquakes, creepers etc. In the case of cables, transformer, generators and
other equipment, the causes of faults are: failure of the solid insulation due to
aging, heat, moisture or overvoltage, mechanical damage, accidental contact with
earth or earthed screens, flashover due to over-voltages, etc.
Sometimes, circuit breakers may trip due to errors in the switching operation,
testing or maintenance work, wrong connections, defects in protective devices,
etc. Certain faults occur due to the poor quality of system components or
because of a faulty system design. Hence the occurrence of such faults can be
reduced by improving the system design, by using components and materials of
good quality and by better operation and maintenance.
4
Two broad classifications of faults are:
(i) Symmetrical faults (ii) Unsymmetrical
faults
Fig. 1.1
1.3.2 Unsymmetrical Faults
Single phase to ground, two-phase to ground, phase to phase short circuit;
ingle phase open circuit and two-phase open circuit are unsymmetrical types of
faults.
Fig. 1.2
5
(b) Two-Phase To Ground (2L-G) Fault
A short circuit between any two phases and the earth (Fig. 1.3) is called a double
line to ground fault or two-phase to ground fault.
Fig. 1.3
Fig.1.4
This type of fault is caused by a break in the conducting path. Such faults
occur when one or more phase conductors break or a cable joint or a joint on the
overhead line fails. Such situations may also arise when circuit breaker or isolators
open but fail to close one or more phases. Due to the opening of one or two
phases, unbalanced currents flow in the system, thereby heating rotating
machines. Protective schemes must be provided to deal with such abnormal
situations.
6
1.3.3 Simultaneous Faults
Two or more faults occurring simultaneously on a system are known as
multiple or simultaneous faults. In simultaneous faults, the same or different types
of faults may occur at the same or different points of the system. An example of
two different types of faults occurring at the same point is a single line to ground
fault on one phase and breaking of the conductor of another phase, both
simultaneously present at the same point. The simultaneous presence of an L-G
fault at one point and a second L-G fault on another phase at some other point is
an example of two faults of the same type at two different points. If these two L-
G faults are on the same section of the line, they are treated as a double line to
ground fault. If they occur in different line sections, it is known as a cross-country
earth fault. Cross-country faults are common on systems grounded through high
impedance or Peterson coil but they are on solidly grounded systems.
(a) Heavy short circuit current may cause damage to equipment or any other
elements of the system due to overheating and high mechanical forces set
up to heavy current.
(b) Arcs associated with short circuit may cause fire hazards. Such fires,
resulting arcing, may destroy the faulty element of the system. There is
also a possibility of the spreading to other parts of the system if the fault
is not-isolated quickly.
(c) There may be reduction in the supply voltage of the healthy feeders,
resulting in the loss of industrial loads.
(d) Short circuits may cause the unbalancing of supply voltages and currents,
thereby heating the rotating machines.
7
(e) There may be a loss of system stability. Individual generators in a power
station may lose synchronism, resulting in a complete shutdown of the
system. Loss of stability of interconnected systems may also result.
Subsystems may maintain supply for their individual zones but load
shedding would have to be resorted in the sub-system which was
receiving power from the other subsystems before the occurrence of the
fault.
(f) The above faults may cause an interruption of supply to consumers,
thereby causing a loss of revenue.
High grade, high speed, reliable protective devices are the essential
requirements of a power system to minimize the effects of faults and other
abnormalities.
For the design and application of a protective scheme, it is very useful to have
an idea of the frequency of occurrence of faults on various elements of a power
system. Usually the power stations are situated far away from the load centers,
resulting in hundreds of kilometers’ length of overhead lines being exposed to
atmospheric conditions. The chances of faults occurring due to storms, falling of
external objects on the lines, flashovers resulting from dirt deposits on insulators,
etc., are greater for overhead lines than for other parts of the power system.
Table 1.1 gives an approximate idea of the fault statistics.
8
Underground cables 9
Transformers 10
Generators 7
Switchgears 12
CTs, PTs, Relays
12
control equipment, etc.
From Table 1.1, it is evident that 50% of the total fault on overhead lines. Hence
it is overhead lines that require more attention while planning and designing
protective schemes for a power system.
Table 1.2 shows the frequency of occurrence of different type (mainly the
different types of short circuits) on overhead lines. From the table it is evident
that the frequency of line to ground faults is more than any other type of fault,
and hence the protection against L-G fault requires greater attention in
planning and design of protective schemes for overhead lines.
Lines
In the case of cable 50% of the faults occur in cables and 50% at end junction.
Cable faults are usually of a permanent nature and hence, automatic reclosures
are not recommended for cables.
9
A protective relay is a device that detects the fault and initiate the operation of
the circuit breaker to isolate the defective elements from the rest of the system.
The relay detects the abnormal conditions in the electrical circuit by constantly
measuring the electrical quantity which are different under normal and fault
conditions. The electrical quantity which makes change under fault condition are
voltage, current, frequency and phase angle. Through the change in one or more
of these quantities, the fault signals, their presence type and location to the
protective relays. Having detected the fault and the relay operates to close the trip
circuit of the breaker. This results in the opening of the breaker and disconnection
of faulty circuit.
Fig.1.5
A typical relay circuit is shown in Fig.1.5. This diagram shows one phase of
three phase system for simplicity. The relay circuit connection can be divided into
three parts, viz.
(a) First part is the primary winding of current transformer CT, which is
connected in series with the line to be protected.
(b) Second part consists of secondary winding of CT and the relay operating
coil.
10
(c) Third part is the tripping circuit which may be either AC or DC. It consists
of a source of supply, the trip coil of the circuit breaker and the relay
stationary contacts.
When a short circuit occur at a point on the transmission line, the current flowing
in the line increased to an enormous value. This results in a heavy current flow
through the relay coil, causing the relay to operate by closing its contacts. This in
turn closes the trip circuit of the breaker, making the circuit breaker open and
isolating the faulty section from the rest of the system. In this way, the relay
ensure the safety of circuit equipment from damage and normal working of the
healthy portion of the system.
Fig.1.6
11
The principal function of protective relaying is to cause the prompt removal
from service of any element of the power system when it starts to operate in any
abnormal manner or interfere with the effective operation of rest of the system. In
order that protective relay system may perform this condition satisfactorily, it
should have the following qualities:
(a) Selectivity
(b) Speed
(c) Sensitivity
(d) Reliability
(e) Simplicity
(f) Economy.
(a) Selectivity: It is the ability of protective system to select correctly that part of
the system in trouble and disconnect the faulty part without disturbing the rest
of the system.
It is the basic requirement of the relay in which it should be possible to select
which part of the system is faulty and which is not and should isolate the
faulty part of the system from healthy one. Selectivity achieved in two ways:
(i) Unit system of protection and
(ii) Non unit system of protection.
(i) Unit system of protection means the one in which the protection responds
only to faults within its own zone and does not make note of the condition
elsewhere, e.g., that is the differential protection of transformers and
generators. Here the protection scheme will work only if the fault is in the
transformer or the generator respectively.
(ii) Non unit system protection is one in which the selectivity is obtained by
grading the time or current setting of the relay at different location, all of
which may respond to a given fault.
(b) Speed
12
A protective relay must operate at the required speed. It should neither be too
slow which may result in damage to the equipment, nor should it be too fast which
may result in undesired operation during transient faults.
The shorter the time of which a fault is allowed to persist on the system, the
more load can be transferred between given points on the power system without
loss of synchronism. Fig.1.7 shows the curve which represent the power that can
be transmitted as a function of fault clearing time for various types of faults.
It can be seen from the curve that the severest fault is the three-phase fault
and the least severe is L-G fault in terms of transmission of power.
The relay system should disconnect the faulty section as fast as possible for the
following reasons:
(i) Electrical apparatus may be damaged if they are made to carry the fault
current for a long time.
(ii) A failure on the system leads to a great reduction in the system voltage. If
the faulty section is not disconnected quickly, then the low voltage created
by the fault may shut-down consumers’ motors and generators on the
system may become unstable.
(iii)The high speed relay system decreases the possibility of development of
one type of fault into the other more severe type.
13
(c) Sensitivity: It is the ability of relay system to operate with low value of actuating
quantity.
14
1.8 Classification of Relays
15
(i) Overvoltage/Overcurrent/Over Power Relay: The relay operates where the
voltage or current or power rises above the specified value.
(ii) Under Voltage/Undercurrent/Under Power Relay: The relay operates when
the voltage or current or power fall below the specified value.
(iii) Directional or Reverse Current Relay: The relay operates when applied
current assumes a specified phase displacement with respect to the
applied voltage and the relay is compensated for fall in voltage.
(iv) Directional or Reverse Power Relay: This type of relay operates when the
power in the circuit flows in specific direction. A directional power relay is
so designed that it obtained its operating torque by interaction of
magnetic field derived from both voltage and current of the circuit to be
protected.
(v) Differential Relay: The relay operates when some specified phase or
magnitude difference between two or more electrical quantities occurs.
(vi) Distance Relay: In this relay, the operation depends upon the ratio of
voltage to the current flowing in the circuit to be protected.
16
current or other quantity causing operation and tends to be definite minimum
time as the value increases without limit.
When a fault occurs on any part of electric power system; it must be cleared
quickly in order to avoid damage and/or interference with the rest of the system.
It is a usual practice to divide the protection scheme into two classes’ viz. Primary
protection and backup protection.
17
an over-current relay that protects the line. If fault occur on any line, it will be
cleared by its relay and circuit breaker. This forms the primary or main
protection and serves as first line of defense. The service record of primary
relying is very high with well over 90% of all operations being correct.
However, sometimes faults are not cleared by primary relay system because of
trouble within the relay wiring system or breaker. Under such conditions,
backup protection does the required job.
Fig. 1.8
(b) Backup Protection: It is the second line of defense in case of failure of
primary protection. It is designed to operate with sufficient time delay so that
primary relaying will be given enough time to function if it is able to do so.
Thus referring to Fig.1.8, relay ‘A’ provides backup protection for each of the
four lines. If a line fault is not cleared by its relay and breaker, the relay ‘A’ on
the group breaker will operate after a time delay and clear the entire group of
lines. It is evident that when backup relaying functions, the larger part is
disconnected than when primary relaying functions correctly. Therefore,
greater emphasis should be placed on the better maintenance of primary
relaying. Time graded schemes such as over current or distance protection
schemes are the examples of those providing inherent backup protection.
The backup protection is further classified as following three types
18
(a) Remote Backup Protection: When a backup relay is located at a neighboring
station, they back up the entire primary protective scheme which includes the
relay circuit breaker, potential transformer, current transformer and other
elements as in case of primary protective scheme. It is widely used backup
protection for transmission lines and a cheapest and the simplest form of
backup protection. It will not fail due to the factors causing the failure of
primary protection, this is most desirable form of protection.
(b) Relay Backup Protection: This is a local backup. Backup protection is provided
by placing an additional relay. It trips the same circuit breaker if the primary
relay fails and its operation takes place without delay. This is very costly, so it
is placed where a remote backup is not possible. They should be supplied
from separate current and potential transformer.
(c) Breaker Backup Protection: This is also a local backup protection. This is
necessary for a bus bar system where a number of circuit breakers are
connected to it. A circuit breaker fails to trip, when a protective relay operates
in response to a fault, this fault is treated as bus bar fault. If the proper
breaker does not trip within a specified time then after a time delay, the main
relay closes the contact a backup relay which trips all other circuit breakers on
the bus.
2 Protective Relays
In this chapter we will discuss different types of protective relays.
19
Depending upon the time of operation, the relays are classified as:
Fig.2.1
20
(II) Time Overcurrent Relay: This relay operates with a time delay. The time delay
is adjustable for a given setting, actual time delay depends on the current
flowing through the relay coil. In general, higher current flow will cause a
faster operation of relay. The minimum current at which the relay operates
(pickup current) is also adjustable. Time overcurrent relay can be classified
as:
(a) Definite Time Overcurrent Relay: It operates after a pre calculated time when
current become higher than its pick value. Fig.2.2 shows the definite time
characteristics of overcurrent relay. As shown in Fig.2.2, the operating time is
constant above the pickup value irrespective of magnitude of current.
(b) Inverse Time Overcurrent Relay: It operates when current exceeds its pick up
value. This relay has inverse time characteristics in which fault current
increases with decrement in operating time. When saturation occurs at a very
early stage than time of operation remain same. Fig.2.2 shows the inverse
time current characteristics of inverse time overcurrent relay. They are more
inverse near the pick-up value of actuating quantity and less inverse as it is
increased. They may be classified as:
(i) Inverse Definite Minimum Time (IDMT) Overcurrent Relay: In I.D.M.T. relay the
operating time is inversely proportional to the fault current near its pickup
value and constant about a pickup value of relay. This relay gives an inverse
time characteristics at lower values of fault currents and definite time
characteristic at its higher value of fault currents.
This type of relay is used for protection of distribution line and provision for
current and time settings.
21
Fig. 2.2: Characteristic of various over current relays.
(ii) Very Inverse Time Overcurrent Relay: In this relay, the saturation of the core
occurs at later stage. It gives more inverse characteristics lies between an
I.D.M.T. characteristics and extremely inverse characteristics as shown in
Fig.2.2.
It can be used where and I.D.M.T. relay failed due to better selectivity.
Calculation of time current characteristics is:
(iii) Extremely Inverse Time Overcurrent Relay: In this relay, the saturation
occurs at a still later stage. This characteristic is more inverse than that of
very inverse and I.D.M.T. relay as shown in Fig.2.2. Where I.D.M.T. and vary
inversely relays are fails, the extremely relays are employed. Its time-current
characteristics is described by
2
I t=K
Where, I= operating current and t=operating time.
This relay is very suitable for machine's protection against overheating and
protection of alternator against overloads and internal faults. An extremely inverse
relay is able to distinguish between a fault current and inrush current due to its
22
steep time current characteristics. So that this relay is suitable for load restoration
purpose.
Most of the relays in service on the electric power system today are of
electromechanical type. They work on the following two main operating principle.
(Based on the principle of operation), these can be further classified into two
groups:
Such relays are normally used for DC operating quantities but they can also be
used for AC operation by providing shading regions on their poles to split air flux
into two out of phase components. These relays are not suitable for continuous
operation on AC in the pickup position because there would be excessive vibration
and noise.
23
The important type of electromagnetic attraction type relays are:
Fig,2.3
24
current through the relay coil increased sufficiently and the relay armature is
attracted toward the electromagnet which closes the trip circuit of circuit breaker.
Electromagnet are usually instantaneous type. A definite time lag can be obtained
by using an oil dash pot or an escapement chamber or a clock work mechanism.
The oil dash pot or air escapement chamber must be widened at one end so that
there should be a free movement over the last part of the stroke to make good
contact. By placing a fuse in parallel with an instantaneous or definite time lag
relay, it can be made as inverse time lag relay.
Fig.2.4
25
in the position shown. However, on the occurrence of fault, the current through
the relay coil becomes more than the pickup value causing the plunger to be
attracted to the solenoid. The upward movement of the plunger closes the trip
circuit, thus opening the circuit breaker and disconnecting the faulty circuit. Such
relay is used for overcurrent protection. This type of relay is usually instantaneous
type but can be made a definite time lag or inverse time lag by using an oil dash
pot, an oil escapement chamber, a clockwork mechanism or by placing a fuse in
parallel with the relay.
Fig.2.5
26
(a) (b) (c)
Fig.2.6
Referring to Fig.2.6 where the two flux and induced current are shown
separately for clarity,
Let
Assuming that path in which the rotor currents flow has negligible self-inductance,
the rotor currents will be in phase with their voltages.
27
Thus, the induction relay is a sine comparative in which the maximum torque is
o o 0 o
developed. When θ =90 or 270 , and zero when θ =0 or 180 .
The following type of structure are commonly used for obtaining the phase
difference in the fluxes and hence the operating torque in the induction relays
28
This shows that driving torque is proportional to the square of current in
the relay coil. Such torque control is employed where directional feature is
required.
Fig.2.7
Fig.2.8
29
An important feature of this type of relay is that its operation can be controlled
by opening or closing the secondary winding circuit. If this circuit is opened no
flux can be set up by the lower magnet. However, greater value of current in the
primary winding may be and consequently not torque will be produced. Therefore,
the relay can be made inoperative by opening the secondary winding circuit.
Closing of contacts carried on arm attached to the spindle which closes the trip
circuit of circuit breaker.
Fig.2.9
Induction Cup structure are more efficient torque producer than either the
shaded pole or watt hour meter structure. Therefore, this type of relay has very
30
high speed and may have an operating time less than 0.1 second. The ratio of
reset to pick-up is inherently high in case of induction relays as compared to
electromagnetic (attraction type) relays as their operation does not involve any
change in air gap of the magnetic circuit.
31