Gulf Cooperation Council

Interconnection Authority
GCCIA

Engineer

GCC Interconnection Project - Phase I


TRANSMISSION & DISTRIBUTION
END TO END Test Report Bay Ref : Q01 – SALWA LINE # 8
OHL Substation: DOHA SOUTH SS 400KV

REVISION
SUMMARY
PAGES 0 1
1 PURPOSE OF TESTS 2 X
2 SCOPE 2 X
3 TEST EQUIPMENT 2 X
4 PRE-REQUISTES 2 X
5 PROCEDURES 3 X
6 RECORD TEST SHEET 5 X
6.1 DIFFERENTIAL PROTECTION END TO END TESTS 5 X
6.2 DISTANCE PROTECTION END TO END TESTS 8 X

6.3 DIRECT INTERTRIP END TO END TESTS : 9 X


6.4 FINAL CHECK 9 X

AREVA T&D GCCIA / SNCL


Signature Signature

Name Name
Date Date
Doc. No. REV-0 Page 1 of 10
Gulf Cooperation Council
Interconnection Authority
GCCIA

Engineer

GCC Interconnection Project - Phase I


TRANSMISSION & DISTRIBUTION
END TO END Test Report Bay Ref : Q01 – SALWA LINE # 8
OHL Substation: DOHA SOUTH SS 400KV

1 PURPOSE OF TESTS
The purpose of the tests is to check the correct transmission signal information send and receive by the
Relays from optic fibers teleprotection and PLC.
All intertrip logic should be tested.
These tests are performed without load on the line. Tests with line charged are covered by energisation
procedure.

2 SCOPE
LOCAL END REMOTE END
Substation Name :- DOHA SOUTH (DSS) Substation Name :- SALWA SS
Diameter: Q01 Diameter: Q01
Line : L8 TO SALWA Bay : L8 TO DSS
Panel Number : 1RB1,1RA1 Panel Number : 1RB1,1RA1
Relays
Relay Denomination
Denomination in 87LB/21A 87LB/21A
in Scheme
Scheme
Scheme to be
END- TO END TEST.
Checked

3 TEST EQUIPMENT USED (LOCAL END)


Equipment Calibration Calibration due
Sl No Description Make
Sl No. date date
1. Secondary
Injection Kit

Setting software Type : MICOM S1 Studio


Version : 3.1.1

AREVA T&D GCCIA / SNCL


Signature Signature

Name Name
Date Date
Doc. No. REV-0 Page 2 of 10
Gulf Cooperation Council
Interconnection Authority
GCCIA

Engineer

GCC Interconnection Project - Phase I


TRANSMISSION & DISTRIBUTION
END TO END Test Report Bay Ref : Q01 – SALWA LINE # 8
OHL Substation: DOHA SOUTH SS 400KV

4. PRE - REQUISITES
PRE-REQUISITES REMARKS
All Safety Condition Are Ok
All Competent Personnel Available For The Test
Ac & Dc Supply Availability And Security
PPE Safety Available.
All Other Relevant Safety Instructions Been Followed
Coordination With Other Parties ( GIS, Transformer, Etc..)

5. TEST PROCEDURES
The following procedures are written for demonstrating the main End to end test to be done for the
Differential Protection and Distance protection for OHL.
All Trip Relays should be reset before the tests.
To perform this test the Differential relay should be set on Test loop back mode – Disabled in
Commission Tests Setting. In order to test the actual communication channels.
These tests can be performed without CB breaker operation, by disconnecting the trip orders at Master
trip side.

5.1 Differential Function (section 6.1)

5.1.1 Communication check


After Normalize of the communication channel between the two ends:
1-Remove one side of the channel 1 (TX) and check the channel 1 communication fail alarm after
setting time.
2- Check the remote end has also communication fail alarm.
3-Remove one side of the channel 2 (TX) and check the channel 2 communication fail alarm after
setting time.
4- Check the remote end has also communication fail alarm.
5-Remove one side of the channel 1 & Channel 2 (TX) and check the communication fail alarm after
setting time.
6- Check the remote end has also communication fail alarm.
7- note for information the propagation delay (few ms), for each channel. Both values should be
similar.

AREVA T&D GCCIA / SNCL


Signature Signature

Name Name
Date Date
Doc. No. REV-0 Page 3 of 10
Gulf Cooperation Council
Interconnection Authority
GCCIA

Engineer

GCC Interconnection Project - Phase I


TRANSMISSION & DISTRIBUTION
END TO END Test Report Bay Ref : Q01 – SALWA LINE # 8
OHL Substation: DOHA SOUTH SS 400KV

5.1.2 Measurement check


1-Inject Current from local side and check the current measurement at both ends of the line.
2- Inject Current from Remote side and check the current measurement at both ends of the line.

5.1.3 Pick up test of differential protection


1-Inject Current from local side until the relay operates, record operation current measured by the
relay at both ends.
2-Inject Current from Remote side until the relay operates, record operation current measured by the
relay at both ends.

5.1.4Communication Fail Blocking test


1-Inject Current from local side with CH1 & CH2 in service: Injected current in R phase 0,5A, check
the relay operates at both ends.
2-Inject Current from local side with CH1 in service & CH2 out of service: Injected current in R
phase 0,5A, check the relay operates at both ends.
3-Inject Current from local side CH1 out of service & CH2 in service : Injected current in R phase
0,5A, check the relay operates at both ends.
4-Inject Current from local side with Both CH1 & CH2 out of service: Injected current in R phase
0,5A, check the Diff function in the relay NOT operates at both ends. and the relay will trip by 21 ,
only for faults in Zone 1. No need to check operation of Zone 1 , This is covered in function Check.

5-Repeat the same test but the injection from remote end.

5.1.5 Checking of Inter Trip Function


1-Increase the setting at local side to 0.5 A and keep remote end at 0.35 A setting , then Inject in
Local end 0.45 A ( greater than remote end setting and lower than local end setting) , relay should
operate and Diff intertrip both sides.
2- Repeat the same test while remote end setting is increased and local end back to normal setting.
3- Return the both sides to the normal setting, and check that both relays operate while injecting
current more than setting.

5.2 Distance Protection (section 6.2)


Aided Zone 2 scheme Test:
1- Inject fault values of Z2 and Check that signal send from relay to remote end. And check that the
signal is received in remote end.
2- Inject fault values of Z2 and Check the operation time with signal received from remote end.
3- Inject fault values of Z2 and Check the operation time without signal received from remote end.

AREVA T&D GCCIA / SNCL


Signature Signature

Name Name
Date Date
Doc. No. REV-0 Page 4 of 10
Gulf Cooperation Council
Interconnection Authority
GCCIA

Engineer

GCC Interconnection Project - Phase I


TRANSMISSION & DISTRIBUTION
END TO END Test Report Bay Ref : Q01 – SALWA LINE # 8
OHL Substation: DOHA SOUTH SS 400KV

Aided DEF scheme Test:


1- Inject fault values of DEF-Forward and Check that signal send from relay to remote end. And
check that the signal is received in remote end.
2- Inject fault values of DEF-Forward and Check the operation time with signal received from
remote end.
3- Inject fault values of DEF-Forward and Check the operation time without signal received from
remote end.

5.3 Direct Intertrip (section 6.3)


1- Operate (DTT A SEND) by activating (TEE, 27/59X, 50/62) respectively and Check that DTT
signal send from relay to remote end. Also check that the signal is received in the remote end.
2- Check the operation of Trip relay when signal received from remote end.

AREVA T&D GCCIA / SNCL


Signature Signature

Name Name
Date Date
Doc. No. REV-0 Page 5 of 10
Gulf Cooperation Council
Interconnection Authority
GCCIA

Engineer

GCC Interconnection Project - Phase I


TRANSMISSION & DISTRIBUTION
END TO END Test Report Bay Ref : Q01 – SALWA LINE # 8
OHL Substation: DOHA SOUTH SS 400KV

6. RECORD TEST SHEET

6.1 DIFFERENTIAL PROTECTION END TO END TESTS

6.1.1 COMMUNICATION STATISTICS (MiCOM P544 only)

Channel One (1)


Propagation delay time (ms)
Error Messages
Valid Messages

6.1.2 COMMUNICATION CHECK


Loss of channel RESULTS
(OK/KO)
Alarm on relay after 10sec
CH 1 Tx Removed
Alarm on remote end
Alarm on relay after 10sec
CH 2 Tx Removed
Alarm on remote end
Alarm on relay after 10sec
CH 1 & CH 2 Tx Removed
Alarm on remote end

6.1.3 MEASUREMENT CHECK


Current applied in: DSS
Relay measured value on HMI in: DSS side
Curren Applied Expected Local Remote Differential
Bias Current
t current value Current Current Current
Ia (A) 0.1 200
Ib (A) 0.3 600
Ic (A) 0.5 1000

AREVA T&D GCCIA / SNCL


Signature Signature

Name Name
Date Date
Doc. No. REV-0 Page 6 of 10
Gulf Cooperation Council
Interconnection Authority
GCCIA

Engineer

GCC Interconnection Project - Phase I


TRANSMISSION & DISTRIBUTION
END TO END Test Report Bay Ref : Q01 – SALWA LINE # 8
OHL Substation: DOHA SOUTH SS 400KV

Relay measured value on HMI in: SALWA side


Curren Applied Expected Local Remote Differential
Bias Current
t current value Current Current Current
Ia (A) 0.1 200
Ib (A) 0.3 600
Ic (A) 0.5 1000

Current applied in: SALWA side


Relay measured value on HMI in: SALWA side
Curren Applied Expected Local Remote Differential
Bias Current
t current value Current Current Current
Ia (A) 0.1 200
Ib (A) 0.3 600
Ic (A) 0.5 1000

Relay measured value on HMI in: DSS side


Curren Applied Expected Local Remote Differential
Bias Current
t current value Current Current Current
Ia (A) 0.1 200
Ib (A) 0.3 600
Ic (A) 0.5 1000

6.1.4 PICK UP TEST OF DIFFERENTIAL PROTECTION

Injected from Injected from


DSS SALWA Expected
Current
Remote end Local Remote end Local value (pu)
SALWA DSS DSS SALWA
Ia (A)
Ib (A)
Ic (A)

AREVA T&D GCCIA / SNCL


Signature Signature

Name Name
Date Date
Doc. No. REV-0 Page 7 of 10
Gulf Cooperation Council
Interconnection Authority
GCCIA

Engineer

GCC Interconnection Project - Phase I


TRANSMISSION & DISTRIBUTION
END TO END Test Report Bay Ref : Q01 – SALWA LINE # 8
OHL Substation: DOHA SOUTH SS 400KV

6.1.5 COMMUNICATION FAIL BLOCKING TEST

1- CH1 in service , CH2 in service : Injected current 0,5A in R phase


Injected from Injected from
DSS SALWA results
Remote end Local Remote end Local
Trip Trip Trip Trip

2- CH1 in service , CH2 out of service : Injected current 0,5A in R phase

Injected from Injected from


DSS SALWA results
Remote end Local Remote end Local

Trip Trip Trip Trip

3- CH1 out of service, CH2 in service: Injected current 0,5A in R phase


Injected from Injected from
DSS SALWA results
Remote end Local Remote end Local
Trip Trip Trip Trip

4- Both CH1 & CH2 out of service: Injected current 0,5A in R phase
Injected from Injected from
DSS SALWA results
Remote end Local Remote end Local
No Trip No Trip No Trip No Trip

AREVA T&D GCCIA / SNCL


Signature Signature

Name Name
Date Date
Doc. No. REV-0 Page 8 of 10
Gulf Cooperation Council
Interconnection Authority
GCCIA

Engineer

GCC Interconnection Project - Phase I


TRANSMISSION & DISTRIBUTION
END TO END Test Report Bay Ref : Q01 – SALWA LINE # 8
OHL Substation: DOHA SOUTH SS 400KV

6.1.6 CHECKING OF INTER TRIP FUNCTION


I diff Settings(A) Injected Current(A) TRIP LED
DSS SALWA DSS SALWA DSS SALWA DSS SALWA
0.5(temp) 0.35 0.45 -
0.35 0.5(temp - 0.45
)

6.2 DISTANCE PROTECTION END TO END TESTS

6.2.1 Aided Zone 2 scheme Test:


(Note: In case of Fault on Z2 with Signal received from remote end, Z2 will be accelerated).
Result Result Result
Item Description
FOTE 1 FOTE 2 PLCC
POR Send signal from Zone
1 NA
2
POR Received signal from
2 NA
Remote side.
Z2Time (with Receive signal)
3 NA
( Aided 1 Trip)
Z2 Time (without Receive
4
signal)

6.2.2 Aided Earth fault scheme Test:


(Note: In case of Fault on Z2 with Signal received from remote end, DEF will be accelerated).
Result Result Result
Item Description
FOTE 1 FOTE 2 PLCC
1 Send signal from DEF NA
Receive Signal from remote
2 NA
side
DEF Time (with Receive
3 NA
signal) ( Aided 2Trip)
DEF Time (without Receive
4
signal)

AREVA T&D GCCIA / SNCL


Signature Signature

Name Name
Date Date
Doc. No. REV-0 Page 9 of 10
Gulf Cooperation Council
Interconnection Authority
GCCIA

Engineer

GCC Interconnection Project - Phase I


TRANSMISSION & DISTRIBUTION
END TO END Test Report Bay Ref : Q01 – SALWA LINE # 8
OHL Substation: DOHA SOUTH SS 400KV

6.3 DIRECT INTERTRIP END TO END TEST :


Result Result Result
Item Description
FOTE 1 FOTE 2 PLCC
1 DTT Send signal NA
DTT Received signal from
2 NA
remote side

6.4 FINAL CHECKS

Item Description Result

1 All test equipment, leads, shorts and test block removed safely?
2 Disturbed customer wiring re-checked?
3 All commissioning tests disabled?
4 Circuit breaker operations counter reset?
5 Current counters reset?
6 Event records reset?
7 Fault records reset?
8 Disturbance records reset?
9 Alarms reset?
10 LEDs reset?

REMARKS
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………

END OF REPORT

AREVA T&D GCCIA / SNCL


Signature Signature

Name Name
Date Date
Doc. No. REV-0 Page 10 of 10