Professional Documents
Culture Documents
Contents
Series C Types JDB, JD, HJD Equipped with Type JT
Thermal-Magnetic Trip Unit
(Curve No. SC-4247-87D) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Series C Types JDC Equipped With Type JT
Thermal-Magnetic Trip Unit
(Curve No. SC-4248-87C) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
AB DE-ION Circuit Breakers
Series C types JDB, JD, HJD equiped with type JT thermal-magnetic trip unit
10000
2 hours
5000
1 hour
1000
maximum single pole trip
times at 25°C (note 1)
500 70 - 250A
100
1 minute
maximum
50
minimum
10
TIME IN SECONDS
Typical
Individual Pole
Trip Unit
1 Adjustments
Nameplate
10X ± 10%
5X ± 20%
0.5
0.1
0.05
interrupting rating
0.01 determines end of
curve
0.005
0.001
10 50 100 500 1,000 5,000 10,000 50,000 100,000
CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)
2 EATON CORPORATION Cutler-Hammer Series C Time-Current Curves for J-Frame Breakers Effective: September 2006
AB DE-ION Circuit Breakers
Series C type JDC equipped with type JT thermal-magnetic trip unit
10000
2 hour
5000
1 hour
1000
maximum single pole trip
times at 25°C (note 1)
500 70 - 250A
100
maximum
1 minute
50 minimum
10
TIME IN SECONDS
Typical
Individual Pole
Trip Unit
1 Adjustments
Nameplate
10X ± 10%
5X ± 20%
0.5
0.1
0.05
240V AC
0.005
0.001
10 50 100 500 1,000 5,000 10,000 50,000 100,000
CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)
UL is a federally registered trademark of Underwriters Laboratories Inc. Cutler-Hammer is a federally registered trademark of Eaton Corporation.