TECHNICAL DATASHEET
1130 1025 Enclosure
Operation Voltage 11 / Ö3 (±10%) (50-60 Hz) kV
Aux.
Insulation Level (B.I.L.) 7,2 / 20 / 60 kV
Electrical Characteristics
Terminal Box
Aux. Resistance Value @ 25°C 22,45 (± 10 %) Ω
A Terminal Rated Fault Current 200 A
Box
765
Resistance
Max. Resistance Variation ≤ 67 %
Resistor Material CrNi Stainless Steel -
Resistor Type Edgewound -
Removable Legs
(Optional) Incoming / Outgoing Terminal Bottom / Side -
B
Enclosure Protection Degree IP23 (Outdoor & Indoor) -
Enclosure
Front View Incoming Terminal (N) Side View G Enclosure Material 2 mm Hot Dip Galvanized Steel -
Expandable Rubber Painting / Min. Thickness --- -
Plate up to Ø89mm Net Weight ≈ 190 kg
INPUT (N) Current Transformer (s)
Lifting Lugs Inclined Roof
200/5 A, 5P10, 10 VA, 1 pc.
Single Line Diagram ---
1090 ---
Fixation Hole Voltage Transformer (s)
---
Ø13 Zig-Zag TR
---
Accessories
Stainless Steel From "11 kV 200 A 10 sec."
C Zig-Zag Transformer*
Disconnector Switch ---
Nameplate Lighting Arrester
Reference Drawing Number ---
Base of NGR GT.O.ZN.R.11V.02A.10T.YG.23.062
Grounding Transformer ---
1025
750
min. 300
IEEE Std C57.32a-2020
Main Standard
Porcelain Insulator (Amendment to IEEE Std C57.32-2015)
D 1150 Insulation (B.I.L) IEC 60071-1 & IEC 60071-2
Releated Standarts
Cable Holder Post Insulator (> 1kV) IEC 60273
Fixation to Concrete
Incoming Terminal Details (N) Insulated Bushing (> 1kV) IEC 60137
M12x100
Nut Removable Stainless Protection Degree IEC 60529
Isometric View Steel Bridge
Spring Washer Current Transformer IEC 61869-2
Washer Grounding Tag NGR Grounding Voltage Transformer IEC 61869-3
Terminal HV Switchgear & Controlgear IEC 62271 series
Concrete
Expansion Type M12 Lightning Arrester IEC 60099-4
min. 80