FOUNDATION-DIMENSIONING

Standard:

Concrete: C25/30

Reinforcement: BSt 550

LC 2 significant for Ground Pressure

LC 2 1 significant for Foundation Design

Working loads:

LC DA gam_f V [kN] H_x [kN] M_y [kNm] H_y [kN] M_x [kNm] UF Ground Comment
1 BS1 1.4 800.00 0.00 0.00 0.00 0.00 76 % Verification calculations OK
2 BS1 1.4 600.00 45.00 -80.00 0.00 0.00 96 % Verification calculations OK
3 BS1 - - - - - - - -
4 BS1 - - - - - - - -
5 BS1 - - - - - - - -
6 BS1 - - - - - - - -
7 BS1 - - - - - - - -
8 BS1 - - - - - - - -
9 BS1 - - - - - - - -
10 BS1 - - - - - - - -

Geometry - Foundation: Geometry - Member:

Height of foundation: h= 60 cm Width / Thickness: 40 cm


Edge distance reinf.: h_1= 5 cm Length: 40 cm
Width of foundation: b= 150 cm
Length of foundation: l= 150 cm
Height of socket: h_s = 20 cm
Type of foundation: In-situ concrete foundation

Soil Data:

Spec. weight of the ground γb= 20.00kN/m³


Angle of friction: φ= 30.00 °
Cohesion: c= 5.00kN/m²
Covering: h_ü= 0.30m
Weight: γü= 20.00kN/m³
Ground water: h_w = 20.00m
Member: Standard: ÖN B 1997-1-2 (ground failure)

Position Concrete: C25/30

Load Case: 1 Reinforcement: BSt 550

LC DA gam_f V [kN] H_x [kN] M_y [kNm] H_y [kN] M_x [kNm] UF Ground Comment
1 BS1 1.4 800.00 0.00 0.00 0.00 0.00 76 % Verification calculations OK

Results - Soil Mechanics: [LC 1]

Calc. width of the foundation: b= 130.20 cm


Calc. length of the foundation: l= 104.40 cm 55 cm 55 cm
Calc. base of the foundation: A‘ = 2.51 m²
Force eccentricity x (from found.middle): e x= 0.00 cm

10
Force eccentricity y (from found.middle): e y= 0.00 cm

30 cm
Angle of ground friction (Design value): φd = 40.68 °

20
Cohesion of the ground (Design value): cd = 5.53 kN/m²
Coefficient general case: Ng= 6.393 -
Nq= 14.436 -
Nc= 39.809 -

60 cm
Coefficient master case: N γ,0 = 12.618 -
Nq= 26.810 -
Coefficient force slope: i γ= 1.480 - R
iq= 0.917 -
ic= 0.968 -
Coefficient foundation: s γ= 0.634 -
sq= 1.571 -
sc= 1.804 -
376 376
Angle horizontal force component: κ= 112.50 °
Coefficient: m= 1.982 -

Proof - safety against sliding: UF


✔ tan δ d / tan δ s ≥ 1 0.465 / 0.000 ≥1 0%
150 cm

Proof - Bearing Pressure:


Shear failure load (Design value) Bearing force (D.v.) UF 376 376
✔ Qfd = 1845.54 kN > Qd = 633.54 kN 78 %
55

40 cm
Results - Foundation Design:

unreinforced construction not possible

Design loads - Foundation range: R


150 cm

40 cm

V_d [kN] H_xd [kN] M_yd [kNm] H_yd [kN] M_xd[kNm]


x
x 953.12 0.00 0.00 0.00 0.00 [LC 1]
y 1424.64 0.00 0.00 0.00 0.00 [LC 1]

Design moment of the column section: a sy


M Bem,x = 141.05 kNm
55

M Bem,y = 141.62 kNm a sx


Statically relevant Reinforcement: as,erf,x = 4.12 cm² [LC 1]
as,erf,y = 3.93 cm² [LC 1]
376 376

y
Nominal / Maximum Reinforcement: As,min,x = 13.71 cm²
As,max,x = 380.52 cm²
As,min,y = 9.98 cm²
As,max,y = 529.20 cm² Results - punching shear:
Distribution of reinforcement:
Compact building element: crit. circumference out of foundation !
x-direction progressive distribution is necessary (see literature)
No punching proof required
y-direction progressive distribution is necessary (see literature)
Member: Standard:

Position Concrete: C25/30

Load Case: 2 Reinforcement: BSt 550

LC DA gam_f V [kN] H_x [kN] M_y [kNm] H_y [kN] M_x [kNm] UF Ground Comment
2 BS1 1.4 600.00 45.00 -80.00 0.00 0.00 96 % Verification calculations OK

Results - Soil Mechanics: [LC 2]

Calc. width of the foundation: b= 61.98 cm


Calc. length of the foundation: l= 120.90 cm 55 cm 55 cm
Calc. base of the foundation: A‘ = 1.49 m²
Force eccentricity x (from found.middle): e x= 23.05 cm

10
Force eccentricity y (from found.middle): e y= 0.00 cm

30 cm
Angle of ground friction (Design value): φd = 24.12 °

20
Cohesion of the ground (Design value): cd = 3.83 kN/m²
Coefficient general case: Ng= 5.393 -
Nq= 29.880 -
Nc= 23.656 -

60 cm
Coefficient master case: N γ,0 = 9.665 -
Nq= 16.285 -
Coefficient force slope: i γ= 1.180 - R
iq= 0.630 -
ic= 1.058 -
Coefficient foundation: s γ= 0.609 -
sq= 1.327 -
sc= 1.149 -
378 378
Angle horizontal force component: κ= 0.00 °
Coefficient: m= 1.050 -

Proof - safety against sliding: UF


✔ tan δ d / tan δ s ≥ 1 0.742 / 0.045 ≥1 11 %
150 cm

Proof - Bearing Pressure:


Shear failure load (Design value) Bearing force (D.v.) UF 378 378
✔ Qfd = 1090.33 kN > Qd = 633.34 kN 72 %
55

40 cm
Results - Foundation Design:

unreinforced construction not possible

Design loads - Foundation range: R


150 cm

40 cm

V_d [kN] H_xd [kN] M_yd [kNm] H_yd [kN] M_xd[kNm]


x
x 968.52 77.80 -148.43 0.00 0.00 [LC 2]
y 440.16 90.47 -173.93 0.00 0.00 [LC 2]

Design moment of the column section: a sy


M Bem,x = 68.36 kNm
55

M Bem,y = 121.80 kNm a sx


Statically relevant Reinforcement: as,erf,x = 8.38 cm² [LC 2]
as,erf,y = 2.95 cm² [LC 2]
378 378

y
Nominal / Maximum Reinforcement: As,min,x = 7.49 cm²
As,max,x = 220.68 cm²
As,min,y = 10.33 cm²
As,max,y = 476.28 cm² Results - punching shear:
Distribution of reinforcement:
Compact building element: crit. circumference out of foundation !
x-direction progressive distribution is necessary (see literature)
No punching proof required
y-direction progressive distribution is necessary (see literature)