Standard:
Concrete: C25/30
Working loads:
LC DA gam_f V [kN] H_x [kN] M_y [kNm] H_y [kN] M_x [kNm] UF Ground Comment
1 BS1 1.4 800.00 0.00 0.00 0.00 0.00 76 % Verification calculations OK
2 BS1 1.4 600.00 45.00 -80.00 0.00 0.00 96 % Verification calculations OK
3 BS1 - - - - - - - -
4 BS1 - - - - - - - -
5 BS1 - - - - - - - -
6 BS1 - - - - - - - -
7 BS1 - - - - - - - -
8 BS1 - - - - - - - -
9 BS1 - - - - - - - -
10 BS1 - - - - - - - -
Soil Data:
LC DA gam_f V [kN] H_x [kN] M_y [kNm] H_y [kN] M_x [kNm] UF Ground Comment
1 BS1 1.4 800.00 0.00 0.00 0.00 0.00 76 % Verification calculations OK
10
Force eccentricity y (from found.middle): e y= 0.00 cm
30 cm
Angle of ground friction (Design value): φd = 40.68 °
20
Cohesion of the ground (Design value): cd = 5.53 kN/m²
Coefficient general case: Ng= 6.393 -
Nq= 14.436 -
Nc= 39.809 -
60 cm
Coefficient master case: N γ,0 = 12.618 -
Nq= 26.810 -
Coefficient force slope: i γ= 1.480 - R
iq= 0.917 -
ic= 0.968 -
Coefficient foundation: s γ= 0.634 -
sq= 1.571 -
sc= 1.804 -
376 376
Angle horizontal force component: κ= 112.50 °
Coefficient: m= 1.982 -
40 cm
Results - Foundation Design:
40 cm
y
Nominal / Maximum Reinforcement: As,min,x = 13.71 cm²
As,max,x = 380.52 cm²
As,min,y = 9.98 cm²
As,max,y = 529.20 cm² Results - punching shear:
Distribution of reinforcement:
Compact building element: crit. circumference out of foundation !
x-direction progressive distribution is necessary (see literature)
No punching proof required
y-direction progressive distribution is necessary (see literature)
Member: Standard:
LC DA gam_f V [kN] H_x [kN] M_y [kNm] H_y [kN] M_x [kNm] UF Ground Comment
2 BS1 1.4 600.00 45.00 -80.00 0.00 0.00 96 % Verification calculations OK
10
Force eccentricity y (from found.middle): e y= 0.00 cm
30 cm
Angle of ground friction (Design value): φd = 24.12 °
20
Cohesion of the ground (Design value): cd = 3.83 kN/m²
Coefficient general case: Ng= 5.393 -
Nq= 29.880 -
Nc= 23.656 -
60 cm
Coefficient master case: N γ,0 = 9.665 -
Nq= 16.285 -
Coefficient force slope: i γ= 1.180 - R
iq= 0.630 -
ic= 1.058 -
Coefficient foundation: s γ= 0.609 -
sq= 1.327 -
sc= 1.149 -
378 378
Angle horizontal force component: κ= 0.00 °
Coefficient: m= 1.050 -
40 cm
Results - Foundation Design:
40 cm
y
Nominal / Maximum Reinforcement: As,min,x = 7.49 cm²
As,max,x = 220.68 cm²
As,min,y = 10.33 cm²
As,max,y = 476.28 cm² Results - punching shear:
Distribution of reinforcement:
Compact building element: crit. circumference out of foundation !
x-direction progressive distribution is necessary (see literature)
No punching proof required
y-direction progressive distribution is necessary (see literature)