Hasil Uji Incoming 20 Trafo 2 GI Sirimau
Hasil Uji Incoming 20 Trafo 2 GI Sirimau
Job # 06 Ambient °C
30
Temperature
Asset ID UPK Maluku Humidity 20.00 %
Comment:
Test results
localhost:59721/?fileport=49199#%2520&ui-state=dialog 1/3
9/25/2020 TRAX - Test report
Circuit Breaker
Open
Parameters Values
Open time A 44.35 ms
Open time B 44.41 ms
Open time C 44.46 ms
Open time RA 44.35 ms
Open time RB 44.41 ms
Open time RC 44.46 ms
Open time 44.46 ms
Diff A-B-C 0.11 ms
Pk current 1.730 A
O contr. V 109.2 V
0 ms
0 ms
0 ms
0 ms
0 ms
0 ms
Close
Parameters Values
Close time A 54.36 ms
Close time B 54.25 ms
Close time C 54.27 ms
Close time RA 54.35 ms
Close time RB 54.24 ms
Close time RC 54.26 ms
Close time 54.36 ms
Diff A-B-C 0.11 ms
Pk current 1.707 A
41.78 ms
3.75 ms
51.31 ms
41.78 ms
3.76 ms
51.31 ms
localhost:59721/?fileport=49199#%2520&ui-state=dialog 2/3
9/25/2020 TRAX - Test report
Comment:
Contact Resistance
Notes Current Measured resistance Voltage
PHASA R 50.0 A 35.15 µΩ 1.757 mV
PHASA S 50.0 A 35.28 µΩ 1.764 mV
PHASA T 50.0 A 34.60 µΩ 1.730 mV