hot water return circulation pump

input data
flow rate
pipe size 3"
fitting (elbow)3"
balance valve 3"
NRV 3"
gate valve
pressure reducing valve

pump room fitting


strainer
balance valve
gate valve

10 l/s @ 3" pipe presure drop


elbow

out put data

total pressur drop in pipe


total pressure drop fitting
total valve 8 nos. consider 0.5 metre each

total calculated pressure drop


pump pressure -proposed
hosbital 330 m X 160 m X 30 m hight

10 l/s
300 m
20 nos.
1
1
2
0

1
1
2

5.8 ft/100 ft
0.25 ft

56.55 m
5 m
4 m

65.55 m
16 m
prim 70
pi 3.14
d 22.29299
Basment level
pipe 75 mm 151 m
elbow 75 mm 8 nos
T 75 mm 1 nos
reducer 2"/3" 1 nos.
elbow 2.5 " 6 nos.
pipe 2.5" 72 m

GF lvel or 2nd floor


total pipe lenth (50, 30 m
total pipe lenth 32 30 m
total pipe lenth 25 , 20 m
total pipe lenth 20 mm ) 20 m

gate valve 2' 1 No


check valve 2" 1 No
tee 2" 1 No
red 50/32 mm 1 No
Tee 32 mm 1 No
red 32/25 1 No
elbow 25 4 No
elbow 20/25 1 No
elbow 20 6 No
Tee 20 1 No
T 32/20 through branch 2 No
T 32/25 through branch 1 No
T 25/20 through branch 6 No
T 20 through branch 2 No
gate valve 20 mm 1 No
balance valve 20 mm 1 No
check valve 20 mm 1 No

Riser
pipe 2.5" 10 m
pipe 3" 10 m
pipe 2" 10 m
reducer 2.5/2" 1 No
reducer 3"/2.5" 1 No
CUP bulding and tunnel
pipe 75 mm 176 m
elbow 3" 32 no
summery
pipe 550 m
friction rate 5.8 ft /100 ft
fitting 100 no
valve 5 no
friction fitting losses rate 0.3 ft
total pipe f 31.9
fitting 9.23076923076923
valve 5