Professional Documents
Culture Documents
sensitivity ratio. For example, for helium, if the system pressure before helium was introduced was 1 ×
10-7 torr and then increased to 1.1 × 10-6 torr due to introduction of helium, the actual helium pressure
will be
6(1.1 × 10-6 - 1 × 10-7) = 6 × 10-6 torr
Sensitivity for helium is approximately six times lower than for nitrogen. The justification for subtracting
the residual pressure, which exists prior to the experiment, can be assertained by noting the meaning of
the ultimate pressure in Eq. (4.17), Section 4.4.
The calibration of high- and ultrahigh-vacuum gauges is not done by a simple and straightforward
procedure because the amount of matter available for measurement is extremely small. Normally,
commercially available gauges are not calibrated.
Typically, the high-vacuum ionization gauges with external collectors (triodes) will have a variation of
about 5% in sensitivity even if purchased from the same manufacturer. The ultrahigh-vacuum gauges
with internal collectors may have a total variation of 10 to 20%. It is only in the last 15 years that well-
established calibration procedures have been developed in standards laboratories in several countries that
have a substantial vacuum industry (including the U.S. National Institute of Science and Technology).
The calibration service for a gauge tube (transducer) and the associated controller will more than double
the price of the instrument.
In industrial practice, one encounters two types of vacuum technologists. Some insist on recording
pressure readings with three-place decimal accuracy. The digital meters are particularly seductive in this
respect. Others insist that
Figure 12.15
Figure 12.16
envelope.
Figure 12.17
gauge locations.
der transient conditions, during evacuation, the upper gauge may read 10 or 100 times higher pressure
after the valve is opened. This is because the gauge has been exposed to atmosphere and has excessive
quantities of gas on its surfaces, subsurface pores, and oxide layers. A period of time (few minutes to a
few hours, depending on the pressure level) and degassing of the gauge are required before the expected
factor of 2 or 3 ratio between the two gauges is established.
Another important consideration is the general location of the gauge in a system. The distribution of
pressure (or density) of the gas in a system at high vacuum is rarely uniform. In the system shown in
Figure 12.18, gauge 1 should read a higher pressure than gauge 2, because gauge 2 is downstream toward
the pump, gauge 1 is affected by the additional outgassing (and possibly permeation) from the large O-
ring in the door and because there is a large object
Figure 12.18