You are on page 1of 8

The potential of phase change materials in

mitigating cooling load of buildings in UAE


..............................................................................................................................................................

Yasir Rashid† , Mohammed Ziauddin, Bobby Mathew and Fadi Alnaimat*


Department of Mechanical Engineering, United Arab Emirates University, Al Ain 15551,

Downloaded from https://academic.oup.com/ijlct/article-abstract/14/4/568/5593704 by Universidad del Norte user on 04 February 2020


United Arab Emirates
............................................................................................................................................
Abstract
Integration of phase change materials (PCM) into building elements is explored extensively in the last decade
to reduce air-conditioning demand for indoor thermal comfort. The PCM could absorb and release thermal
energy as latent heat in a narrow temperature range. Several experimental studies reported energy saving
and indoor temperature drop in summer conditions. However, the matter is sparsely researched in the
environment of the United Arab Emirates (UAE), a region of high heat flux throughout the year. The current
research provides an overview of the integration of PCM in buildings for indoor thermal comfort and energy
saving in the UAE. The research highlights the problems of building-integrated photovoltaics (BIPV), e.g.
efficiency drop. The significance of the PCM application in the built environment and its research gap is
highlighted by reporting all the previous findings on the topic including the application of PCM in glazing,
concrete and BIPV.

Keywords: building energy efficiency; indoor thermal comfort; building-integrated photovoltaics; phase
change materials
∗ Corresponding author:

falnaimat@uaeu.ac.ae Received 14 February 2019; revised 26 April 2019; accepted 19 June 2019
................................................................................................................................................................................

1 INTRODUCTION but still it transmits heat indoors significantly. Figure 1 shows


the representation of double-layered glazing with an air cavity
Buildings consume almost 40% of the global energy consumption, in between the two transparent glass layers [3]. It represents
of which roughly 80% is used in air conditioning (heating/cooling how heat is lost from indoor thermally comfortable space to the
based on the climatic conditions) [1]. According to an estimate, outdoor cold environment. Exactly opposite mechanism happens
cooling load in Al Ain city of United Arab Emirates (UAE) will in hot climates where heat is transmitted from outside to inside
increase by 23% based on the increase in ambient temperature causing thermal discomfort.
by 5.9◦ C due to global warming [2]. There is an urgent need to One option to improve the thermal characteristics of glazing is
reduce energy consumption in buildings. Glazing is an important to add transparent phase change materials (PCM) in between two
building component that has the maximum thermal transmit- layers of glazing. Building envelops, another building component,
tance value (U-value) among other elements, but the presence play a vital role in energy demand of the building because these
of glazing in the design of buildings cannot be compromised. components are the first barrier between the indoor thermal
U-value of single glazing may go up to 4.8 W/m2 K, which is comfort zone and outdoor harsh environment. The contribution
significantly higher than the recommended values for building of facades in the energy performance of the building is more
materials [3]. For instance, the U-value of 10-cm thick fiberglass significant in high rise buildings, which is obvious due to
insulation is 0.4 W/m2 K [3]. The higher is the U-value, the poor is higher facade surface area compared to roof [4]. Desired
the material in isolating indoor environment from harsh outdoor functions of a building facade are ventilation, natural and
climatic conditions. More precisely, U-value is the measure of uniform daylighting, visibility to outdoor for psychological effects
thermal energy transfer per unit area across the materials with and reduced solar heat gain indoor. On the other side, the
the difference of 1◦ C on both sides, so a lesser is the U-value, esthetics of the facades is the demand for architecture. In a
greater is its thermal insulation property. However, double glazing practical scenario, all these desired characteristics may be
and triple glazing concept have reduced the U-value of glazing, contradicting. The solution is to find an optimal way that fits best

† YasirRashid, http://orcid.org/0000-0002-0984-6489
International Journal of Low-Carbon Technologies 2019, 14, 568–575
© The Author(s) 2019. Published by Oxford University Press.
This is an Open Access article distributed under the terms of the Creative Commons Attribution License (http://creativecommons.org/licenses/by/4.0/), which
permits unrestricted reuse, distribution, and reproduction in any medium, provided the original work is properly cited.
doi:10.1093/ijlct/ctz042 Advance Access publication 18 October 2019 568
The potential of phase change materials

2 APPLICATION OF PCM IN THE BUILT


ENVIRONMENT OF UAE
The subsequent sections include the climatic conditions of the
UAE and the amount of energy consumption in the residential
sector. It also summarizes different methodologies to use PCM
to reduce indoor cooling load demand and to reduce surface
temperature.

Downloaded from https://academic.oup.com/ijlct/article-abstract/14/4/568/5593704 by Universidad del Norte user on 04 February 2020


2.1 Energy requirement in buildings of the UAE
Climatic conditions of the UAE are very harsh, and the condition
is considered an arid climate. Temperatures in summer in the
coastal cities rise up to 48◦ C with the humidity level of 90%,
while in southern cities like Al Ain, the temperature may go up
to 50◦ C. Figure 2 shows the yearly weather data of Al Ain city
in UAE including solar radiation, air temperature and relative
humidity issued by the Directorate of Meteorology of Abu Dhabi
[15]. The mean air temperature remains in the range of 32.2–
35.5◦ C from April to September. The air temperature of coastal
Figure 1. Heat loss mechanism through glazing in cold climate [3]. cities (Dubai and Abu Dhabi) is estimated much higher than
this due to building materials, congestion, less foliage, multiple
reflections of radiations, anthropogenic heat caused by vehicles
to the esthetics and functionality of the building. Furthermore, and air conditioning. Further, the effect of high levels of humidity
the solution suits best for energy saving. Efforts are made to makes the living conditions worst to breathe in. The region has a
optimize the building facades for energy saving by offering lot of potentials to harness solar energy because of its availability
different designs including double skin facades [5], ventilated around the year. The range of the monthly average total solar
facade [6], opaque multilayer facade [6], inclusion of insulation radiation is 375 W/m2 in December to 590 W/m2 in June as shown
and thermal mass [4], facade albedo [7], integration of PCM [8], in Figure 2.
photovoltaic (PV)-integrated facades [9] and modular building According to a report, above 37% of the total energy in UAE
facades [10]. is consumed in residential buildings only [16] as shown in
Building-integrated photovoltaics (BIPV) technology is replac- Figure 3. The proportion of energy consumption in the residential
ing conventional building envelopes, and it has the potential sector increased at a rate of 4% from 2009 to 2014. Further, it
to produce 840 terawatt hours of electricity, which is almost is predicted that the proportion of energy use in the building
22% of European 2030 annual electricity demand [11]. Ventilated sector will increase at the rate of 5% till 2020, making an
BIPV has been investigated for thermal management of PV to overall energy consumption of 56.4 terawatt hours in residential
enhance its conversion efficiency. A temperature drop of 5–10◦ C buildings only [16], indicating a quick response to curtail the
is reported in the case of natural ventilated BIPV as compared issue.
to the conventional BIPV [12]. A recent study investigated the
combined effect of the installation of heat pipe-based building
facade-integrated PV-thermal system in the climatic conditions of
Hong Kong. Newly designed facade can reduce heat transmission
by 23.2% annually as compared to the conventional brick wall.
The thermal and electrical efficiency of the system was 34.7 and
9.8%, respectively [13].
PCM have the potential to absorb and release a large amount of
energy in a very narrow temperature range due to its latent heat
of fusion [14]. The materials are least investigated in the climatic
conditions of UAE, although the energy consumption per capita
of UAE is ranked in top countries. The paper summarizes the
results of the experimental studies conducted in the UAE and
highlights the research gaps to be addressed by the researchers.
The paper advocates the need for further research in the applica-
tion of PCM in buildings for energy conservation. Figure 2. Weather data of Al Ain, UAE [15].

International Journal of Low-Carbon Technologies 2019, 14, 568–575 569


Y. Rashid et al.

Downloaded from https://academic.oup.com/ijlct/article-abstract/14/4/568/5593704 by Universidad del Norte user on 04 February 2020


Figure 3. Total electricity consumption and residential percentage of the total [16].

2.2 Classification of PCM to indoor space as compared to the building without PCM and
Primarily, PCMs are categorized into organic, inorganic and hence increasing the indoor air-conditioning demand.
eutectics. Organic PCMs include paraffins and non-paraffins,
while inorganic PCMs include salt hydrates and metallics.
Eutectics could be mixture of organics and inorganics [14]. 2.3 Application of PCM in glazing
Desired characteristics of the PCMs for buildings and investigated The use of PCM in windows and glazing is least studied in
materials among all categories are summarized in [14] with the UAE. However, it has the potential to decrease U-value; hence,
associated advantages and disadvantages of each. The phase it can reduce heat transmission. The only experimental study by
transition temperature of the most of these materials is available Jain and Sharma [17] investigated the use of transparent PCM
in the operation range of buildings. An important feature in PCM in window to reduce heat gain indoors without compromising
for building application is the selection of melting point of PCM. the transparency function of the windows. Experimental set-
Ideally, the melting point should be as close to the required indoor up of the research is shown in Figure 4. The effect of thickness
thermal comfort as possible. However, in hot climate, PCM with ranging from 4 to 30 mm on the transmittance of natural
this much melting point (let say 27◦ C) may not regenerate itself light was investigated with the additional benefits of damping
for next cycle during night-time. Eventually, if the PCM is in and delaying heat loads [17]. Solar transmittance decreased
liquid state before the start of next day, it will transfer more heat by almost 7.7% by increasing thickness from 4 to 30 mm.

Figure 4. Experimental set-up for transparent glazing incorporating PCM [17].

570 International Journal of Low-Carbon Technologies 2019, 14, 568–575


The potential of phase change materials

Transparency of the PCM is still better than water at the thickness 2.4 Use of PCM in concrete
of 15 mm. Additionally, the transparency level of the PCM The application of PCM in a multilayered arrangement in concrete
is almost equivalent to that of toughened glass with low iron blocks without proper caging/leak proofing is investigated in out-
content [17]. The idea has a lot of potential in energy saving door experiments in Al Ain, UAE [19, 20]. It is not recommended
and passive thermal management of the building; however, to use PCM in concrete because it leaks in the liquid state
the concept has not been investigated in depth to include causing structural instability and vulnerability to fire. The research
other influencing parameters including diurnal and seasonal investigated the effect of the placement of the PCM layer among
performance. other layers of polystyrene insulation and air cavity on the back-
Giovannini et al. modeled double-glazed window for visual surface temperature of concrete blocks and on the reduction of

Downloaded from https://academic.oup.com/ijlct/article-abstract/14/4/568/5593704 by Universidad del Norte user on 04 February 2020


comfort integrating PCM for the climatic conditions of Abu indoor temperature. Schematic diagram and experimental set-up
Dhabi. The simulation was carried out considering the solid state are shown in Figure 5. One of the small chambers was reference
of the PCM only because the optical properties of liquid PCM called chamber A without PCM, while the other two chambers
are quite similar to that of specular glass. Input conditions to with different position of PCM layer were named chambers B and
the model were a south-facing wall with glazing at the clear sky C. The temperature profiles and energy saving for these chambers
day. The study reported that the PCM transmitted more daylight were denoted by the subscripts of α, β and γ , respectively.
to the indoor space as compared to the specular glass [18]. The Figure 6 represents the drop in indoor temperature in the case
authors stated that the increase in daylight transmission did not of chambers B and C as compared to chamber A. The curves
increase the visual comfort at different geographical latitudes. It are an average of 14-day experimental data. At 07:00, indoor
was observed that the zenith angle and sun position have more temperature in the reference chamber was less than the other two
effect on visual comfort as compared to the geographical location because of the heat retention in the previous night, which is a
and climatic conditions [18]. typical function of PCM if not regenerated properly.

Figure 5. Schematic diagram and the experimental set-up of the concrete blocks, with construction layers and the test chamber [19].

International Journal of Low-Carbon Technologies 2019, 14, 568–575 571


Y. Rashid et al.

damping and delaying was investigated by Ghazal and Zurigat


[22]. By mimicking climatic conditions of UAE to the model,
the system was developed. The research reported that the peak
cooling load can be delayed by 3 hours, and the magnitude of the
peak can be reduced by 5.2 W/m2 [22]. Ghazal et al. modeled the
integration of microencapsulated PCM into concrete as a layer to
reduce the thickness of the standard insulation material without
altering the energy-saving capacity of the insulation [23]. Three
standard insulations were compared with the application of PCM,

Downloaded from https://academic.oup.com/ijlct/article-abstract/14/4/568/5593704 by Universidad del Norte user on 04 February 2020


and the research concluded that 0.5% PCM addition can reduce
the thickness of insulation material (16, 11 and 6 cm for all direc-
tions) by 5, 4 and 2 cm, respectively [23]. The problem of PCM
leakage was resolved by developing a novel coating layer around
PCM-filled expanded clay matrix. The efficacy of the coating layer
was evaluated rigorously, which confirmed it for the application in
buildings [24, 25]. The use of PCM was also compared with waste
materials for its effectiveness in reducing heating/cooling load of
buildings in the extreme weather conditions [26].
Recently, PCM RT-31 procured from Rubitherm, Germany,
was encapsulated into geopolymer with the intended purpose of
robust coating and leak proofing of the PCM in molten state
Figure 6. Evolution of the indoor temperature for the reference chamber A (Tαi), [24, 25]. In one set of experiments, lightweight expanded clay
chamber B (Tβi) and chamber C (Tγ i) for an average of the 14 days, while was used to absorb PCM in its porous structure and eventually
the difference of the indoor temperatures of the test chambers B and C from the coated with geopolymer [27]. While in the other experiments, the
reference chamber is presented in the corresponding inset graphs [19].
PCM was absorbed in polyurethane foam and eventually coated
with geopolymer [28]. These developed capsules were embedded
in geopolymer concrete to investigate the reduction in thermal
However, the temperature started lagging for chambers B and transmittance. It was reported that PCM capsules in expanded
C with the value of 0.3 and 1 hour, respectively, due to higher clay reduced the thermal transmittance (U-value) of the geopoly-
thermal mass of concrete exploiting the latent heat of fusion effect mer concrete from 2 to 0.9 W/m2 K [27]. Using PCM capsules
of PCM. Indoor temperature drop in blocks B and C with respect in polyurethane matrix, the U-value was reduced from 2 to 1.1
to B was 1.4 and 3.1◦ C, respectively. As revealed in the inset graph, W/m2 K [28].
the magnitude of temperature drop through multilayered block C The impact of PCM on the energy saving by reducing cool-
was much higher during day time, but it was negative during the ing load in hot climate was theoretically calculated by Rashid
night. In block B, the magnitude of temperature drop was less, et al. recently based on the experimental investigation using two
but it was always positive. The results imply that configuration
C can be used effectively for office buildings with night-time
natural ventilation of building, while configuration B is helpful in
reducing cooling load in all type of buildings.
Elnajjar modeled brick containing PCM by feeding ambient
conditions of UAE to the model [21]. The effects of different melt-
ing point of PCM on energy efficiency, peak temperature shaving
and peak shifting were investigated. The research analyzed 1-day
simulation and continuous 7-day simulations and reported that
the results for 1-day simulation were misleading [21]. According
to 1-day results, n-octadecane (nO-27, with a melting point of
27◦ C) performed best among all. However, the actual results were
totally opposite when simulated for consecutive 7 days. Cooling
load reduction in the case of different PCM can be observed in
Figure 7 where nO-27, nE-37 and P11-47 represent n-octadecane
with a melting temperature (T m ) of 27◦ C, n-eicosane with T m of
37◦ C and paraffin wax with T m of 47◦ C, respectively. It is evident
that the maximum energy consumption was in the case of original
brick while cooling load reduced by 10% for nO-27, 16% for nE- Figure 7. The daily indoor heat flux profile for a brick with different types of
37 and 30% for P11-47 [21]. The use of PCM for peak temperature PCM comparing to the reference case of brick without PCM [21].

572 International Journal of Low-Carbon Technologies 2019, 14, 568–575


The potential of phase change materials

degradation and reducing life span [29]. Energy performance of


PV decreases with the increase in temperature. For every 30◦ C rise
in temperature, 1–2% conversion efficiency of PV is dropped [29].
In the array system, rare side of the PV is in contact with
air, so heat is dissipated through convection and radiation. For
BIPV, more heat is accumulated because the PV module is stacked
onto building element without any air passage and heat is not
dissipated into the ambient through convection. Several ways are
investigated to mitigate this problem while the integration of PCM

Downloaded from https://academic.oup.com/ijlct/article-abstract/14/4/568/5593704 by Universidad del Norte user on 04 February 2020


is the most optimal solution. Hassan et al. conducted experiments
in Al Ain, UAE [8, 30], by integrating PCM container at the rare
side of BIPV and examined its effects on the surface temperature
drop of PV, enhancing the energy conversion efficiency of PV,
drop in indoor temperature and drop in indoor cooling demand.
Using PCM, the power output of the PV was increased by 7.2%
Figure 8. Monthly energy efficiency enhancement achieved by PV-PCM through at the maximum, while cooling effect was enhanced by 9.5% by
the PV cooling [32]. blocking the heat transmission to the indoor space [8]. In further
experiments, water was circulated through the PCM integrated
different PCMs, i.e. PCM-RT31 and PCM-RT42 [26]. RT31 and at the rare side of PV to extract thermal energy for water heating
RT42 had melting points of 31 and 42◦ C, respectively. Both were purposes. The system has benefits to drop the surface temperature
paraffin based and procured from Rubitherm, Germany. It was of PV and to exploit the thermal energy for additional benefits
reported that RT31 can reduce cooling load up to 45.4%, while [31]. In the year around experiments and simulated models, effi-
RT42 can reduce cooling load up to 43.3% in the climatic condi- ciency enhancement of PV in the range of 4.3% in May to 7.2% in
tions similar to the UAE [26]. October was achieved as shown in Figure 8 [32]. Table 1 provides
a succinct comparison of the studies that are conducted in the
multilayered concrete or PV-PCM system in the UAE.
2.5 Application of PCM in BIPV
The PV cells have a tendency to absorb 80% of the solar irradiance
that strikes the surface of PV. A small proportion of the absorbed 3 RECOMMENDATIONS AND FUTURE WORK
energy is converted into electricity and the residue is converted
into heat [29]. The generated heat is accumulated at the surface of Based on the critical review of the available literature, PCM has
PV resulting in lowering of power efficiency, accelerated thermal the potential to harness solar energy in an efficient way in the

Table 1. Summary of energy saving by the application of PCM.


PCM used Melting point Heat capacity Thermal PV efficiency Temperature Indoor cooling Thermal
(◦ C) (KJ/kg) conductivity enhancement drop load reduction energy
(W/m.K) harnessinga

BIPV-PCM [8] Paraffin-based 41 145 0.2 7.2% 5◦ C 9.5% NA


PCM RT-42
Layered concrete [19, 20] Paraffin-based 41 145 0.2 NA 8.5% 44% NA
PCM RT-42
Layered concrete [22] NA 27 33.5 0.17 NA NA 5.9 W/m2 , NA
3-hour
peak delay
Concrete embedded with Paraffin RT-31 31 110 0.2 NA 8◦ C NA NA
PCM capsules in expanded
clay [26]
Concrete embedded with Paraffin RT-31 31 110 0.2 NA 12.6◦ C NA NA
PCM capsules in
polyurethane foam [27]
Yearly PV-PCM [32] Paraffin-based 41 145 0.2 5.9% 13◦ C NA NA
PCM RT-42
BIPV-PCM with water Paraffin-based 41 145 0.2 1.3% 9◦ C NA 41%
circulation [31] PCM RT-42

a Water heating by circulating through PCM.

International Journal of Low-Carbon Technologies 2019, 14, 568–575 573


Y. Rashid et al.

United Arab Emirates, a region of high solar flux throughout the reduced the temperature up to 12.5◦ C on the back surface of
year. As the building facades and modern architecture demands concrete, which directly emits heat to the indoor space through
glass, the thermal transmittance of the windows and glazing could radiation and convection. Thermal transmittance (U-value) of the
be reduced with the application of transparent PCM in double- geopolymer is also reduced improving the insulation properties of
glazed or triple-glazed windows without affecting the func- the materials. Lastly, the impact of PCM integration into PV was
tionality of the glazing and without compromising the modern analyzed in UAE, which has proven to be an excellent technology
architecture. There are very limited studies on this subject, for conversion efficiency enhancement of PV (7.2% up) with
and it is recommended to explore it in fine detail. Several additional benefits of cooling enhancement (9.5% up) and water
studies investigated the use of PCM in multilayered concrete and heating. As the region of study is full of solar insolation around the

Downloaded from https://academic.oup.com/ijlct/article-abstract/14/4/568/5593704 by Universidad del Norte user on 04 February 2020


embedding PCM capsules into the concrete structure. However, year, remarkable benefits can be achieved with the advancement
the scale of the study is not comparable to the real-sized buildings. of this technology in the built environment.
In Spain, the potential of active and passive systems on energy
efficiency were tested experimentally on the real-sized cubicles
[33]. A similar scale research is needed to evaluate and benchmark
the options according to the climatic conditions and yearly FUNDING
temperature patterns of UAE.
The research was supported by the UAE University through the
Leakage of PCM is a critical problem in the application of start-up research grant (31N265).
PCM in buildings, which can reduce the building life. However,
the leakage problem is solved by coating the PCM capsules with
geopolymers. The coating is very robust and easily integratable REFERENCES
into the building materials with very strong interfacial bonding
[24]. Further refinement could be proposed to produce bulk [1] Sarbu I, Sebarchievici C. General review of ground-source heat pump sys-
tems for heating and cooling of buildings. Energ Buildings 2014;70:441–54.
production of PCM capsules as the currently devised method is [2] Radhi H. Evaluating the potential impact of global warming on the UAE
only for small-scale production. One most important problem in residential buildings – a contribution to reduce the CO2 emissions. Build
the application of PCM in UAE environment is the regeneration Environ 2009;44:2451–62.
of the PCM. In a case of improper selection of the PCM melting [3] The Open University. Energy and Sustainability. http://www.
point, the PCM may not solidify during night-time when ambient openuniversity.edu/courses/modules/t213 (21 April 2019, date last
accessed).
temperature at the night is higher than the congealing point of [4] Bojić M, Yik F. Cooling energy evaluation for high-rise residential build-
the PCM. In such scenario, PCM will affect adversely on building ings in Hong Kong. Energ Buildings 2005;37:345–51.
energy efficiency [19]. A proposed method is to design the air- [5] Ghaffarianhoseini A, Ghaffarianhoseini A, Berardi U et al. Exploring the
conditioning ducting system in a way that exhaust air of the advantages and challenges of double-skin façades (DSFs). Renew Sust Energ
buildings should pass over the building facades. The exhaust air is Rev 2016;60:1052–65.
[6] Guillén I, Gómez-Lozano V, Fran JM et al. Thermal behavior analysis of
normally at room temperature, which is significantly lower than different multilayer façade: numerical model versus experimental proto-
the congealing point of the PCM. This exhaust is also necessary for type. Energ Buildings 2014;79:184–90.
maintaining the good air quality, and it can serve the dual purpose [7] Wang X, Kendrick C, Ogden R et al. Dynamic thermal simulation of a retail
in this design. shed with solar reflective coatings. Appl Therm Eng 2008;28:1066–73.
[8] Hasan A, Alnoman H, Rashid Y. Impact of integrated photovoltaic-phase
change material system on building energy efficiency in hot climate. Energ
Buildings 2016;130:495–505.
4 CONCLUSION [9] O’Hegarty R, Kinnane O, McCormack SJ. Review and analysis of solar
thermal facades. Sol Energy 2016;135:408–22.
Integration of PCM into building elements in the climatic con- [10] Thalfeldt M, Pikas E, Kurnitski J et al. Facade design principles for nearly
ditions of UAE has been assessed. Through careful literature zero energy buildings in a cold climate. Energ Buildings 2013;67:309–21.
[11] Defaix PR, van Sark WGJHM, Worrell E et al. Technical potential for
survey, only two studies were found on the application of PCM photovoltaics on buildings in the EU-27. Sol Energy 2012;86:2644–53.
in glazing. Further, findings of both studies are contradicting to [12] Chiu MS, Hou SP, Tzeng CT et al. Experimental investigations on the
each other. The contradiction requires further in-depth investi- thermal performance of the ventilated BIPV wall. J Appl Sci 2015;15:613–8.
gation of the pertaining matter. Application of PCM in layered [13] Long H, Chow TT, Ji J. Building-integrated heat pipe photovoltaic/thermal
geometry of concrete is also investigated in the environment of system for use in Hong Kong. Sol Energy 2017;155:1084–91.
[14] Hassan A, Laghari MS, Rashid Y. Micro-encapsulated phase change mate-
UAE by numerical modeling and experimentations. However, the rials: a review of encapsulation, safety and thermal characteristics. Sustain-
scale of the experimental set-up used in the research was not ability 2016;8:1046.
comparable to that of real-sized buildings. Also, research was [15] Radhi H. 2010. On the effect of global warming and the UAE built
carried out for specific days, rather it should include all seasons environment. In Arthur S (ed). Global Warming. Sciyo. 95–110.
to cover diurnal and seasonal performance to ultimately calculate [16] Tayar A, Karlsson PO, Decker C et al. Energy Efficiency in the UAE
- Aiming for Sustainability. https://www.strategyand.pwc.com/me/report/
the yearly energy performance. It is reported that PCM has the energy-efficiency-in-uae (21 April 2019, date last accessed).
potential to reduce cooling load of buildings by 43% approxi- [17] Jain L, Sharma SD. Phase change materials for day lighting and glazed
mately. PCM capsules embedded into geopolymer concrete also insulation in buildings. J Eng Sci Technol 2009;4:322–7.

574 International Journal of Low-Carbon Technologies 2019, 14, 568–575


The potential of phase change materials

[18] Giovannini L, Goia F, Verso VRML et al. Phase change materials in glazing: [26] Rashid Y, Alnaimat F, Mathew B. Energy performance assessment of
implications on light distribution and visual comfort. Preliminary results. waste materials for buildings in extreme cold and hot conditions. Energies
Energy Procedia 2017;111:357–66. 2018;11:3131.
[19] Hasan A, Al-Sallal K, Alnoman A et al. Effect of phase change materials [27] Hassan A, Mourad AHI, Rashid Y et al. Thermal and structural perfor-
(PCMs) integrated into a concrete block on heat gain prevention in a hot mance of geopolymer concrete containing phase change material encapsu-
climate. Sustainability 2016;8:1009. lated in expanded clay. Energ Buildings 2019;191:72–81.
[20] Hasan A, Al-Sallal K, Alnoman H et al. Phase change materials (PCMs) [28] Hassan A, Rashid Y, Mourad AHI et al. Thermal and structural char-
integrated into concrete blocks to reduce cooling load in hot climate. acterization of geopolymer-coated polyurethane foam—phase change
In: International Conference on Zero Energy Mass Customised Housing, material capsules/geopolymer concrete composites. Materials 2019;
Kuala Lumpur, Malaysia, pp. 270–278. 12:796.

Downloaded from https://academic.oup.com/ijlct/article-abstract/14/4/568/5593704 by Universidad del Norte user on 04 February 2020


[21] Elnajjar E. Using PCM embedded in building material for thermal man- [29] Makki A, Omer S, Sabir H. Advancements in hybrid photovoltaic
agement: performance assessment study. Energ Buildings 2017;151:28–34. systems for enhanced solar cells performance. Renew Sust Energ Rev
[22] Ghazal AM, Zurigat Y. Numerical simulation of integrating PCM in 2015;41:658–84.
multilayer wall construction in UAE. In: 2017 7th International Conference [30] Hassan A, Alnouman H, Assi A et al. Temperature regulation and thermal
on Modeling, Simulation, and Applied Optimization (ICMSAO), Sharjah, energy storage potential of phase change materials layer contained at the
United Arab Emirates, 2017. pp. 1–5. IEEE. back of a building integrated photovoltaic panel. In: International PLEA
[23] Ghazal AM, Alnaimat F, Mathew B et al. The effect of incorporating Conference, 16–18 December 2014. CEPT University, Ahmedabad.
microencapsulated phase change materials (PCMs) in brick sandwiched [31] Hasan A, Alnoman H, Shah A. Energy efficiency enhancement of pho-
walls in reducing the thermal insulation thickness for hot climates. In: tovoltaics by phase change materials through thermal energy recovery.
2018 5th International Conference on Renewable Energy: Generation and Energies 2016;9:782.
Applications (ICREGA), Al Ain, 2018. pp.164–167. IEEE. [32] Hasan A, Sarwar J, Alnoman H et al. Yearly energy performance of a
[24] Rashid Y. Thermal and structural characterization of macro-encapsulated photovoltaic-phase change material (PV-PCM) system in hot climate. Sol
phase change material integrated into concrete cubes. Thesis. 731. 2018. Energy 2017;146:417–29.
[25] Hassan A, Ismail N, Mourad AHI et al. Preparation and characterization [33] de Gracia A, Navarro L, Coma J et al. Experimental set-up for testing active
of expanded clay-paraffin wax-geo-polymer composite material. Materials and passive systems for energy savings in buildings–lessons learnt. Renew
2018;11:2191. Sust Energ Rev 2018;82:1014–26.

International Journal of Low-Carbon Technologies 2019, 14, 568–575 575

You might also like