Refrigeration laboratory

BCN 4510

Name: Date:

Complete the following table and use the attached graphs to plot the performance of the first option for each
trainer. For example, With the Imperial HT Pump trainer, measure values and perform calculations for both
heating and cooling mode; but only plot the performance on the graphs of the heating mode. Do not perform
the calculations or plot the performance of the Ductless system.

PSIA = PSIG + 14.7

Temperature of refrigerant in Evaporator is based on Pressure or vaporization. Obtained from pressure


gauges or tables

Temperature of refrigerant in Condenser is based on Pressure of condensation. Obtained from pressure


gauges or tables

Superheat on low side is the difference between temperature entering the Compressor and temperature in
Evaporator

Superheat on the high side is the difference between temperature exiting the Compressor and temperature in
Condenser

Sub cooling is difference between temperature in Condenser and temperature entering expansion device

Cooling Capacity of the system = Refrigerant Effect x Flow Rate x 60 min/hr = (h2 – h1) x Flow x 60

Colling capacity in Tons = Cooling Capacity/ 12,000

COP = RE/HC = (h2 – h1)/ (h3 – h2)

EER = COP x 3.414

Compression ratio = P high/ P low


  Imperial   H-ACD-1   H-RST-2   Ductless
Ht Pump Sytem

  heating cooling   low high   low flow high    


blower blower flow

What refrigerant is used in the system  R-134A  R-134A    R-134A  R-134A    R-123      R-22

                     
Is it a CFC, HCFC, or HFC  HFC  HFC    HFC  HFC    HCFC      HCFC

                     
Draw the chemical structure on the                    
back of this page

                     
What is the low side pressure in psia  44.7  44.7    45.7  62.7    2.7      26.7

                     
What is the high side pressure in psia  234.7  234.7    189.7  189.7    44.7      54.7

                     
Temperature of refrigerant in  32  32   51  62    11      3
evaporator
                     
Temperature of refrigerant in  130  130    127  127    145      27
condenser
                     
Temp refrigerant entering compressor  64  64    50  64    60      -60

                     
Temp refrigerant exiting the  160  160    160  165    180      100
compressor
                     
What is the superheat on low side  32  32    -1  2    49      -62

                     
What is the superheat on high side  30  30    33  38    35      73

                     
Temp of refrigerant enter expansion  77  77    34  93    60      -60
device
                     
How much sub cooling is there  53  53    93  34    85      87

                     
Enthalpy of refrigerant entering  40  40    22  41    19      -5
evaporator (h1)
                     
Enthalpy of refrigerant entering  115  115    111  115    95      100
compressor (h2)
                     
Enthalpy of refrigerant exiting the  128  128    130  132    116      120
compressor (h3)
                     
Flow meter        25  45    45      
                     
Flow rate  1.29lb/mi  1.29lb/mi    0.66lb/mi  1.29lb/mi    14.05lb/h      1.29lb/mi
n n n n r n
                     
Cooling capacity of the evaporator in  0.484  0.484    0.294  0.477    0.089      0.677
tons
                     
COP of the system  5.77  5.77    4.68  4.35    3.62      5.25

                     
EER of the system  19.7  19.7    16  14.9    12.4      17.9

                     
What is the quality  20%  20%    0%  13%    11%      5%

                     
Percent liquid refrig entering the  80%  80%    100%  87%    89%      95%
evaporator
                     
Compression Ratio  5.25  5.25    4.15  3.03    16.6      2.05