You are on page 1of 14

feature

Recycled Water
in
Ready Mixed
Concrete
Operations By Colin Lobo
and Gary M. Mullings

Introduction enforce- ment penalties.


Process and storm water manage- The initial need for using
ronmental regulations. NRMCA mem- bers
ment at ready mixed concrete opera- recycled water in concrete
collected data of water from typical
tions is a growing issue for the came from California in the
sedimentation pits and the effects on concrete
industry. As regulations and early 1970s due to evolving
when this water was used as mixing water.
enforcement govern- ing discharge envi-
Based on these evalua- tions, criteria were
from plant sites evolve, the option of
developed and in 1978, ASTM C 94,
reusing these sources of water will
Specification for Ready Mixed Concrete was
become a necessity, thus moving
revised to permit the use of wash water as mixing
the industry toward zero-dis- charge
water in concrete. State highway agen- cies for
facilities. It is important that
the most part still do not allow its use or if they
positive terminology is used in
do, their requirements are more conservative than
describ- ing the source of water and
C 94. The criteria or requirements for wash water
that the customer is informed of its
in C 94 have not changed since they were
use in a positive manner. In this
originally incorporated in the standard. In the
article, the term recycled water will
’70s, producers in Cal- ifornia were looking for
be used for mixer wash water, storm
some relief to use some of their recycled water
water or gray water. Concrete
and reduce the quality of effluent from their
producers face the dichotomy production facilities and were not really striving
whereby their customers are generally for zero-discharge facilities. They retained the
resistant to allowing the use of problem of cleaning out debris from
recycled water in their concrete while sedimentation pits, handling it and disposing it
producers are forced to move in that in landfills. The industry’s needs have changed
direction because it’s the environmen- and so should the standard to allow an
tally responsible thing to do and there increased use of wash water while pro- tecting the
is a cost, sometimes unquantified, consumer. Current technol- ogy better facilitates
asso- ciated with its disposal. It’s true the collection of process and storm water with the
that when moving toward zero asso- ciated solids, water treatment and auto-
discharge the producer has to make an mated measurement and batching.
investment in equipment, people and
ASTM C 94 has criteria for wash water that
training, but in the relatively short
can be invoked at the option of the purchaser.
term this investment will be recovered
While these are optional requirements, the
in a successful applica- tion.
uninitiated
Producers who are leaders in envi-
ronmental management initiatives
have demonstrated this fact, without
includ- ing cost of compliance and
amounts to about 15 purchaser does not observe, or
pounds of solids in 1 cubic perceive, any diminished quality or
producer, relative to use of
yard of a typical concrete batch-to-batch variation. It takes just
recycled water, should try to
mixture. Does it matter if one bad story to generate a negative
remain within these limits for any
the solids added to the perception and essentially kill any ini-
structural concrete or slab
mix from recycled water tiative to move forward on this impor-
application. The requirements
exceed this limit? It tant issue. ASTM committees have
apply to the total mixing water in
depends on the concrete been deliberating for the last several
con- crete and are essentially limits
ingredients, years on revising the provisions for
on the water chemistry for alkalis,
characteristics of the mix- ing water, and while the
sulfates and chlorides for reasons
recycled water, time of consensus process can be frustrating,
related to concrete durability. The
year and everything else it hopefully achieves a better standard
other limiting criterion is the
that one could think of. that satisfies the producers and their
amount of total solids, which is
The important issue is customer.
limited to 50,000 parts per This is a brief report of portions of
that the concrete meets
million (ppm) or 5 percent by mass
the requirements of the in focus ı1
of the total mixing water. This CONCRETE
job specification and the
feature continued
the research conducted at the NRMCA
hardened concrete properties. A cubic foot mixer, tempered with water
Alfred H. Smith Research Laboratory typical air-entrained portland cement to a very high slump and water slurry
to answer some questions on reusing concrete mix design without any was decanted over a 150 µm (No. 100
recy- cled water in concrete. The admixtures was selected using stock sieve). The water slurry passing the
study was intended to simulate a materials from the research sieve was captured in a five-gallon
practical situation where a producer laboratory. The design mixture bucket and represented the wash water
has an environmental management characteristics and proportions are from the mixer. This wash water was
system that includes a returned pro- vided in Table 1. The kept agitated using a motorized paddle
concrete reclaimer that gener- ates experimental variables used in Phase I to keep the solids in suspension for
recycled water slurry. The slurry is of the study are listed in Table 2. Note the duration of the testing. The water
kept agitated in tanks and is used in a that the solids contents of the recycled slur- ry solids content varied from
controlled manner as a portion or all of 3
water, at 30 and 60 lb/yd , are at about 40 percent solids by mass to
the batch water in concrete mixtures. levels that are double and four times about 25 per- cent toward the end of
An important point to note is that the the current limit for solids in ASTM C the series at nine days as it was
char- acteristics of the slurry in this 94. This series was replicated three periodically diluted to maintain a
tank will be quite variable as water is times for a total of 48 concrete sufficient volume for the
removed and batches.
added to it from truck wash out during tests. A portion of the recycled water
any production day. Figure 1 Table 1 – Design Proportions was allowed to stand for about two
illustrates the variation of solids and Characteristics of hours and clear water was siphoned
content with time from an actual Concrete off the top to represent clarified
recycled water holding tank. Adding Portland Cement 600 lb/cu.yd recycled water.
this variable product with- out control Mixing Water 300
is sure to cause batch-to- batch lb/cu.yd. Natural Sand 1,100
variations of concrete properties. It is lb/cu.yd.
imperative that the producer has a sys- Limestone coarse
tem in place that recognizes this aggregate, max. size 1 inch 1,800
variabil- ity and adjusts for it so lb/cu.yd. Air content 4 to 6%
that the Slump 3 to 5 inches
customer does not see differences in
concrete performance properties in of using recycled water on Table 2 – Experimental variables in Phase I
sub- sequent loads of concrete. fresh and of the Study
The first phase of the study also Water • Tap water (Control)
includes a situation where a producer • Clarified recycled water
might use relatively clear water from • Recycled water at 30 lb solids
a sedimentation pit after the solids per cubic yard
have settled out. The reader is advised • Recycled water at 60 lb
that the data and trends are very solids per cubic yard Age of
specific to the materials and slurry • 4 ± 1 hour
conditions used in this study. • 1 day
• 3 days
Procedures • 9 days
The first phase of the NRMCA
study was to quantify the basic effects Recycled water
A concrete mixture was mixed in a 1 a microwave oven to determine the
percentage of solids by mass. At least
two samples of recycled water were
tested in this manner on each day
Figure 2 – Laboratory Set-up to
and the average was used to establish
Maintain Agitated Recycled the water slurry density and solids
Water Slurry content. Solids were filtered out from
the water slurry to measure the loss
When concrete on ignition and specific gravity.
mixtures were made, This information is useful to quantify
samples of the recycled the progressing degree of hydration of
water slurry were cement in these solids. Loss on
obtained and the density ignition is the loss in mass when an
was mea- sured by oven-dried sample is heated to 750ºC.
determining the mass of A portion of the solids was dissolved
water in a container of in acid to determine the insoluble
known volume. The water residue. Since cementitious materials
slurry sample was then dissolve in acid,
dried to constant mass in
Figure 1 – Variation in Solids Content in Recycled Water. Courtesy: M.D.A. Thomas, U of New
Brunswick the insoluble residue represents the fine

2 ı SPRING 2003

sand fraction, which was about 10 typically occur in practice. measured to estimate the initial setting time. A 4 x
per- cent of the mass of the dry solids. It is important to note that 8-inch cast cylinder was placed in an insulated 5-
the batches were adjusted to gallon contain- er. A thermocouple embedded in
Concrete batches achieve a similar target the center of the cylinder was connected to a data
On each day, four concrete batches slump and not to a constant logger to obtain the rate of heat evolution of the
with the four types of mixing water water-cement ratio. concrete. A correlation was established between
list- ed in the first row of Table 2 After the 30-minute
initial set from the C 403 method and a point on
were mixed. The concrete batches period, the
the heat signature curve. After some confi- dence
were nom- inally 0.75 cubic foot size concrete was discharged into
was achieved with this correla- tion, set time was
batches in a 1 cubic foot revolving a sample container and the
measured using the heat signature for the batches
drum laboratory mixer. Standard mass of discharged concrete
in the third round of replication.
ASTM procedures were used to mix was determined so that
Specimens for hardened concrete tests from
the concrete batches and to conduct precise mixture proportions
each batch included four 4 x 8-inch cylindrical
the fresh and hardened concrete tests. could be calculat- ed.
specimens for com- pressive strength
To achieve the target solids contents determination at seven and 28 days; one 4 x 14-
in the mixing water, recycled water inch cylinder with embedded gage studs for
slurry with known solids content was drying shrinkage measurement; one 4 x 14- inch
diluted with a calculated quantity of cylinder for freeze-thaw testing; and one 4 x 8-
tap water used. Clarified recycled inch cylinder for rapid chloride permeability
water was used at 100 percent of the testing.
added water in those respective
batches. Results and Discussion
The results of three replicate batches for the
Testing same experimental condition were very
Concrete mixtures were mixed to a reproducible and within typi- cal batch-to-batch
target slump of 5 inches. After the ini- variation quantified for procedures used at the
tial mixing for eight minutes, slump research lab- oratory. The average value of three
and density were measured. Air replicates of each condition is reported in many
content (gravimetric) was calculated cases in the subsequent discus- sion. Detailed data
from the measured density. Concrete on calculated con- crete mixture proportions,
from these tests was returned to the slump, temperature, air content and hardened
mixer. The mixer was covered to concrete test results are available and are not
prevent evapora- tion and the concrete reported here for the sake of brevity. Concrete
was periodically agitated and temperatures were in
retempered with water as necessary to
retain the target five-inch slump until
approximately 30 minutes after the
ingredients were batched in the
mixer. This was done to simulate a
30-minute delivery time of ready
mixed concrete and what might
the range of 70 to 75ºF and air con- cled water slurry to pounds, the mix- ing water demand to
tents and slumps were at target incorporate 30 and 60 lb/ achieve and main- tain the target
levels within the acceptable solids per yd . The slump increased. The increase is
tolerances. recycled water slurry was proportional to the amount of solids
used at ages of four hours, and the age of the recycled water
Water Demand one day, three days and slurry. With four-hour old slur- ries,
Figure 3 illustrates the nine days as indicated in the increase in mixing water was
calculated mixing water content Table 2. minimal, but as the slurry is aged past
for all the batches at 30 minutes to When clarified water one day, a higher water demand is
achieve and maintain the target was used, the mixing noticeable.
five-inch slump. The chart water content was By monitoring the loss on ignition
indicates that the mixing water essentially similar to the and specific gravity of the slurry 3
content for the nine control batches control batches. solids, it was observed that the contin-
was quite similar and averaged When recycled water ued cement hydration with time caus-
about 308 lb/yd . The chart also slurries were incorporated es the solids to get finer and of a
indicates the effects of using to achieve the target solids lower specific gravity.
3
These finer or
clarified recycled water and recy- content of 30 and 60 fluffier
Fresh concrete tests included
slump, temperature and density. Initial
setting time was measured by two
methods. The first method was in
accordance with ASTM C 403 by
the penetration resistance on a wet-
sieved mortar. On several batches, the
heat evolution (or heat signature) of Figure 3 – Mixing Water Content for Individual Concrete
Batches
the concrete was CONCRETE in focus ı3
Recycled
Water
at the University of Toronto

I
n 1996, ready mixed concrete water cement ratio. Results from The study included an evaluation
produc- ers in Ontario, Canada, this study and several field study on a wide range of concrete
commis- sioned the University of cases of external slabs on grades properties. Selected data are reported
Toronto to conduct a study, similar to placed in 1996 were reported to the here.
the NRMCA study, on the effects of Canadian Standards Association The study also measured the chem-
wash water in concrete. The important (CSA) in 1998 (personal istry of the recycled water and the
differences in the U. of Toronto study communication, Dr. alkalies, chlorides and sulfates
were that wash water slurries were M.D.A. Thomas, currently at the were significantly below the limiting
used from concrete production University of New Brunswick). criteria in ASTM C 94. Increased
facilities and laboratory mixtures were The experimental variables in scaling was observed when concrete
preparedVariables
Table 1: Experimental to a constant this study were: slabs made with recycled water at a
Air entrained Non-air entrained higher solids content were tested by
Cement content, kg/m3 (lb/cu.yd.) 375 (630) 250 (420) ASTM C 672, Test Method of
w/cm ratio 0.40 0.62 Concrete Surfaces Exposed to
Solids from recycled water, kg/m3 (lb/cu.yd.) • 0 (control) • 0 (control) Deicing Chemicals. Field slabs
• 10 (17) • 20 (34) have not revealed an increased
• 20 (34) • 40 (67) scaling. ASTM C 672 does result in a
• 40 (67) more severe exposure and indication
of scaling that has not been observed
in field concrete.

Figure 1.3: 28-day compressive strength of air entrained and non-air


Figure 1.1: Slump of air entrained and non-air entrained entrained concretes
concretes
Figure 1.2: Setting time of air entrained and non-air entrained Figure 1.4: ASTM C 1202 results for air entrained and non-air
concretes entrained concretes

4 ıı SPRING 2003
Stud
feature continued from page 3
is the effect on set-
ting time. Hydrated
cement and calcium

y
hydroxide
(hydrated lime) are
known to
accelerate setting
characteristics.
Problems with set-
ting with the use of
recycled water
Figure 4: Initial Setting Time of Concrete
slurry will be
This study also indicates that the exacerbated in
primary issue with the use of recy- particles cause the increased water summer but can
cled water at higher solids content demand. Specific gravity of dried possibly be used to
is the acceleration of the setting slurry solids varied from around 3.10 advantage in cooler
time. At the same w/cm ratio at four hours to 2.50 and lower at ages temperatures. These
strength, permeability, shrinkage one day and later. set time data illus-
and other characteristics were trate that the four-
similar to the control batches. Initial Setting Time hour old slurry had lesser effect on
Figure 1.1 illustrates the slump Figure 4 illustrates the effects of setting time than slurry that was aged
of the concrete mixtures. Since the using recycled water on initial setting for one day or longer. Setting times of
w/cm ratio was constant, using an time. Values reported are the average concrete with slurries aged for one
increasing solid content from recy- of three replicate batches for each day or longer were essentially similar,
cled water slurries resulted in lower condi- tion. The setting time of the possi- bly because most of the cement
slump. control is the average of nine concrete solids had hydrated at one day.
Figure 1.2 illustrates the setting batches.
characteristics of the concrete mix- The initial setting time of the con- Compressive Strength
tures. Similar to the NRMCA study, trol batch was around 4.9 hours. The Figure 5 illustrates the 28-day com-
increasing solids content resulted in setting time of the batches with clari- pressive strength of concrete batches
faster set times in both types of con- fied recycled water was similar to that rep- resenting each experimental
crete of the control batches. When recycled condition. The data represents the
water slurry was used, the setting time average of three replicate batches for
Figure 1.3 illustrates the com-
was accelerated and the faster setting each condition.
pressive strength of these mixtures.
time was proportional to the amount The compressive strength data
As concrete was mixed to a
of solids and the age of the water reflects the well-known fact that
constant water-cementitious
slurry. increased water content in the
materials ratio, similar strengths
The primary problem with reusing concrete will cause a reduction in
were obtained regardless of the
recycled water with solids in concrete strength. The reduction in strength
amount of solids from recycled
correlates well to the additional water
water in the mixtures.
used in the respective batches. The
Figure 1.4 illustrates the results lower compres- sive strength of
of ASTM C 1202, Test Method for batches containing recycled water
Electrical Indication of Concrete’s with higher solids con- tent could be
Ability to Resist Chloride Ion adjusted for by reducing
Penetra- tion, also known as the the water content of
rapid chlo- ride permeability test. these batches using
For similar materials, a higher appropriate mixture
value of the charge passed will adjustments. (See
result in concrete with a higher Figure 5)
permeability. It can be concluded The data also
from Figure 1.4 that the show that the batch-
permeability was not affected when es with the four-
recycled water slurry was used in
Figure 5: Compressive Strength at 28 days hour-old slurry did
these mixtures of the same
have a
w/cm
compressive
ratio. ■ strength similar to
the control batches,
which is related to
the lower mixing and CONCRETE in focus ı5
water demand
feature continued
designed to In this phase of the study, the recy-
evaluate whether cled water slurry was obtained in the
the treat- ment of same manner and placed in three sepa-
wash water with a rate containers. Two of these
hydration containers were dosed with the
stabilizing admix- hydration stabiliz- ing admixture at
ture (HSA) could two hours after the initial contact
offset some of the of water with the cement. The two
negative effects hours was chosen to simulate when a
with high solids mixer truck might return to the plant
recycled slurries and wash out with water that
Figure 6 – The progression of hydration of the cement (effectiveness of the
admixture dosage) was quantified from the loss on ignition on the dry solids observed in Phase I contained HSA.
from the slurries. of the study. Phase The Low dosage was established
II also included a from other tests to maintain the
condition where cement solids from hydrating about
1.5 day
possibly some cementing value from effects on mixing water the mixing water using recycled water slurry was
unhydrated cement solids. demand and setting time, the at the ASTM limit for solids content of 15 pounds
second phase of the study per cubic yard.
Durability Properties was The same concrete mix design and procedures
Data on drying shrinkage, freeze- were used for Phase II of the study. The details of
thaw resistance and rapid chloride 6 ı SPRING 2003 the experimental conditions are listed in Table 3.
per- meability were collected and are The data was generated from two replica- tions
not included or illustrated in this of the experimental series.
report. Mixtures that had a higher
mixing water content had a Table 3 – Experimental variables in Phase II of
concomitant increase in results for the Study Water • Tap water
drying shrinkage and rapid chloride (Control)
permeability. These higher values can • Recycled water at 15 lb solids
be offset if appropri- ate steps are per cubic yard
taken to reduce the mixing water • Recycled water at 45 lb
content of those mixtures. solids per cubic yard HSA
Freezing and thawing was Treatment • No admixture
conducted in accordance with • Low Dosage (1.5 day
Procedure A of ASTM C 666, which protection)
is the most severe exposure of freezing • High Dosage (8 day
in water and thaw- ing in water. The protection) Age of
samples were exposed to in excess of slurry • 4 ± 1 hour
600 freeze-thaw cycles. Typical • 1 day
evaluations are conducted for 300 • 7 days
cycles. All the samples had adequate
air contents and the durability factor
for all conditions exceeded 90 percent
when the tests were terminated. Typical
failure criteria for freeze-thaw
evaluations are when the durability
factor falls below 80 percent in 300
cycles. The severe expo- sure of
Procedure A caused scaling of the
freeze-thaw specimens. Mass loss
quanti- fied to an average 2.5 percent
of the original mass of the specimen.
There was no distinct experimental
condition that showed a higher level of
scaling.

Phase II
With the observation that recycled
water slurries used at four hours did
not cause significant detrimental
and the High dosage was established to
keep the cement solids from
hydrating for eight days. The
progression of hydration of the
cement (effectiveness of the
admixture dosage) was quantified
from the loss on ignition on the dry
solids from the slurries. These
results are illustrated in Figure 6. A
low loss on ignition value
corresponds to a low degree of
hydration of cement. Data in Figure
6 are from the actual slurries used
in the concrete batches.

Within ASTM C 94 Limits


Figures 7 and 8 illustrate the
setting time and 28-day
compressive strength of concrete,
respectively, of concrete batches
with solids content at the 50,000-
3
ppm limit (or 15 lb/yd ) of ASTM
C 94. The slurry ages were four
hours, one day and seven days.
Mixing water requirements were 0
(at four hours) to 15 lbs/yd3 higher
than that of the control batches for
target slump.
The data indicate that setting
time (expressed as percent of
control) and strength were similar
to control, except for modest setting
time acceleration

Figure 7 –
Setting time
of concrete
batches
with
recycled
water at
the ASTM
C 94 solids
limit
Simple Procedures for
Quality
Control
When Using Recycled Water

T
he primary criteria for
question- able sources of
mixing water in ASTM C 94
are for setting time Figure 2.1 – Density measurement of
and strength. When compared to using water by mass
tap water (control), the setting time
should not be accelerated by more
than one hour or retarded by more
than 90 minutes; and the seven-day
strength should not be less than 90
percent of control. Test methods
referenced in ASTM C 94 are those
used for cement testing – ASTM C
109 standard mortar cube, and ASTM
C 191 Vicat set. Equipment for these
tests typically is not used in Figure 2.2 – Density measurement of water using a hydrometer
laboratories at concrete plants and a
revision is being attempted to permit Density
these tests on concrete sam- ples with
The more accurate method is to determine the
the same criteria.
mass of recycled slurry water in container of
While the solids content is the
known volume (Figure 2.1). Another common
requirement in the standard, producers
proce- dure is the use of a hydrometer (Figure
will typically measure the density
2.2). This is less accurate as the solids tend to
(spe- cific gravity) of recycled water
settle rapidly.
slurry and establish blending
To determine the density, use a cylindrical
percentages of slurry and tap (or well)
container with a glass or Plexiglas plate that fits
water to meet a target density. A
over it. Calibrate the volume of the container in
water slurry at 50,000 ppm correlates
accor- dance with procedures used for cali-
to a density of about
brating air or unit weight buckets, as in ASTM C
1.03 g/mL.
29.
The following are recommended
Obtain the mass of the empty con- tainer and
tests and procedures that can be used
plate.
to determine blending percentages of
Take a representative sample of recy- cled
recy- cled water slurry and tap water
slurry water from the pit and fill it in the
to com- ply with a limit on solids.
container. Cover the container with the plate
ensuring that there are no air bubbles in the
container. Wipe the outside dry and obtain the
mass. The density is the net mass of water in the
container divided by its volume.
The operator might also obtain hydrometer
readings on a separate sam- ple of recycled water
slurry at the same
time and this will serve as drying. evapo- rated. Determine the mass of
calibration for the density the dish until two subsequent
measurement if the hydrometer will weighings do not change by much
be used during pro- duction. (0.5 g). The percent- age of solids in
the recycled water slurry can now be
Solids content calculated. Convert percent solids to
The quickest way is to dry a ppm by multiplying by 10,000.
sample of recycled water slurry in a
microwave oven (Figure 2.3). Use a Develop a correlation
glass dish with fiberglass cloth Make these measurements on recy-
(check at boat repair shop). Obtain cled water slurry on several days to
the empty mass of the dish and the cover the range of solids contents that
Figure 2.3 – Determining
cloth. solids content in a will be anticipated at a production
Pour the recycled water slurry microwave oven facility. Add to this data with
sam- ple from the density periodic
measurement into the glass dish Place the dish in a
and cover with the fiber- glass cloth microwave oven and dry it
to prevent loss of solids dur- ing until all the water has CONCRETE in focus ı7
(50,000 – 2000)
tests on the recycled water slurry. of this recycled water slurry and tap RW = –––––––––––––––– = 34%
Estab- lish a linear relationship (for water (assume density of 1.00 and (144,000 – 2000)
simplicity) between the slurry total dissolved solids of 2000 ppm for
density and the solids content (see sim- plicity), for a target solids The same equation can be used if
Figure 2.4). Based on target density content, the following relationship can the preference is to work with water
of the mixing water, one can calculate be used: density, where the respective water
the blending percent- ages. RW x SRW + (1 – RW) x STW = den- sity replaces the solids content.
TS Blending recycled water slurry and
Example Where: tap water is frequently done with in-
Figure 2.4 illustrates a sample rela- RW = Recycled slurry line water density gages and
tionship of recycled water density and
water TW = Tap water = automated adjustments. Ensure that
solids content in ppm. This relation-
(1-RW) the software is doing these
ship holds only for this particular con-
SRW = Solids content of recycled calculations accurately and calibrate
crete plant. A spreadsheet and
slurry water these density gages using the simple
graphing software (like MS Excel)
STW = Solids content of tap water procedures described here. The
can be used to plot this relationship
and obtain an equation. TS = Target solids content (limit) producer should check the density of
In this example the relationship in mixing water recycled water at a minimum
between the solids content and the The percent recycled slurry water frequency of two per day. When
den- sity is as follows: can be calculated by rearranging the mixing water is used at a higher
Solids content, ppm = 1356495 previous equation: solids content, there are other
(Density) – 1348016 adjustments necessary to batch
(TS-STW)
If the density of the slurry on a par- RW = –––––––––– ingredients to compensate for the
ticular day is 1.10, using this (SRW-STW) water and solids in the recycled water
equation, the solids content is slurry and to establish more accurate
approximately 144,000 ppm. If the target solids content is the mixture proportions and water-cement
To determine blending percentage ASTM C 94 limit or 50,000 ppm, the ratio. The producer should also docu-
percentage recycled water slurry to ment strength and setting time data
blend with tap water in this example to
will be: provide to the customer on request. ■
Figure 2.4 – Correlation between density and solids content for recycled water slurry

8 ı SPRING 2003

feature continued from page 22


admixture. The concrete There are many examples in
batches used recycled Japan, Europe, Canada and the U.S.
water slurries such that where these types of systems are
45 pounds of solids per being successfully used.
cubic yard were incorpo-
rated in the batches. As
expected from Phase I,
the batches with the
untreated slurries had a
higher mixing water
requirement to achieve
the target slump and an
Figure 8 – 28-day compressive strength for concrete batches with recycled associated reduction in
water at the ASTM C 94 solids limit strength is noted. Setting
time of these batches,
and lower strength for the batches was accelerated relative to the control exceed the current limits of ASTM
with the seven-day-old slurry. These batches. C 94.
devia- tions from control for concrete In the batches that had the slurry
with the four-hour and one-day-old with the Low dose of HSA, the setting
slurries are within permissible limits time and strength with the one-day-
for water in ASTM C 94. old treated slurries were similar to
control batches, but the same negative
HSA Treated Slurries effects were observed when this
Figures 9 and 10 illustrate selected slurry was used at an age of seven
data for setting time and 28-day com- days. Recall that the HSA dosage was
pressive strength of concrete, selected to prevent cement hydration
respective- ly, of concrete batches for about one day.
with and without slurries treated In batches with the slurry treated
with the HSA with the High dose of HSA, the
setting
time and strength of
batches using the seven-
day-old treated recycled
water slurry were similar
to that of the control
batches.
These data
illustrate that
hydration stabilizing
admixtures can work
to facilitate the use of
recycled water slurries at
solids con- tent that
Figure 11 – Schematic of HSA treated concrete certain solids content, it These conclusions are pertinent to
wash out system Courtesy: Knelson Concrete
Recovery System is diverted to this feed the materials and conditions used in
tank and this water is used this research study. These
Another option for the producer is as batch water. This tank observations are based on mixing
to maintain a certain consistency now has a constant solids concrete to a target slump. The
of the recycled water solids in content and can be used in associated effects on concrete
consecutive batches while fixed quantities to
properties, except for setting time,
ensuring that it meets job maintain batch-to- batch
consistency. were primarily a result of the
performance requirements. additional mixing water needed to
Some reclaimer manufacturers achieve and maintain the target slump
will install a separate feed tank. Conclusions of five inches.
When recycled water reaches a
Figure 9 - Setting time of concrete batches with HSA treated and Achieving this state 1. Using recycled water with a solids
untreated recycled water at 45 pound solids per cubic yard will content at or less than the ASTM C
Figure 10 – 28-day Compressive Strength of concrete batches with require some capital 94 limit should comply with the
HSA treated and untreated recycled water at 45 pound solids per cubic
yard expense and company mix- ing water criteria for strength
commitment. For this and set- ting time in the standard.
option to be However, recycled water aged to
economically viable, the seven days seemed to have
goal should be to marginally detrimental effects in
establish a mass balance this study.
such that the volume 2. Performance properties of concrete
of recycled water batches with clarified recycled
generated at a concrete water were similar to the control
production facility is batches. The data from this study
completely used in a indicates that the use of clarified
defined period. The water should be able to comply
economics will need with the mixing water criteria in
to consider the market ASTM C 94.
area of operation and the 3. Using recycled water slurries at signifi-
cost of regulatory CONCRETE in focus ı9
compliance.
feature continued 6. Freeze thaw results of all
concretes in this study
cantly higher than the ASTM C crete in freeze-thaw environments.
were acceptable,
94 limit for solids resulted in 7. Results of this laboratory study indi- cate that
indicating that when
increased mixing water demand hydration stabilizing admix- tures can be used
recycled water is used,
and accelerated setting time. The to overcome the negative effects of age and
attaining adequate air
effects were more pronounced higher solids content in recycled mixing
entrainment and strength
with an increase in the age of the water. ■
will provide durable con-
slurry past one day and an increase
in the solids content. References
4. At the higher solids content, 1. ASTM C 94, Specification for Ready Mixed
four- hour-old slurries had a Concrete, ASTM, West Con- shohocken,
minimal effect on the setting time Pennsylvania, www. astm.org
and water demand of the concrete 2. Gray Water Recycling, Article in 3 parts,
mixtures. Setting time and strength Greg Vickers, The Concrete Producer, from
for these batches were similar to October 2002, Han- ley-Wood LLC,
control. This indicates that www.worldofcon crete.com
hydrated cement in the slurry 3. Slurry Compensation Calculations¸ per- sonal
solids at later ages is the primary communication from Rich Szecsy,
reason for the negative effects on Lattimore Materials Corpora- tion, Dallas,
water demand and setting time. Texas
5. Mixtures that had a higher water 4. Use Of Slurry Water In Concrete – Field &
con- tent due to the use of higher Laboratory Investigations; Implica- tions for
solids recycled slurry had an Standards, M. D. A. Thomas, personal
associated reduction in strength communication and presen- tation to CSA,
and increase in drying shrinkage 1998
and rapid chloride permeability 5. Scott Hammersly, personal communi-
results.
10 ı SPRING 2003

cation, Newington Concrete and


New Rock Materials,
Newington, VA
6. Dave Beckham, personal
communica- tion, Knelson
Concrete Recovery Sys- tem,
British Columbia, Canada
7. A Novel Method Of Recycling Returned
Concrete Using Extended Life
Admix- tures, Seiji Nakamura and
Lawrence R. Roberts,
Proceedings of Congress of the
European Ready Mixed
Concrete Organization
(ERMCO), 1998

Acknowledgements
This research study would not
have been possible without the
planning and dedication of Richard
D. Gaynor, previ- ously executive
vice president at NRMCA and
NAA, and the assistance of Soliman
Ben-Barka, senior lab technician at
the AH Smith Research Lab. The
financial and technical assistance
of the following is also gratefully
acknowledged: Portland Cement
Association; Grace Construction
Products; Master Builders; Holnam,
Inc. (now Holcim); Transit Mix
Concrete, Colorado Springs, CO;
Boral Materials; The Aberdeen
Group (now Hanley- Wood) and
Cadman.

You might also like