You are on page 1of 8

970 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO.

2, APRIL 2005

Power System Harmonic Analysis Using


State-Estimation Method for Japanese Field Data
Norikazu Kanao, Member, IEEE, Mitsunori Yamashita, Hikoni Yanagida, Munehisa Mizukami,
Yasuhiro Hayashi, Member, IEEE, and Junya Matsuki, Member, IEEE

Abstract—The harmonic state-estimation (HSE) method ap- One is a method using a Kalman filter or harmonic power flow
pears to be effective but its applicability has yet been fully verified with a least squares estimator, and another is the state-estimation
using actual data in power systems. Particularly in Japan, there method with Global Positioning System (GPS) to reduce the in-
has been no verification of the applicability of the method in actual
power systems. In this paper, for Japanese field data synchronized fluence of measurement error. The state-estimation method ap-
with a Global Positioning System (GPS) clock, a practical method pears to be effective but its applicability has yet been fully ver-
for power system harmonic analysis is proposed, which is based on ified using actual data in power systems. Particularly in Japan,
HSE. In the proposed method, in order to improve the precision there has been no verification of the applicability of the method
of HSE, uncertain parameters R, X, and Y of the transmission in actual power systems.
lines are determined from measured fundamental data, and
bad measured harmonic data excluded systematically. It is also In this paper, for Japanese field data synchronized with a GPS
possible to estimate the error of each measurement instrument by clock, a practical method for power system harmonic analysis
using HSE. It is confirmed that by using only partial and selected is proposed, which is based on the harmonic state estimation
measurement data synchronized with a GPS clock, the entire har- (HSE). In the proposed method, in order to improve the pre-
monic distribution of the actual power system has been obtained cision of HSE, uncertain parameters R, X, and Y of the trans-
effectively. In this paper, field-test results of the HSE on an actual
Japanese power system are shown. Furthermore, an example of mission lines are determined from measured fundamental data,
harmonic analysis based on HSE in the actual power system is and bad measured harmonic data excluded systematically. It is
presented, which is prediction of harmonic voltage distribution also possible to estimate the error of each measurement instru-
after a change of the actual power system configuration. ment by using HSE. It is confirmed that by using only partial
Index Terms—Global positioning system, least-squares methods, and selected measurement data synchronized with a GPS clock,
measurement error, power system harmonics, state estimation. the whole harmonic distribution of the actual power system has
been obtained effectively. Field-test results of the harmonic state
estimation on an actual Japanese power system are shown. Fur-
I. INTRODUCTION
thermore, an example of harmonic analysis based on HSE in the

W ITH the widespread use of power electronic equipment,


many inverters have been built into devices, and har-
monics arising from them are injected into the power system and
actual power system is presented, which is prediction of har-
monic voltage distribution after a change of the actual power
system configuration.
distributed over the entire system. Due to the harmonics, their
influence on power quality due to damage by voltage distortion
is of concern. Thus it is important to determine harmonic distri- II. OUTLINE OF PROPOSED HARMONIC ANALYSIS METHOD
bution precisely. In a bulk power system, a large-volume ac/dc
conversion facility that utilizes power electronics technology is In conventional analyses of harmonics, harmonics are calcu-
introduced, so that it is important to avoid unstable operation of lated repeatedly by trial and error to fit the calculated values to
the facility by the overloading of an alternating current filter due the measured values. The conventional harmonic analyzes have
to the distribution of harmonics. the following problems.
Thus far, in order to determine the distribution of harmonics • Number of Measurements
in a power system, several methods have been proposed [1]–[4]. For an actual power system, it is easy to obtain funda-
mental voltages/currents at all substations, but harmonics
Manuscript received June 5, 2003; revised November 14, 2004. Paper no. are not always measured at all substations. In order to de-
TPWRD-00288-2003. termine the harmonic distribution, it is desirable to obtain
N. Kanao and M. Yamashita are with the Engineering Research and Devel- the data of all substations. However, it is difficult to mea-
opment Center, Hokuriku Electric Power Company, Toyama 930-0848, Japan
(e-mail: n.kanao@rikuden.co.jp; yamashita.mi@rikuden.co.jp). sure the harmonic data because a number of instruments
H. Yanagida is with Ishikawa Control Center, Hokuriku Electric Power Com- cannot be provided due to the high cost and long time re-
pany, Ishikawa 920-1304, Japan (e-mail: yanagida.hikoni@rikuden.co.jp). quirements.
M. Mizukami is with the Power System Management Department, Hokuriku
Electric Power Company, Toyama 930-8686, Japan (e-mail: mizukami.mune- • Synchronization of Harmonic Data
hisa@rikuden.co.jp). Synchronization of harmonic voltages/currents be-
Y. Hayashi and J. Matsuki are with the Department of Electrical Systems, tween measurements at every substation is necessary
Fukui University, Fukui 910-8507, Japan (e-mail: hayashi@fuee.fukui-u.ac.jp;
matsuki@fuee.fukui-u.ac.jp). in order to recreate the distribution of the entire power
Digital Object Identifier 10.1109/TPWRD.2004.838632 system in the simulation. It is difficult to maintain the
0885-8977/$20.00 © 2005 IEEE
KANAO et al.: POWER SYSTEM HARMONIC ANALYSIS USING STATE-ESTIMATION METHOD 971

Fig. 2. Measurement system at HEPCO.

Fig. 1. Outline of harmonic analysis.

synchronization solely on the basis of the conventional


measurement that is carried out at each substation.
• Measurement Error
Almost no magnitudes of harmonic voltages/currents
are more than 5% of the fundamental value. Since the
measurement range of an instrument is adjusted for the
range of fundamental values, harmonics are not measured
precisely. In particular, the potential device (PD) for the
voltage measurement, which is widely used at 275–66 kV
substations, is fabricated for the purpose of fundamental
frequency measurement. The frequency characteristics of
the PD change significantly under the influence of the
Fig. 3. Harmonic measuring instrument.
burden (meter and relay) connected to the secondary of
the PD. Practically, it would be expensive and laborious
to measure the frequency characteristics of each PD and voltages/currents, voltage dip, harmonics, and calculate fault
calibrate the harmonic voltages. Thus, it is desirable to ob- location. Fig. 2 shows the overview of the measurement system.
tain the harmonic voltage/current distribution of the entire Each instrument is connected to the research center through
system using only few harmonic data values without PD a LAN. The measurement data recorded in the instrument are
measurement. collected through the LAN at the Engineering Research and
In order to overcome these problems, a practical method of Development Center in HEPCO at almost weekly intervals.
harmonic analysis is proposed. The proposed method consists Measured harmonic data are recorded with the time stamp
of three parts: 1) measurement of harmonics and determination of a GPS clock. The synchronization error of this system is
of transmission lines’ parameters; 2) harmonic state estimation; within 6 , which corresponds to 0.13 degrees in electrical
and 3) evaluation of estimated harmonics. The data of harmonics angle. The error of one pulse per second (pps) for the GPS signal
is obtained by the measurement system with a GPS clock at is within 1 . The signal processing error is within 4 , and
Hokuriku Electric Power Company (HEPCO). The outline of the signal transmission error between units in this instrument is
the method of harmonic analysis is shown in Fig. 1. The HSE 1 . Therefore, the synchronization error is negligible for the
can be run off-line when necessary. Details of each part are ex- fifth and seventh harmonics.
plained in the succeeding sections. The instrument measures the harmonics of up to the 15th
order every 30 min by the sampling frequency of 3840 Hz and
sampling interval of eight cycles (512 points) for 60 Hz, and
III. MEASUREMENT SYSTEM OF HARMONICS AT HEPCO calculates the harmonics by fast Fourier transform (FFT). The
harmonic measuring instrument is shown in Fig. 3. Harmonic
A. Measurement System
data are changed into phasor data by FFT from the instantaneous
The measurement instruments are installed at the main values measured through PT/CT, the analog filter, and A/D
substations of HEPCO, which measure fault waveforms of converter.
972 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005

TABLE I
MEASUREMENT ERRORS OF VOLTAGE AND CURRENT

Fig. 5. Transmission line model and transformer model with a voltage tap T.
(a) Transmission line mode. (b) 3-Winding transformer model with a voltage
tap T.

data because of the application of the single-phase models. The


transmission line model and transformer model are shown in
Fig. 5.
While the parameters , , and of transformers are
obtained by tests, the parameters R, X, and Y of transmission
lines are uncertain. In order to increase the precision in harmonic
data calculation, the values of R, X and Y must be determined
by measurement data. The relations among , , , and
Fig. 4. HEPCO power system. at both ends of a transmission line at the fundamental fre-
quency are given by (1) and (2). Since the number of unknown
parameters is smaller than the number of measured values, pa-
There exist measurement errors of the PT/CT and the in- rameters R, X, and Y of a transmission line are obtained by the
strument. The frequency characteristics of PT/CT are flat up to least-squares method using the measurement data , , ,
2 kHz and the rate of error is almost the same as the fundamental and
frequency, so that the error rate and angle of the Standards of
The Japanese Electrotechnical Committee (JEC) 1201 [5] (1%
to 3%, 1–3 degrees) are used. The measurement error charac- (1)
teristic of the analog filter is 0 dB up to 960 Hz, and the A/D
converter error is 0.2%, which is 16 bits ( 0.15% of the rel-
(2)
ative error calculated from 0.0015% of the quantum error).
The total error is shown in Table I. It is noted that when there is
a phase error of at the fundamental frequency, the phase error
of arises at the th harmonics.
IV. METHOD OF HSE
B. Power System and System Model A. State-Estimation Method
As shown in Fig. 4, the HEPCO power system has seven par- For the problems on harmonic data measurement, i.e., the
tial power systems that are represented as loads. Seven harmonic number of harmonics and measurement error, it is very effec-
current sources are included in these loads (Load 1 Load 7). tive to use a state-estimation method that has been applied to
A transmission line is modeled as a single-phase equivalent power systems for automatic dispatching systems and so forth.
model with distributed parameters. Since our targets of analysis By applying the method to harmonics, it is possible to deter-
are the fifth and seventh harmonics and the length of transmis- mine the entire harmonic distribution of a power system that
sion lines is maximum at 70 km [6], [7], one step of the cir- obeys Kirchhoff’s law using only partial and selected measure-
cuit is adopted. A transformer is modeled as a 3-winding trans- ment, and to analyze the harmonics obtained by the estimation
former model with a voltage tap T. In addition, harmonic data results. This section describes the overview of HSE program-
is extracted from the three phases as symmetrical components ming developed by CRIEPI [8].
KANAO et al.: POWER SYSTEM HARMONIC ANALYSIS USING STATE-ESTIMATION METHOD 973

The n points of unknown harmonic current sources and


points of measured harmonic voltages/currents phasors
are represented by (3) as measurement error [9]

(3)

where is the observational matrix defined by the power Fig. 6. Relationship of z , z , and  .
system configuration and measurement terms. Specifically, (3)
is represented by (4) as
obtained by Table I are defined as and , respectively, the range
of is within a circle, as shown in Fig. 6
(7)
(8)
where includes the error of measurement data and where
error rate of ;
error angle of .
The best-estimate value with minimizing is given as
follows:

(9)

(4) The estimated value of measurement data due to is repre-


where sented by (10) as
current of harmonic current source ;
(10)
total number of measured currents;
total number of measured voltages; Covariance matrix of and covariance matrix of
total number of unknown harmonic current sources are calculated as follows:
.
In (4), is defined as the current sensitivity (complex) of a
measurement branch for source current injected into the (11)
power system. Similarly, in (4) is the voltage sensitivity
(complex) of a measurement node for the injected current .
For example, can be calculated as the node voltage by (12)
substituting and (where ) for the basic Since the diagonal terms of and correspond to the vari-
equation (where [V], [Y], and [J] are the voltage ance, the deviations of estimated values are calculated by their
matrix, admittance matrix and the current source matrix of the square roots.
power system, respectively).
By considering the squares of the errors with a weighting B. Exclusion of Bad Data
factor as the objective function shown in (5), an estima- When a measurement is erroneous or bad, it should be de-
tion value is defined as the value of with minimum tected so that it can be removed from the estimator calculations
to improve the estimate precision [9]. The statistical properties
of measurement errors facilitate such detection.
(5) By using index represented by (13)–(15), it is possible to
identify bad data. When no measurement data is bad data, is
where and where less than 1 according to the Gaussian distribution
weighting factor matrix
(13)

(14)
(6)

(15)
covariance of measurement data ; Here, denotes the diagonal terms of covariance of .
matrix operator of complex conjugate transpose. By removing bad data , the precision of the estima-
Since the deviation corresponds to the measurement error tion can be improved. Since true values are unknown, the most
that is the magnitude of the deference between and , is probable values (MPV) estimated on the basis of reduced mea-
calculated by (7) and (8). If the error rate and error angle of surement data are defined as true values in this paper.
974 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005

TABLE II TABLE III


TRANSMISSION AND TRANSFORMER PARAMETERS FIFTH HARMONIC CURRENT DATA AT EIGHT MEASUREMENT POINTS

Fig. 7. Example of transmission line parameters (B line).


Fig. 8. Estimated results from eight measurement data of Table III.

V. ESTIMATION RESULTS OF FIELD TEST ON POWER SYSTEM points give us the entire harmonic voltage/current distribution
According to the procedure shown in Fig. 1, harmonic state that obeys Kirchhoff’s law.
estimation was field tested at the HEPCO power system shown
in Fig. 4. In this section, the results and evaluation of the field C. MPV and Evaluation of Estimated Results
test are described. The estimated results shown in Fig. 8 were compared with the
true value (MPV). The true values were calculated by removing
A. Parameters of Transmission Line bad data, as shown in Table IV. It is noted that the voltage mea-
surements at buses , , and were not used due to PD mea-
According to (1) and (2), R, X, and Y of each transmis-
surement. In Table IV, Case 1 shows of the calculated results
sion line were calculated by using 168 measurement data (24
including bad data and Case 2 shows of the calculated results
data/day in a week) of fundamental data , , , and in
after the removal of bad data.
the HEPCO power system. The averages of R, X, and Y were
Fig. 9 shows the estimated values and the deviations derived
used as transmission parameters. Table II lists the parameters
from (11) for the measured load currents in comparison with the
of each transmission line and transformer. In this paper, the
true value. It is noted that the true values exist in each deviation
value estimated using measurements are used. Fig. 7 shows an
range of estimated values by eight measurement points on the
example of R, X, and Y of the transmission line B.
branch currents. This means that the results estimated by eight
measurements of currents are sufficient.
B. Harmonic State-Estimation Result Using Field Data Furthermore, improvement of the precision of HSE by
The HSE was performed at the power system shown in Fig. 4 increasing the number of measurement points was examined.
using only eight measurement points of fifth harmonic currents Fig. 9 also indicates the estimated values and the deviation
as shown in Table III, where more than seven measurements range in the cases of 10 and 15 measurement points. It is evident
were necessary for the redundancy of measurements because that the deviations of magnitude/phase angle in each estimated
seven unknown harmonic current sources existed in the power current become small with increasing number of measurement
system. The estimated results are shown in Fig. 8. It is noted points, which indicates that the estimate precision is improved
that fifth harmonic current data at only eight measurement by increasing the number of measurement points.
KANAO et al.: POWER SYSTEM HARMONIC ANALYSIS USING STATE-ESTIMATION METHOD 975

TABLE IV
INDEX  AND THE MPV OF MEASUREMENT DATA

Fig. 9. Comparison of HSE results and true values (MPV) on fifth harmonic
current sources. (a) Magnitude. (b) Phase angle.

Fig. 10. Estimated error rate and maximum error angle. (a) Error rate  at  =
0 in Step 1. (b) Maximum error angle  in Step 2. Fig. 9. Comparison of HSE
results and true values (MPV) on fifth harmonic current sources. (a) Magnitude.
(b) Phase angle.

Step 2) Calculate the maximum error angle by (16), when


vector is tangential to the circle with the radius of
obtained by Step 1 as shown in Fig. 10(b)

D. Estimation of Error of Fifth Harmonic Voltage (16)


Measurement
where is the root of weighting factor when of
As shown in Table IV, the fifth harmonic voltage measure- HSE equals to 1
ments of , and were removed as bad data when the error
shown in Table I was used. This means that some of the fifth Fig. 11 shows the change of of the fifth harmonic voltage
harmonic voltage measurements include more errors than the measurements by varying the weighting factors. in
expected error of 1.0%, which corresponded to the degrada- Fig. 11 was normalized by measurement data ( corresponds
tion of the weighting factors. Thus it is possible to estimate the to of (8) in case of ). Table V shows the estimated error
error rate and error angle of measured harmonic data by using rate and error angle of the fifth harmonic voltage measurement.
HSE. Procedures of the estimation are based on the relationship For example, in the case of measurement , the index was
shown in Fig. 6 and has two steps, as shown below. less than 1.0 when the was not greater than 20%
in Fig. 11. Since the maximum error rate is ,
Step 1) Calculate the error rate by assuming the error angle the maximum error angle
is zero as shown in Fig. 10(a), when the index of in the case of measurement is calculated from
HSE equals to 1.0. (16), as shown in Table V.
976 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005

Fig. 11. Index  of fifth harmonic voltage measurement as a function of


normalized  by measurement data in (8). Fig. 9. Comparison of HSE results
and true values (MPV) on fifth harmonic current sources. (a) Magnitude.
Fig. 12. Procedure of harmonic analysis in the case of change of power system
(b) Phase angle. configuration.

TABLE V
ESTIMATED ERROR OF FIFTH-HARMONIC VOLTAGE MEASUREMENT

VI. APPLICATION OF HSE FOR SYSTEM


CONFIGURATION CHANGE

When the configuration in the subpower system of Load 1 was


Fig. 13. Fifth harmonic voltages before/after the change of power system
changed, a change of approximately 50% of the fifth harmonic configuration at Load 1.
voltages of each bus bar in Fig. 4 was observed. In order to check
whether the change of the fifth harmonic voltages was due to a
change of system configuration, harmonic analysis was carried well with the true values (new). This means that HSE can be ap-
out by the following procedure, as shown in Fig. 12. plied to predict a harmonic voltage distribution after a change
of the power system configuration.
Step 1) Perform HSE using the measured harmonic data (old)
and the power system data (old) before changing the
VII. CONCLUSIONS
power system configuration. Find the harmonic
sources (old) and the harmonic voltage distribution Power system harmonic analysis using the HSE method,
(old). which is applied to the actual power system in Hokuriku
Step 2) Perform HSE using the measured harmonic data Electric Power Company in Japan, is described. HSE has been
(new) and the power system data (new) after verified in the applicability using field data synchronized with
changing the power system configuration. Find the a GPS clock, i.e., the entire harmonic distribution (eight node
harmonic sources (new) and the harmonic voltage voltages and 25 branch currents in this study) of the actual
distribution (new). power system has been obtained effectively through eight
Step 3) Calculate harmonic distribution using the harmonic measurement data values.
current sources (old) derived from Step1 and the • In order to increase the precision of HSE, the uncertain pa-
power system data (new). rameters R, X, and Y of transmission lines are determined
Step 4) Compare the harmonic voltage distribution of Step3 from measured fundamental data.
with the harmonic voltage distribution (new) derived • By introducing index and determining the MPV, it is
from Step2. examined whether the exclusion of bad data improves the
The estimated harmonic current sources (old) in Step1 and precision of HSE and whether by increasing the number of
harmonic current sources (new) in Step 2 remained almost good measurement data values, more precise HSE results
unchanged. are obtained. By using the index of HSE, the error of
The measured and calculated values of the fifth harmonic each measurement instrument can be estimated.
voltages are shown in Fig. 13. It is seen that the harmonic volt- • HSE can be applied to predict a harmonic voltage distri-
ages calculated by harmonic current sources (old) agree very bution after a change of the power system configuration.
KANAO et al.: POWER SYSTEM HARMONIC ANALYSIS USING STATE-ESTIMATION METHOD 977

ACKNOWLEDGMENT Hikoni Yanagida was born in Toyama Prefecture,


Japan, in 1957. He received the B.S degree in elec-
The authors gratefully acknowledge the contributions of trical engineering from Waseda University, Tokyo,
K. Yukihira and T. Yoshida to the program development. The Japan, in 1981.
In the same year he joined Hokuriku Electric
authors also acknowledge the technical support of Kinkei Ltd. Power Co., Toyama, where he is now a Manager of
and K. Tsuji. the Ishikawa Control Center.
Mr. Yanagida is a member of the IEE of Japan.
REFERENCES
[1] G. T. Heydt, “Identification of harmonic sources by a state estimation
technique,” IEEE Trans. Power Delivery, vol. 4, no. 1, pp. 569–576, Jan.
1989.
[2] H. M. Beides and G. T. Heydt, “Dynamic state estimation of power
system harmonics using Kalman filter methodology,” IEEE Trans.
Power Delivery, vol. 6, no. 4, pp. 1663–1670, Oct. 1991.
[3] Z.-P. Du, J. Arrillaga, and N. Watson, “Continuous harmonic state es- Munehisa Mizukami was born in Toyama Prefec-
timation of power systems,” Proc. Inst. Elect. Eng. Gener., Transm., ture, Japan, in 1952. He received the B.S degree in
Distib., vol. 143, no. 4, pp. 329–336, July 1996. electrical engineering from Tokyo Denki University,
[4] A. P. S. Meliopoulos, F. Zhang, and S. Zelingher, “Power system Tokyo, Japan, in 1974.
harmonic estimation,” IEEE Trans. Power Delivery, vol. 9, no. 3, pp. In the same year, he joined Hokuriku Electric
1701–1709, July 1994. Power Company, Toyama, Japan, where he is now a
[5] Standard of the Japanese Electrotechnical Committee (JEC)—1201, In- Deputy Manager of the Power System Management
strument Transformers for Protective Relays, 1985. Department.
[6] J. Arrillaga, B. C. Smith, N. R. Watson, and A. R. Wood, Power System Mr. Mizukami is a member of the IEE of Japan.
Harmonic Analysis. New York: Wiley, 1998.
[7] CIGRE Working Group 36-05, “Guide for Assessing the Network Har-
monic Impedance,” CIGRE WG 36.05 internal working document WG
CC02 93202,29,10, 1993.
[8] K. Yukihira, “Development of a Program for Estimating Harmonic Cur-
rent Sources,”, CRIEPI REPORT, T89043, May 1999.
[9] J. J. Grainger and W. D. Stevenson Jr, Power System Analysis. New
York: McGraw-Hill, 1994. Yasuhiro Hayashi (M’91) was born in Fukui Pre-
fecture, Japan, in 1967. He received the B.E., M.E.,
and Dr. Eng. degrees from Waseda University, Tokyo,
Japan, in 1989, 1991, and 1994, respectively.
Norikazu Kanao (M’03) was born in Toyama Pre- In 1994, he joined Ibaraki University, Ibaraki,
fecture, Japan, in 1959. He received the Master’s de- Japan, as a Research Associate. Since 2000, he has
gree in electrical engineering from Nagoya Univer- been an Associate Professor with the Department
sity, Nagoya, Japan, in 1984. of Electrical and Electronics Engineering, Fukui
In the same year, he joined Hokuriku Electric University, Fukui, Japan. His research interests
Power Company, Toyama, Japan, where he is now include the fields of optimization of power system
is a Sub-Manager of the Engineering Research and operation and planning, power system analysis, and
Development Center. load forecasting.
Mr. Kanao is a member of the IEE of Japan.

Mitsunori Yamashita was born in Toyama Prefec- Junya Matsuki (M’71) was born in Kumamoto Pre-
ture, Japan, in 1972. He received the B.S. degree fecture, Japan, in 1946. He received the B.S., M.S.,
in electrical engineering from Sophia University, and Dr.Eng. degrees from Kyoto University, Kyoto,
Tokyo, Japan, in 1995. Japan, in 1969, 1971, and 1979, respectively, all in
In the same year, he joined Hokuriku Electric electrical engineering.
Power Company, Toyama, Japan, where he now is In 1971, he joined the Mitsubishi Electric Com-
with the Engineering Research and Development pany, Japan. Currently, he is a Professor at Fukui Uni-
Center. versity, Fukui, Japan. His research interests include
Mr. Yamashita is a member of the IEE of Japan. power system analysis and synchronous machines.

You might also like