Professional Documents
Culture Documents
victron energy
BLUE POWER
AC Input Inverting AC Loads
victron energy
0W 435W
75%
+
PV-Charger
victron energy
950W
MPPT 100 | 50 BLUE POWER
340W
DC Power
25.6V 13.2A -155W
MEGA
xxxA Load+ SHORE POWER
! i IP43
ISOLATION TRANSFORMER OR
Battery 12/24V 50A GALVANIC ISOLATOR SHOULD BE
OFF MEGA V+
Absorbtion
xxxA Load+ GND
PV 100Vmax 50A INSERTED HERE IF NEEDED,
INCLUDING NECESSARY
Float
Bulk
BREAKERS.
MEGA
xxxA Load+ PV ARRAY
VE.Direct-1
VE.Direct-2
VE.Direct
VE.Bus
ETHERNET
VRM
MEGA WORLD
PRE-MAIN-FUSE xxxA Load+
1A FUSE
name name
ANL
60 AMPERE
600A
285060F
A
B
T
PV BREAKERS
D
A
L
100mA FUSE
SE
T MPPT+ ISOLATORS
RE
OFF
MultiPlus Batt +
MEGA
ON 400A
MAINSWITCH-2
MultiPlus Batt +
AC POWER SOURCE MAIN INCOMING
CHANGE OVER SWITCH AC BREAKERS
MULTIPLUS 5KW/24V/230V AC INVERTER/CHARGER
BMV-712 SMART
BMV-712 SMART
BATTERY MONITOR
victron energy
BLUE POWER
MAIN V
0
Shore Gen
victron energy name name
BLUE POWER
0 OFF 0 OFF 0 OFF 0 OFF
www.victronenergy.com
charger inverter
AGM Super Cycle Battery mains on
I on
inverter on
CENTRAL NEGATIVE.BusBAR
AC in 1 AC out 1
bulk overload
AC out 2 O off
absorption low battery
charger only
float temperature
MultiPlus Battery
.powerassist .parallel
connectable
.three phase
connectable
VOLT
24 |5000 |120
AMP
VA
AC transfer capacity: 100A | Inverter 230V
CE
Load-
1 N 1 N
Load-
victron energy
BLUE POWER name name name name name name name name
ADxxxxx xxA/I n0.03A ADxxxxx xxA/I n0.03A
MPPT- Bx
T
test regularly Bx
T
test regularly
MultiPlus Batt-
AGM 12-230
earth fault indicator earth fault indicator
Recommended AC Out-2 cable/breaker size MultiPlus Recommended AC Out-1 cable/breaker size MultiPlus Recommended DC cable/fuse size MultiPlus Recommended AC IN WARNING
cable/breaker size MultiPlus
AC Out-2 only is available when power is With Power assist the MultiPlus can add 0-5 m cable length: 4 x 50SQmm 230 VOLT IS EXTREMELY HAZARDOUS
present on AC IN. During battery operation 5KW to the output load when needed. 5-10 m cable length: 4 x 95SQmm AC IN must be protected by a circuit DO NOT TOUCH ANY LIFE WIRED
it will be disconnected. AC Out-2 supports Together with the adjustable 100A input Cable length stands for the distance between the breaker rated at 100A max or less. This PARTS OF THE INSTALLATION !!!
up to 50A. An Earth leakage device with this all adds up to the max sum of input battery connections and the MultiPlus connections depends heavily on the size of the WHEN IN DOUBT, ALWAYS CONSULT
breaker or a combination MCB/RCD must and output current of 100+21=121A. An !!! Recommendations are without other loads in the connected power source.The input current YOUR VICTRON DEALER !!!
be installed on the output. Cable size must Earth leakage device with breaker or a system and these also should be taken into must be adjusted to fit the size of the
be adjusted accordingly. combination MCB/RCD must be installed account for proper main battery, main fuse & main connected power source.
on the output. Cable size must be adjusted switch cables !!! The breaker and cable size for AC IN
accordingly. Fuse size should be 1 x 400A. should be adjusted accordingly.