You are on page 1of 1

LEGEND DC SOURCE - 1 DC SOURCE - 2

INCOMING SUPPLY INCOMING SUPPLY


SWITCH IOCL SCOPE IOCL SCOPE

MCB 3R X 3C X 300 Sq.MM Ar.Cu.

FUSE

110V DCDB (FLOOR MOUNTED)


INDICATING
LAMP LOCATION - CRP ROOM

MONITORING
STATUS FOR
MONITORING
STATUS FOR

SCADA
NOTE :

SCADA
1 DC SUPPLY 1 & 2 WILL BE FEEDING DC
LOAD CONTINUOUSLY AND BUS
SECTIONALIZER CAN BE USED IN EMERGENCY
(MANUALLY) IN THE EVENT OF ISSUE WITH ANY
OTHER SOURCE

125A DP SWITCH 125A DP SWITCH


(INCOMER -1) (INCOMER - 2)

125A HRC FUSE 125A HRC FUSE

0 - 125A 0 - 125A
A A
A A
TRD TRD
WITH DUAL WITH DUAL
O/P 4 - 20mA O/P 4 - 20mA
0 - 150V 0 - 150V
V V
V V
4A TRD 4A TRD
WITH DUAL WITH DUAL
O/P 4 - 20mA 125A DP SWITCH 110V DC, 10kA O/P 4 - 20mA
(SECTIONALIZER) COPPER B/B

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

32A 32A 32A 32A 32A 32A 32A 32A 32A 32A 32A 32A 32A 32A 32A 32A 32A 32A 32A 32A
DPMCB DPMCB DPMCB DPMCB DPMCB DPMCB DPMCB DPMCB DPMCB DPMCB DPMCB DPMCB DPMCB DPMCB DPMCB DPMCB DPMCB DPMCB DPMCB DPMCB

DC SOURCE - 1 DC SOURCE - 2 EARTH BUS


INCOMING SUPPLY INCOMING SUPPLY
IOCL SCOPE IOCL SCOPE

3C X 50 Sq.MM Ar.Cu. E E

2C X 4 Sq.MM Ar.Cu.

2C X 4 Sq.MM Ar.Cu.
220/33KV TR-1 CRP

220/33KV TR-2 CRP

220/33KV TR-1 CRP

220/33KV TR-2 CRP


110V DCDB (WALL MOUNTED

220KV I/C-1 CRP

220KV I/C-2 CRP

220KV I/C-1 CRP

220KV I/C-2 CRP


DC SOURCE - 1

DC SOURCE - 1

DC SOURCE - 1

DC SOURCE - 1

DC SOURCE - 1

DC SOURCE - 2

DC SOURCE - 1

DC SOURCE - 2

DC SOURCE - 2

DC SOURCE - 2
220KV B/C CRP

220KV B/C CRP


LOCATION - 33KV CRP ROOM

EMERGENCY
MONITORING
STATUS FOR
MONITORING
STATUS FOR

LIGHTING

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE
SCADA
SCADA

32A DP SWITCH 32A DP SWITCH


(INCOMER -1) (INCOMER - 2)

32A HRC FUSE 32A HRC FUSE

0 - 30A 0 - 30A
A A
A A
TRD TRD
WITH DUAL WITH DUAL
O/P 4 - 20mA O/P 4 - 20mA
0 - 150V 0 - 150V
V V
V V
4A TRD 4A TRD
WITH DUAL WITH DUAL
O/P 4 - 20mA O/P 4 - 20mA
110V DC, 10kA
COPPER B/B

32A DP SWITCH
(SECTIONALIZER)
1 2 3 4 5 6

6A 6A 6A 6A 6A 6A
DPMCB DPMCB DPMCB DPMCB DPMCB DPMCB

INDIAN OIL CORPORATION LIMITED


REFINERIES DIVISION, VADODARA
EARTH BUS
CONTRACTOR :-
RAJESH POWER SERVICES PVT. LTD.
"SIDDHI HOUSE", B/H. KAMALDEEP APARTMENT, OPP. LAL BUNGLOW,

E
OFF. C.G. ROAD, NAVRANGPURA, AHMEDABAD - 380 006

E E-MAIL : TECHNICAL@RAJESHPOWER.COM

PROJECT:-
LILO OF S/C OF 220KV ASOJ-IOCL LINE FOR FEEDING
POWER TO IOCL PLANT AT DUMAD

WORK ORDER
2C X 4 Sq.MM Ar.Cu.

2C X 4 Sq.MM Ar.Cu.

NO. :- 27342006 DTD : 06-11-2021


33KV CRP PANEL

33KV CRP PANEL


DC SOURCE - 1

DC SOURCE - 1

DC SOURCE - 2

DC SOURCE - 2

220KV SWITCHYARD - IOCL DUMAD


110V DC DISTRIBUTION SINGLE LINE DIAGRAM
SAS PANEL

SAS PANEL
SPARE

SPARE

DRAWN: CHECKED: APPD:

SIZE:
DEVANG RAVI BHALODIA BIREN SHAH
A0
R1 REVISED AS PER IOCL COMMENTS
SCALE: DATE: DRG. NO: SHEET: REV:
R0 FIRST PREPARATION
N.T.S. 30.01.2023 RPSPL/IOCL-D/ELE/009 1 OF 1 R1
REV: DESCRIPTION