Professional Documents
Culture Documents
SUMMARY: The coatings on modern pipelines for the oil and gas industry combine durability
with high resistivity to provide environmental and electrical protection against corrosion.
Impressed current cathodic protection (ICCP) from a transformer rectifier may be used to
provide additional corrosion protection. The high resistance of the pipeline coating when first
installed may require little protection current but the current requirement after many years in
service can be significantly greater. The requirement for the rectifier control system to
operate in a stable manner over a very wide dynamic range creates design problems
because the pipeline may require very little current when first installed.
This paper discusses the reason that rectifier instability can occur in such situations and
methods that can be used to mitigate or eliminate rectifier instability.
1. INTRODUCTION
Modern gas and water pipelines are often provided with mill applied outside coatings made from plastics or
epoxies which have good insulating properties. (1) The DC electrical resistance of a pipe applied with these
coatings in good condition to ground, can be many millions of ohms even for long lengths of pipe (2). The output
current the rectifier delivers is determined by Ohms Law I = V/R, where I is current, V is rectifier voltage and R is
the total circuit resistance. If R is high then I will be correspondingly low.
The pipe also has AC electrical characteristics of capacitance, which depends on the insulation thickness and
inductance, which depends on the pipe length and diameter. In addition, the longer the pipe the more it is
susceptible to external electrical and magnetic fields such as induced voltages from powerlines and induced
currents from telluric or soil currents. In essence, the pipe is also a long antenna whose sensitivity to picking up
these external signals is increased as the pipe has higher resistance to ground.
This combination of low current demand and susceptibility to external electrical influences can lead to cases like
the following.
Case 1. A 30V 10A rectifier is commissioned on a newly finished pipeline. The operating voltage for full
protection is a fluctuating 3V and close to zero current, which does not display on the analog ammeter
used. The operators are unsure if the rectifier is operating at all.
Case 2. A 20V 5A cathodic protection system is installed on a long pipeline running north south in an
iron ore rich area. The output voltage sometimes rises slowly to about 12V and the rectifier current
subsides to zero then the voltage falls to a few volts and the current rapidly increases to a few amps. Is
the rectifier functioning correctly?
Case 3. A series of 20V 10A rectifiers are installed on a new pipe network that has temporary zinc mesh
earthing. The output voltage is a low value and the rectifiers do not delivery any current. The pipeline
remains protected. The customer questions the need for the expenditure on impressed current
cathodic protection rectifier systems.
This paper will discuss how these observations relate to the problem of rectifier stability and suggest mitigation
strategies.
2. FEEDBACK CONTROL
Rectifiers installed on pipe systems usually have some form of automatic control to hold the output constant
against some given value without manual intervention.
Common modes of operation of rectifiers used on pipelines are constant voltage, where the rectifier output
voltage remains constant for varying current, constant current, where the output current remains constant
although the voltage can vary and constant potential, where the voltage from an external reference is held
constant and both the voltage and current vary.
To hold the output of any system constant the output is checked, or sampled, and compared to the desired
value. Any difference between the desired value and the sample of the output value becomes an error signal.
The error signal is fed into the device which provides the output, in our case ,the rectifier, and the output moves
up or down to make it closer to the desired output set by the control signal.
This control process is called negative feedback and can be shown in a simple system as below
The rectifier may not respond instantly to the change in control and if the response is delayed the situation could
arise where the rectifier is always trying to respond to an output which has already changed. The output might
then oscillate or ‘hunt’.
This could be imagined as a driver trying to reach a constant speed while driving a car that is very slow to
respond to the accelerator being depressed or released. The driver reaches the speed they desire and
releases the accelerator but the car continues to accelerate. Releasing the pedal doesn’t slow the car until later
and it loses speed to below the desired level, never achieving the desired speed.
This delay between input and output is called, in control theory, phase shift.
The rectifier may also respond to the change in control by increasing or decreasing the output by a large
amount for a small change in control signal. This might be analogous to our driver now driving a powerful sports
car where a small touch of the accelerator instantly increased the car speed to above the desired level.
Releasing the pedal instantly engages a brake and the speed drops. Again, the driver can’t achieve the desired
speed.
It is possible to see if a system will be stable, that is, if the driver will be able to settle on the desired speed, by
examining the values of gain and phase shift versus frequency using the technique called “Bode” plotting.
Frequency can be imagined as how fast you can depress and release the accelerator or how fast you can
increase and decrease the control potentiometer of the rectifier.
A Bode plot shows the gain of the forward system, be it rectifier or car, versus frequency and the phase shift of
the forward system versus frequency.
Examining the gain and phase shift can show if the system will be stable by calculation of a value called gain
margin
Gain Margin. The gain in dB must be less than zero dB (less than a gain of 1 ) when the phase shift is 180
degrees. This can be understood being that the feedback signal when the phase shift is 180 degrees – acting
to amplify the output, not reduce it, must occur when the gain is less than 1 or the system will oscillate
For a fixed phase shift the higher the gain, the closer to instability the control system will be and will become
unstable if the gain is above zero db at 180 degrees phase shift. (5)
While simple in construction and reliable in operation, the drawback to this type of rectifier is that the output will
not compensate for any changes in environmental conditions such as the circuit loop resistance. The output
from the rectifier is approximately constant voltage and the current varies in proportion to the loop resistance.
Rectifiers with closed loop feedback control can be adjusted over a wide operating range in voltage, current or
potential modes and have advantages in setting maximum output current and voltage to protect anodes and to
reduce the chance of overprotection of the protected structure. (7)
A block diagram for a thyristor controlled rectifier with feedback, commonly used for cathodic protection is
shown below in figure 3.
Understanding from the Bode plot that increased gain leads to reduced stability provides a way of examining
why a rectifier with closed loop control might be unstable .
Gain is the ratio of the error signal to the rectifier output in the case we are considering. It can be shown that
the higher the gain, the less is the difference between the control signal and the feedback signal and so the
closer the output is to the desired set point. (9) A requirement to provide a tightly regulated output over a wide
range will require higher gain and the stability of the system may be reduced.
Figure 4 Thyristor controlled cathodic protection rectifier with feedback and external source
Figure 4 shows an external source connected to the pipeline in parallel with the rectifier. When the external
source, a telluric in this case. causes the pipeline voltage to drop the rectifier will compensate by delivering
current to the CP load. When the external source causes the voltage to rise above the desired setpoint the
rectifier, which is unable to prevent that voltage rise, will not deliver any current.
In the case of auto-potential control, a voltage is derived from a half cell connected to the pipe. If the half-cell
measured value exceeds the value of the setpoint i.e is more protected, there is no action the rectifier can take
to pull the pipe back to a less protected state. The closest action the feedback circuit can undertake is to switch
off the output.
In all the above cases, the specific electrical characteristics of a well-coated pipe, combined with the
consequential requirements for minimal protective current, when used with a feedback controlled rectifier, led to
the issues described of instability or unexpected behavior.
Voltage taps at 25%, 50% and 75% of rated transformer output are sometimes specified for this purpose. A
reduced maximum output voltage has several advantages as well as reducing the gain, which include reduced
AC ripple, lower AC input current and lower transformer losses. However, this strategy also reduces the
maximum voltage of the rectifier and it may be necessary to monitor rectifier performance to ensure that the
rectifier can deliver sufficient voltage to provide protective current in the worst case of high circuit loop
resistance
Australian Standards for cathodic protection do not specify a required rate of response for the rectifier (10).
6. CONCLUSION
Transformer rectifiers for well coated pipelines have to be able to operate in a stable way when the pipeline
coating is in good condition and little current is required. The same rectifier must also be able to provide
sufficient protective current to the pipeline when the coating has degraded.
This paper discusses causes for unstable rectifier operation based on the control theory technique of Bode
analysis and suggests ways of improving stability by additional loading, e.g. the backhoe approach, and by
other strategies that can reduce gain or increase stability.
Well coated metallic pipelines are likely to be in use for many years and the requirement for pipelines to be
cathodically protected will accompany them. Stable operation of the rectifier will be necessary to provide
consistent, effective cathodic protection and to reassure the operators and asset owners that the rectifier is
operating in a predictable and well- mannered way.
7. REFERENCES
1. The Evolution of Pipeline Coatings [Gas Exploration]KTA University. Senkowski E. B
https://ktauniversity.com/evolution-pipeline-coatings/
2. Cathodic Protection issues with Ultra Well coated Pipelines. Martin B and Brodribb R. Presented ACA
National Conference 2007.
3. Feedback and Control systems, page 112. Distefano J, Stubberud, A, Williams I, McGraw Hill New
York, NY. 1967.
4. “Introduction to Operational Amplifiers – Microchip 2018
http://microchipdeveloper.com/asp0107:phase-gain-margins
5. Reference data for Radio Engineers, 4th Edition IT and T, Chapter 14. New York, NY 1949.
6. VEC Resource Manual DOC /14/11619, Energy safe Victoria 2014
7. Cathodic Protection Design Recommended Practice DNV-RP-B401, section 5.5. Det Norske Veritas
2011
8. “The design of a simple single phase Silicon Controlled Rectifier Regulator” McVey E, Russell, R, IEEE
International Convention Record, Part 8, March 1966
9. Feedback and Control systems, Pg 164, op.cit
10. AS 2832.1 – 2015. Cathodic Protection of Metals – Pipes and Cables.