You are on page 1of 2

E N C L O S U R E S

Exclusively from your Caterpillar® dealer

CAE – SOUND ATTENUATED


WEATHERPROOF ENCLOSURE
FOR GAS GENERATOR SETS
10-30 kVA, 50 Hz
11-31 kVA, 60 Hz
These weatherproof, sound attenuated, factory
designed and installed enclosures are of rugged
construction and sound attenuated down to
extremely quiet levels.
They incorporate internally mounted silencers
for safety and aesthetic value. Modular design
principles utilize many interchangeable
components permitting on-site repair.

FEATURES
HIGHLY CORROSION EXCELLENT ACCESS FOR SECURITY AND SAFETY
RESISTANT CONSTRUCTION MAINTENANCE ● Lockable access doors
● Body made from galvanized ● Large cable entry area for ● Cooling fan and battery
steel installation ease charging alternator fully
● Black zinc die cast hinges ● Large doors located guarded
tested and proven to convenient to controls and ● Exhaust silencing system
withstand extreme service areas for easy access totally enclosed for operator
conditions of corrosion to control panel, circuit safety
● Zinc plated or stainless breaker and ● Roof outlet exhaust with roof
steel fasteners engine/generator aperture and rain cap
● Vertically hinged “lift-off”
● Sheet steel components pre- ● Emergency stop push button
treated with zinc phosphate doors allow full 180° (red) mounted flush on
prior to polyester powder opening rotation exterior enclosure wall
coating at 200°C (392°F) ● Lube oil and cooling drains ● Stub-up cover for “rodent
piped to edge of enclosure proofing”
and terminated with drain
valves
TRANSPORTABILITY
● Lifting/drag points on
baseframe

W H E R E T H E W O R L D T U R N S F O R P O W E R
E N C L O S U R E S
Exclusively from your Caterpillar® dealer
SOUND PRESSURE LEVELS (dBA)
50 Hz at 1500 rpm 60 Hz at 1800 rpm
Sound 15 m 7m 1m 15 m 7m 1m
Generator Power
Set Level 75% 100% 75% 100% 75% 100% 75% 100% 75% 100% 75% 100%
Model Duty (LWA) Load Load Load Load Load Load Load Load Load Load Load Load
Prime 85.0 52.8 53.7 58.9 59.8 69.1 70.2 55.7 55.9 61.8 62.0 72.7 72.8
GEUG16-1,
Standby 85.0 52.8 53.7 58.9 59.8 69.1 70.2 55.7 55.9 61.8 62.0 72.7 72.8
Prime 94.4 63.6 64.5 69.7 70.6 80.1 80.8 67.5 67.4 73.6 73.5 84.5 84.5
GEUHG30-1
Standby 94.4 63.6 64.5 69.7 70.6 80.1 80.8 67.5 67.4 73.6 73.5 84.5 84.5
Prime 84.1 55.7 57.1 61.8 63.2 70.4 73.2 56.9 58.9 63.0 65.0 73.0 75.2
GEFG25-1
Standby 84.1 55.7 57.1 61.8 63.2 70.4 73.2 56.9 58.9 63.0 65.0 73.0 75.2
Prime 85.0 52.8 53.7 58.9 59.8 69.1 70.2 55.7 55.9 61.8 62.0 72.7 72.8
GEUG13S1
Standby 85.0 52.8 53.7 58.9 59.8 69.1 70.2 55.7 55.9 61.8 62.0 72.7 72.8
Prime 94.4 63.6 64.5 69.7 70.6 80.1 80.8 67.5 67.4 73.6 73.5 84.5 84.5
GEUHG24S1
Standby 94.4 63.6 64.5 69.7 70.6 80.1 80.8 67.5 67.4 73.6 73.5 84.5 84.5
Prime 84.1 55.7 57.1 61.8 63.2 70.4 73.2 56.9 58.9 63.0 65.0 73.0 75.2
GEFG20S1
Standby 84.1 55.7 57.1 61.8 63.2 70.4 73.2 56.9 58.9 63.0 65.0 73.0 75.2

The sound pressure level data shown is free field and for guidance only. Actual levels produced may vary according to site conditions.

Generator Set A B C D E Weight*


Model mm (in) mm (in) mm (in) mm (in) mm (in) kg (lb)
GEUG16-1 1970 (77.6) 850 (33.5) 1175 (46.3) 1290 (50.8) 900 (35.4) 560 (1235)
GEUHG30-1 1970 (77.6) 850 (33.5) 1175 (46.3) 1290 (50.8) 900 (35.4) 563 (1241)
GEFG25-1 1970 (77.6) 850 (33.5) 1200 (47.2) 1315 (51.8) 900 (35.4) 602 (1327)
GEUG13S1 1970 (77.6) 850 (33.5) 1175 (46.3) 1290 (50.8) 900 (35.4) 560 (1235)
GEUHG24S1 1970 (77.6) 850 (33.5) 1175 (46.3) 1290 (50.8) 900 (35.4) 563 (1241)
GEFG20S1 1970 (77.6) 850 (33.5) 1200 (47.2) 1315 (51.8) 900 (35.4) 602 (1327)
**Net weight with lube oil and coolant

www.CAT-ElectricPower.com

© 2001 Caterpillar
All rights reserved.
European sourced Printed in U.S.A.

Materials and specifications are subject to change without notice.


LEHF1346 (03-01) The International System of Units (SI) is used in this publication.

You might also like