Professional Documents
Culture Documents
SPECIFICATION
FOR
(NFOC)
TABLE OF CONTENTS
1.0 SCOPE
4.1 General
4.2 Design Criteria
4.3 Optical Fiber
4.4 Color Coding
7.0 TESTS
1.0 SCOPE
2.0 CROSS-REFERENCES
This Material Standard Specification shall be read in conjunction with the SCECO-
East General Specification No. 01-SMSS-01 titled "General Requirements for All
Equipment/ Materials", which shall be considered as an integral part of this SMSS.
This SMSS shall also be read in conjunction with SCECO-East Purchase Order or
Contract Schedules for project, as applicable.
The latest revision of the following Codes and Standards shall be applicable for the
equipment/material covered in this SMSS. In case of conflict, the vendor/
manufacturer may propose equipment/material conforming to one group of Industry
Codes and Standards quoted hereunder without jeopardizing the requirements of this
SMSS.
3.4 EIA/TIA 455 Standard Test Procedures for Fiber Optic Fibers, Cables,
Transducers, Sensors, Connecting and Terminating Devices,
and other Fiber Optic Components.
4.1 General
4.1.1 The Non-Metallic Fiber Optic cables (NFOC) shall meet or exceed the
requirements of this Specification in all respects.
Table I
Dispersion
Unshifted Single
Mode
i) @ 1300 nm 0.45 dB/km Less than 3.5 ps/nm/ 1310 ± 10nm Nominal value shall lie
Operating at 1300 nm km in 1285 nm to between the range of 9
Wavelength 1330 nm to 10 µm at 1300 nm
Operating Wavelength
with allowable + 5%
deviation from nominal
value.
ii) @ 1550 nm 0.25 dB/km Less than 20 ps/nm/ Nominal Value shall lie
Operating at 1550 nm km at 1550 nm between the range of 10
Wavelength to 11 µm at 1550 nm
Operating Wave-length
with allowable
deviation of + 10%.
4.3.1 The Optical Fiber shall be made of germanium doped silica glass or
pure silica glass.
4.3.3 The cladding of the Optical Fiber shall be made of silica glass having
lower refractive index. The outside diameter of the cladded fiber shall
be 125 µm with tolerance of ± 2.0 µm.
4.3.5 The nominal fiber coating diameter shall be in the range of 250 – 40
µm.
4.3.6 There shall be no joints or splices in any optical fiber in any reel
length of the complete optical cable.
4.3.8 Each group of fiber may be enclosed in a loose buffer tube or may be
taped in a helical fashion to provide protection against mechanical
stresses and environmental effects.
4.3.9 The buffer shall be easily removed. If special tools are recommended
by the manufacturer; these shall be provided.
4.4.1 The individual color and group color coding scheme of optical fibers
shall be as specified in Table II.
4.4.2 The scheme applies to optical fiber cable where fibers are physically
separated.
4.4.3 Optical fibers within a cable shall be grouped and each group shall
contain six fibers.
4.4.4 When a number of optical fibers form a group, the group shall be
uniquely identified.
4.4.6 When groups are defined by means of tubes, binder tapes, ribbons,
threads, etc., such means shall be discernible and uniquely color
coded as shown in Table II.
Table II
The complete NFOC shall have the following minimum dimensions and ratings :
5.1 The fiber optic cable shall be able to withstand a compressive stress specified
in Data Schedule without mechanical or optical degradation.
5.2 The tensile strength of the fiber optic cable shall be such that the nominal
pulling tension specified in Data Schedule cause no temporary or permanent
optical degradation and cable damage.
5.3 The minimum bending radius of cable that can be applied without temporary or
permanent optical degradation shall not exceed 200 mm radius.
5.4 The types of Non-metallic Fiber Optic Cables are the following:
6.1.2 Strength members shall be an integral part of the cable assembly but are
not considered part of the messenger support component.
6.1.5 The wrapping tape shall be dielectric material. The wrapping tape may
be used as a heat barrier to prevent deformation and contain the inner
core.
6.1.6 Filling gel shall be applied to the core wrap so that voids or air spaces
are eliminated between the core and the inner side of the slot.
This type of fiber optic cable shall be used for direct buried applications.
a. The inner (first) sheath surrounding the tube or core shall be made
of medium density polyethylene (MDPE)
This type of fiber optic cable shall be used for duct applications.
This type of fiber optic cable shall be used for indoor applications.
All test results shall be provided for review and acceptance by SCECO-East.
In lieu of the actual type (design) tests, certified test reports of type
(design) tests performed on an identical unit may be submitted to
SCECO-East for review and approval during the bidding stage.
The cut-off wavelength of the cabled fiber, shall be less than l250
nm and shall be measured in accordance to EIA/TIA-455-170, cable
cutoff wavelength of Single Mode Fiber by transmitted power.
Water ingress tests for cables designed for water blocking shall be
performed in accordance with the requirements of EIA-455-82B,
Fluid Penetration Test for Fluid Blocked Fiber Optic Cable, in l
(one)m cable sample.
No water shall leak through the open end of l m sample. If the first
sample fails, one additional l m sample, taken from a section of
cable adjacent to the first sample may be tested for acceptance.
Water leaks from second sample shall constitute failure.
d. Vibration Test
f. Creep Test
c. Micro-Bending
In lieu of the actual type (design) tests, certified test reports of type
(design) tests performed on an identical unit may be submitted to
SCECO-East for review and approval during the bidding stage.
a. Attenuation Coefficient
c. Chromatic Dispersion
e. Concentricity Error
g. Coating Diameter
Upon receipt of the NFOC from the manufacturer, the purchaser shall at his
option, perform acceptance tests in order to verify that the optical
characteristics of the fiber meet the order requirements and to determine if
optical fibers have been damaged during shipment. The results of these tests
and the manufacturer's certified quality control information, which is attached
to each reel, shall be compared to the fiber requirements specified in the
purchase order.
7.3.2 Attenuation
Total attenuation for the entire reel length and attenuation per kilometer
should be measured on each fiber. Attenuation uniformity shall meet
the requirements of Section 7.2.2.b.
The fiber length may be measured using the OTDR. The index factor
to be used in this measurement should be furnished by the fiber
manufacturer. A check should be made to verify received reel numbers
and lengths correspond to ordered quantities.
8.1 The NFOC ends shall be sealed with a waterproof, heat shrinkable plastic or
elastomeric end cap with adhesive type sealing compound. NFOC ends shall
be properly secured to the reel.
8.2 The NFOC shall be delivered without splices, on standard sized non-returnable
wood drums properly packed and lagged externally to prevent the cable from
possible damage during transportation. Wood lagging shall be used and have a
minimum thickness of 25 mm.
8.3 For all NFOC purchases, the standard order length shall be 2000 meters. For
NFOC intended for Turnkey Projects, the order length shall be as specified in
Data Schedule.
d. Gross Weight
e. Dimensions of Reel
k. 11-SMSS-14, Rev. 1
8.4.2 All markings shall appear on both sides of the reel. Reel marking
locations shall be shown in Figure 1.
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Cladding Material
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Attenuation Loss:
at 1310 nm (dB/km) *
at 1550 nm (dB/km) *
at 1550 nm (ps/nm/km) *
Cladding Non-Circularity *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Connection Material *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Filling compound *
Wrapping Tape *
Compression (mm) *
Installation (mm) *
Operation (mm) *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Temperature during:
Operation °C *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Filling Compound *
Wrapping Tape *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Compression (mm) *
Temperature during:
Operation (°C) *
Filling Compound *
Wrapping Tape *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
(Installation) (mm) *
(Operation) (mm) *
Temperature during:
Operation (°C) *
Wrapping Tape *
Sheath Material *
REFERENCE
SECTION NO. DESCRIPTION 'A' 'B' 'C'
Compression (N/mm) *
(Installation) (mm) *
(Operation) (mm) *
Official Seal/Stamp
of the Company