Control
→ Parallel
Profibus DP
Modbus
DeviceNet
Foundation Fieldbus
Reference documents:
● Manual (Operation and setting) AUMATIC AC 01.1/ACExC 01.1 Parallel
Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA
(refer to <Addresses>).
2
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Table of contents
6. Operation................................................................................................................................ 22
6.1. Manual operation 22
6.1.1 Manual operation: engage 22
6.1.2 Manual operation: disengage 22
6.2. Motor operation 22
6.2.1 Local operation 22
6.2.2 Operation from REMOTE 23
6.3. Menu navigation via push buttons (for settings and indications) 24
6.3.1 Short overview: Functions of the push buttons 24
6.3.2 Structural design and navigation 24
6.4. Password entry 25
6.5. Language change in the display 26
7. Indications.............................................................................................................................. 28
7.1. Status indications in the display 28
7.1.1 Status indication S0/S6 - operation 28
7.1.2 Status indication S4 - torque 29
7.1.3 Torque indication: edit 29
7.2. Indication lights/LEDs 29
7.3. Mechanical position indicator/running indication 30
8. Signals..................................................................................................................................... 31
8.1. Feedback signals via output contacts (binary) 31
8.2. Feedback signals (analogue) 31
9. Commissioning (basic settings)........................................................................................... 32
9.1. Heat-up time for low temperature version 32
9.2. End stops in part-turn actuator 32
9.2.1 End stop CLOSED: set 33
9.2.2 End stop OPEN: set 34
9.3. Swing angle 34
9.3.1 Swing angle: modify 35
9.4. Type of seating: check/edit for end positions 36
9.5. Torque switching: check/set 39
9.6. Limit switching: set 43
9.7. Test run 46
9.7.1 Direction of rotation: check 46
9.7.2 Limit switching: check 46
9.8. Switch compartment: open 47
9.9. Mechanical position indicator: set 47
9.10. Switch compartment: close 48
9.11. Operating time: set 48
10. Corrective action.................................................................................................................... 50
10.1. Faults during commissioning 50
10.2. Fault indications and warning indications 50
10.2.1 Status indication S0 - faults and warnings 50
10.2.2 Status indication S1 - faults 50
10.2.3 Status indication S2 - warnings 51
10.2.4 Status indication S3 - causes for not ready remote 52
10.3. Fuses 52
10.3.1 Fuses within the actuator controls 52
10.3.2 Motor protection (thermal monitoring) 53
3
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Table of contents AC 01.1 Non-Intrusive
4
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Safety instructions
1. Safety instructions
1.1 Basic information on safety
Standards/directives AUMA products are designed and manufactured in compliance with recognised
standards and directives. This is certified in a Declaration of Incorporation and an
EC Declaration of Conformity.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
Safety instructions/war- All personnel working with this device must be familiar with the safety and warning
nings instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to avoid personal injury or property
damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out exclusively by suitably qualified personnel having been authorised by
the end user or contractor of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Commissioning Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation. The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Maintenance To ensure safe device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior consent of the manufacturer.
1.2 Range of application
AUMA part-turn actuators are designed for the operation of industrial valves, e.g.
butterfly valves and ball valves.
Other applications require explicit (written) confirmation by the manufacturer.
5
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Safety instructions AC 01.1 Non-Intrusive
● Escalators
● Continuous duty
● Buried service
● Permanent submersion (observe enclosure protection)
● Potentially explosive areas, with the exception of zone 22
● Radiation exposed areas in nuclear power plants
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device's
designated use.
Information These operation instructions are only valid for the "clockwise closing" standard
version, i.e. driven shaft turns clockwise to close the valve.
1.3 Applications in Ex zone 22 (option)
Actuators of the indicated series basically meet the requirements for applications in
dust hazardous locations of ZONE 22 in compliance with the ATEX directive 94/9/EC.
The actuators are designed to meet enclosure protection IP 67 or IP 68 and fulfil the
requirements of EN 50281-1-1:1998 section 6 - Electrical apparatus for use in
presence of combustible dust, requirements for category 3 electrical equipment -
protected by enclosures.
To comply with all requirements of EN 50281-1-1:1998, it is imperative that the
following points are observed:
● In compliance with the ATEX directive 94/9/EC, the actuators must be equipped
with an additional identification – II3D IP6X T150 °C.
● The maximum surface temperature of the actuators, based on an ambient
temperature of +40 °C in accordance with EN 50281-1-1 section 10.4, is +150
°C. In accordance with section 10.4, an increased dust deposit on the equipment
was not considered for the determination of the maximum surface temperature.
● The correct connection of the thermoswitches or the PTC thermistors as well
as fulfilling the requirements of the duty type and the technical data are prere-
quisites for compliance with the maximum surface temperature of devices.
● The connection plug may only be plugged in or pulled out when device is dis-
connected from the mains.
● The cable glands used also have to meet the requirements of category II3 D
and must at least comply with enclosure protection IP 67.
● The actuators must be connected by means of an external ground connection
(accessory part) to the potential compensation or integrated into an earthed
piping system.
● As a general rule, the requirements of EN 50281-1-1 must be respected in dust
hazardous locations. During commissioning, service, and maintenance, special
care as well as qualified and trained personnel are required for the safe opera-
tion of actuators.
1.4 Warnings and notes
6
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Safety instructions
Information The term Information preceding the text indicates important notes and information.
7
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Identification AC 01.1 Non-Intrusive
2. Identification
2.1 Name plate
Each device component (actuator, controls, motor) is equipped with a name plate.
Figure 1: Arrangement of name plates
8
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Identification
Commission number An order-specific commission number is assigned to each device. This commission
number can be used to directly download the wiring diagram, inspection records and
further information regarding the device from the Internet: http://www.auma.com.
Wiring diagram The 7th position in the ACP wiring diagram indicates the type of feedback signals
from the actuator:
M = MWG, <Non-Intrusive version>.
P = Potentiometer
R = RWG (electronic position transmitter)
Control
24 V DC = Control via parallel interface at 24 V DC control voltage.
115 V AC = Control via parallel interface at 115 V AC control voltage.
0/4 – 20 mA = Control via parallel interface via analogue input 0/4 – 20 mA.
2.2 Short description
9
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Transport, storage and packaging AC 01.1 Non-Intrusive
Hovering load!
Risk of death or serious injury.
→ Do NOT stand below hovering load.
→ Attach ropes or hooks for the purpose of lifting by hoist only to housing and NOT
to handwheel.
→ Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
→ Actuators mounted to gearboxes: Attach ropes or hooks for the purpose of lifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.
→ Actuators mounted to controls: Attach ropes or hooks for the purpose of lifting
by hoist only to the actuator and NOT to the controls.
3.2 Storage
Long-term storage If the device must be stored for a long period (more than 6 months) the following
points must be observed in addition:
1. Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:
Check for corrosion. If first signs of corrosion show, apply new corrosion protec-
tion.
3.3 Packaging
Our products are protected by special packaging for transport when leaving the
factory. The packaging consists of environmentally friendly materials which can easily
be separated and recycled. We use the following packaging materials: wood,
cardboard, paper, and PE foil. For the disposal of the packaging material, we
recommend recycling and collection centres.
10
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Assembly
4. Assembly
AUMA actuators and actuator controls can be operated without restriction in any
mounting position.
1. Remove cap nut [1] and pull out ball handle [2].
2. Insert ball handle [2] in correct position and fasten with cap nut [1].
11
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Assembly AC 01.1 Non-Intrusive
4.3.1 Coupling
[1] Coupling
[2] Valve shaft
[3] Grub screw
[4] Screw
12
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Assembly
The mounting position of the local controls is selected according to the order. If, after
mounting the actuator to the valve or the gearbox on site, the local controls are in
an unfavourable position, the mounting position can be changed at a later date. Four
mounting positions are possible.
Figure 7: Mounting positions A-2 and B-2
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
13
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Assembly AC 01.1 Non-Intrusive
14
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Electrical connection
5. Electrical connection
5.1 Basic information
Wiring diagram/terminal
The pertaining wiring diagram/terminal plan (in German and English language) is
plan attached to the device in a weather-proof bag, together with these operation
instructions. It can also be obtained from AUMA (state commission no., refer to name
plate) or downloaded directly from the Internet (www.auma.com).
Protection on site
For short-circuit protection and for disconnecting the actuator from the mains, fuses
and disconnect switches have to be provided by the customer.
The current values for respective sizing is derived from the current consumption of
the motor (refer to electrical data sheet) plus the current consumption of the controls.
If controls are mounted separately from actuator (controls on wall bracket): Consider
length and cross section of connecting cable when defining the protection required.
Power supply for the
If the controls (electronics) are supplied externally with 24 V DC and DC motors (24
controls (electronics) V DC, 48 V DC, 60 V DC, 110 V DC, 220 V DC) are used simultaneously, the 24 V
DC voltage supply for the controls should be ensured via the XK25/26 terminals,
separately from the power supply (U1, V1). In case of common supply using a single
cable (links from U1, V1 with XK25/26, for 24 V DC only !!!), short-term excess or
falling below the permissible voltage limits can be the consequence during switching
(24 V DC +10 %/–10 %). Any possibly incoming operation commands are not
executed outside the admissible limit values. The controls briefly signal a fault
condition.
Potential of customer All input signals (control) must be supplied with the same potential.
connections All output signals (status signals) must be supplied with the same potential.
Safety standards All externally connected devices shall comply with the relevant safety standards.
Cable installation in ac-
Signal and bus cables are susceptible to interference.
cordance with EMC
Motor cables are interference sources.
● Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
15
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Electrical connection AC 01.1 Non-Intrusive
● The interference immunity of signal and bus cables increases if the cables are
laid close to the earth potential.
● If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
● Avoid long parallel paths with cables being either susceptible to interference or
interference sources.
● For the connection of remote position transmitters, screened cables must be
used.
Type of current, mains Type of current, mains voltage and mains frequency must match the data on the
voltage and mains fre- motor name plate.
quency
Figure 9: Motor name plate (example)
● Power terminals (U1, V1, W1, U2, V2, W2): max. 6 mm² flexible/10 mm² solid
●
PE connection : max. 6 mm² flexible/10 mm² solid
● Control contacts (1 to 50): max. 2.5 mm²
16
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Electrical connection
[1] Cover
[2] Screws for cover
[3] O-ring
[4] Screws for socket carrier
[5] Socket carrier
[6] Cable entry
[7] Blanking plug
[8] Cable gland (not included in delivery)
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
4. Seal unused cable entries [6] with suitable blanking plugs [7].
5. Insert the cables into the cable glands [8].
5.2.2 Cable connection
17
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Electrical connection AC 01.1 Non-Intrusive
Information Some actuators are equipped with an additional motor heater. The motor heater
minimises condensation within the motor and improves the start-up behaviour for
extremely low temperatures.
18
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Electrical connection
[1] Cover
[2] Screws for cover
[3] O-ring
[4] Screws for socket carrier
[5] Socket carrier
[6] Cable entry
[7] Blanking plug
[8] Cable gland (not included in delivery)
1. Insert the socket carrier [5] into the cover [1] and fasten with screws [4].
2. Clean sealing faces of cover [1] and housing.
3. Check whether O-ring [3] is in good condition, replace if damaged.
4. Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5. Fit cover [1] and fasten screws [2] evenly crosswise.
6. Fasten cable glands [8] applying the specified torque to ensure the required
enclosure protection.
5.3 Accessories for electrical connection
— Option —
5.3.1 Controls mounted to wall bracket
The wall bracket allows separate mounting of controls and actuator.
Application ● If the actuator cannot be accessed.
● If the actuator is subject to high temperatures.
● In case of heavy vibration of the valve.
19
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Electrical connection AC 01.1 Non-Intrusive
20
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Electrical connection
For protection against touching the bare contacts and against environmental
influences.
Figure 15: Parking frame
21
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Operation AC 01.1 Non-Intrusive
6. Operation
Information Turning the handwheel during motor operation extends or reduces the operating time,
depending on the direction of rotation.
✔ Perform all commissioning settings and the test run prior to motor operation.
22
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Operation
➥ The actuator can now be operated using the push buttons [1 – 3].
- Run actuator in direction OPEN: Press push button OPEN [1].
- Stop actuator: Press push button STOP [2].
- Run actuator in direction CLOSE: Press push button CLOSE [3].
Information The OPEN - CLOSE operation commands can be given either in push-to-run opera-
tion mode or in self-retaining mode. In self-retaining mode, the actuator runs to the
defined end position after pressing the button, unless another command has been
received beforehand. For further information, please refer to the Manual (Operation
and setting).
➥ Now, it is possible to operate the actuator via remote control, via operation
commands (OPEN, STOP, CLOSE) or via analogue setpoints (e.g. 0 – 20 mA).
23
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Operation AC 01.1 Non-Intrusive
Information For actuators equipped with a positioner, it is possible to select between open-close
control (Remote OPEN-CLOSE) and setpoint control (remote SETPOINT). Selec-
tion is made via MODE input, e.g. based on a 24 V DC signal (refer to wiring diagram).
6.3 Menu navigation via push buttons (for settings and indications)
The push buttons of the local controls are used to view, edit, and show various
indications on the display.
Figure 21: Local controls
➥ Now, settings and indications can be performed via the push buttons [1 – 4].
24
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Operation
ENTER PASSWORD
0 * * *
Step by step:
25
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Operation AC 01.1 Non-Intrusive
Step by step:
1. Set selector switch to position 0 (OFF).
MAIN MENU M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
3. Press .
➥ Display indicates:
LANGUAGE/CONTRAS M00
VIEW
EDIT
4. Press .
➥ Display indicates:
LANGUAGE/CONTRAS M01
VIEW
EDIT
5. Press .
➥ Display indicates:
ENTER PASSWORD
0 * * *
26
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Operation
6. Enter password:
→ Press 4 x = 0000 (default factory password).
➥ Display indicates:
EDIT M010
LANGUAGE
LCD CONTRAST
7. Press .
➥ Display shows the set value:
EDIT M010
LANGUAGE
ENGLISH
:EDIT C:ESC
EDIT M010
LANGUAGE
ENGLISH
:EDIT :OK C:ESC
27
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Indications AC 01.1 Non-Intrusive
7. Indications
7.1 Status indications in the display
The status indications in the display locally indicate the current operation states as
well as faults and warnings.
This section describes the indications for the operation states. Faults and warnings
are described in the <Fault indications and warning indications> chapter.
7.1.1 Status indication S0/S6 - operation
Information For actuators equipped with process controllers, status indication S6 is displayed
instead of status indication S0 in selector switch position REMOTE. The description
below applies to both indications (S0 and S6).
Operation mode display Line 1 indicates the current operation mode (LOCAL MODE, OFF, REMOTE MODE,
…).
LOCAL MODE S0
OPEN
E2 100 %
RUNNING OPEN
Operation command/set-
Line 2 indicates currently incoming operation commands (OPEN, STOP, CLOSE)
point display or the setpoints E1 or E7 (for actuators equipped with positioner/process controller)
in % of the total travel.
LOCAL MODE S0
OPEN
E2 100 %
RUNNING OPEN
LOCAL MODE S0
OPEN
E2 100 %
RUNNING OPEN
28
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Indications
TORQUE S4
TORQUE 50 %
Information It is possible to change the unit displayed (%, Nm or Lbs/ft.). For further information,
please refer to the Manual (Operation and setting).
EDIT M1317
TORQUE INDICATION
NEWTONMETER
:EDIT ↵:OK C:ESC
29
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Indications AC 01.1 Non-Intrusive
Information The behaviour (blinking/illuminated) can be changed via the BLINKER (M1311)
parameter.
[1] Cover
[2] Indicator disc
[3] Mark
[4] Symbol for position OPEN
[5] Symbol for position CLOSED
30
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Signals
8. Signals
8.1 Feedback signals via output contacts (binary)
The output contacts can be used to indicate operation modes of the actuator or the
controls as binary signals. The signals can be freely assigned. Example:
Output contact open = no thermal fault
Output contact closed = thermal fault in actuator
The output contacts are denominated in the wiring diagram as follows:
● Output contacts 1 to 5: DOUT1 to DOUT5
● Alarm contacts: NC fault/NO ready
Signal assignment is made via the parameters: OUTPUT CONTACT 1 to OUTPUT
CONTACT 5 and ALARM CONTACT.
Alarm contact default value:
FAULT GROUP 3 = fault signal (includes: torque fault, thermal fault, phase failure
and internal faults)
Default values OUTPUT CONTACT 1 to OUTPUT CONTACT 5:
OUTPUT CONTACT 1 = CLOSED POSITION
OUTPUT CONTACT 2 = OPEN POSITION
OUTPUT CONTACT 3 = REMOTE SW. POSITION
OUTPUT CONTACT 4 = TORQUE FAULT (CLOSE)
OUTPUT CONTACT 5 = TORQUE FAULT (OPEN)
8.2 Feedback signals (analogue)
Valve position Signal: E2 = 0/4 – 20 mA (galvanically isolated)
Designation in the wiring diagram:
ANOUT1 (position)
Torque feedback Signal: E6 = 0/4 – 20 mA (galvanically isolated)
Designation in the wiring diagram:
ANOUT2 (torque)
For further information to this topic, please refer to the Manual (Operation and setting).
31
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive
32
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Commissioning (basic settings)
Information When leaving the factory (without valve), the screws [1] are not fastened, i.e. the
end stops must be set. If the actuator is mounted onto the valve with the screws [1]
fastened, the valve manufacturer has already performed the end stop setting. In this
case, the end stops must only be checked (use the handwheel to drive valve into
end positions).
9.2.1 End stop CLOSED: set
[1] Screws
[2] End stop nut
[3] Protective cap
1. If the four screws [1] are fastened: Unfasten the screws [1] with approx. 3 turns.
2. Move valve to end position CLOSED with handwheel. Check whether end stop
nut [2] rotates simultaneously.
→ Otherwise: Turn end stop nut [2] clockwise until end stop is reached.
3. In case end position CLOSED has been passed: Turn back the handwheel by
several turns and approach end position CLOSED again.
4. Turn end stop nut [2] counterclockwise by 1/8th turn.
Information: In this process, the protective cap [3] must not be unfastened.
➥ Thus, the end stop CLOSED within the part-turn actuator is set to a slightly
higher swing angle (approx. 1°) than the valve end position.
5. Fasten screws [1] crosswise at 25 Nm.
● Following end stop setting, the limit switching for end position CLOSED
can be set (refer to <Limit switching: set> chapter). For this, the switch
compartment must be opened and the indicator disc removed (refer to
<Switch compartment: open> chapter).
● In general, the end stop OPEN does not require setting due to fact that
the swing angle was already set in the factory.
33
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive
[1] Screws
[2] End stop nut
[3] Protective cap
1. If the four screws [1] are fastened: Unfasten the screws [1] with approx. 3 turns.
2. Move valve to end position OPEN with handwheel. Check whether end stop
nut [2] rotates simultaneously.
→ Otherwise: Turn end stop nut [2] counterclockwise until end stop.
3. In case end position OPEN has been passed: Turn back the handwheel by
several turns and approach end position OPEN again.
4. Turn end stop nut [2] clockwise by 1/8th turn.
Information: In this process, the protective cap [3] must not be unfastened.
➥ Thus, the end stop OPEN within the part-turn actuator is set to a slightly higher
swing angle (approx. 1°) than the valve end position.
5. Fasten screws [1] crosswise at 25 Nm.
● Subsequent to this setting, the limit switching for end position OPEN can
be set (refer to <Limit switching: set> chapter). For this, the switch com-
partment must be opened and the indicator disc removed (refer to <Switch
compartment: open> chapter).
● In general, the end stop CLOSED does not require setting due to the fact
that the swing angle was already set in the factory.
9.3 Swing angle
The swing angle must only be changed if the swivel range for end stop setting is not
sufficient.
The swing angle set in the factory is indicated on the name plate.
In the standard version the swing angle can be adjusted within the range of 80° to
110°. Optional swivel ranges: refer to technical data pertaining to the order.
34
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Commissioning (basic settings)
35
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive
Limit seating The limit switching is set in such a way that the actuator switches off at the desired
switching points. The torque switching acts as overload protection for the valve.
Torque seating The torque switching is set to the desired tripping torque. After reaching the tripping
torque the actuator is turned off.
The limit seating is used to signal that the limit switching will trip shortly before
reaching the set tripping torque. If this is not the case, one of the following fault
signals is displayed: TSO FAULTS or TSC FAULTS (menu S1).
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
SEATING MODE (M11)
VIEW (M110)
EDIT (M111)
OPEN POSITION (M11_0)
CLOSED POSITION (M11_1)
Step by step:
1. Set selector switch to position 0 (OFF).
MAIN MENU M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
3. Press .
➥ Display indicates:
MAIN MENU M1
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
4. Press .
➥ Display indicates:
SETTINGS M10
SET LIMIT SWITCHES
SEATING MODE
TORQUE
36
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Commissioning (basic settings)
5. Press .
➥ Display indicates:
SETTINGS M11
SET LIMIT SWITCHES
SEATING MODE
TORQUE
6. Press .
➥ Display indicates:
VIEW M1100
OPEN POSITION
CLOSED POSITION
VIEW M1101
OPEN POSITION
CLOSED POSITION
VIEW
OPEN POSITION
LIMIT
C:ESC
VIEW
CLOSED POSITION
LIMIT
C:ESC
Use and to also select here between OPEN POSITION and CLOSED
POSITION.
10. Return to the VIEW/EDIT menu:
→ Press C twice.
37
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive
12. Press .
➥ Display indicates:
ENTER PASSWORD
0 * * *
EDIT M1111
OPEN POSITION
CLOSED POSITION
EDIT M1110
OPEN POSITION
LIMIT
↵:EDIT C:ESC
EDIT M1111
CLOSED POSITION
LIMIT
:EDIT C:ESC
38
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Commissioning (basic settings)
EDIT M1110
OPEN POSITION
LIMIT
:EDIT :OK C:ESC
EDIT M1111
CLOSED POSITION
LIMIT
:EDIT :OK C:ESC
EDIT M1110
OPEN POSITION
LIMIT
:EDIT C:ESC
AENDERN M1111
CLOSED POSITION
LIMIT
:EDIT C:ESC
39
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive
Step by step:
1. Set selector switch to position 0 (OFF).
MAIN MENU M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
3. Press .
➥ Display indicates:
MAIN MENU M1
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
4. Press .
➥ Display indicates:
SETTINGS M10
SET LIMIT SWITCHES
SEATING MODE
TORQUE
5. Press twice.
➥ Display indicates:
SETTINGS M12
SET LIMIT SWITCHES
SEATING MODE
TORQUE
6. Press .
➥ Display indicates:
TORQUE M120
VIEW
EDIT
40
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Commissioning (basic settings)
7. View or edit?
→ Display torque setting: continue with 8.
→ Edit torque setting: continue with 11.
Display torque setting: 8. Press .
➥ Display indicates:
VIEW M1200
OPENING
CLOSING
BY-PASS DURATION
VIEW M1201
OPENING
CLOSING
BY-PASS DURATION
VIEW
OPENING
65%
C:ESC
VIEW
CLOSING
65%
C:ESC
TORQUE M121
VIEW
EDIT
12. Press .
➥ Display indicates:
ENTER PASSWORD
0 * * *
41
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive
EDIT M2111
OPENING
CLOSING
BY-PASS DURATION
EDIT M1210
OPENING
100%
:EDIT C:ESC
EDIT M1211
CLOSING
100%
:EDIT C:ESC
EDIT M1210
OPENING
100%
:EDIT :OK C:ESC
EDIT M1211
CLOSING
100%
:EDIT :OK C:ESC
42
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Commissioning (basic settings)
EDIT M1210
OPENING
100%
:EDIT C:ESC
EDIT M1211
CLOSING
100%
:EDIT C:ESC
Step by step:
1. Set selector switch to position 0 (OFF).
43
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive
MAIN MENU M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
3. Press .
➥ Display indicates:
MAIN MENU M1
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
4. Press .
➥ Display indicates:
SETTINGS M10
SET LIMIT SWITCHES
SEATING MODE
TORQUE
5. Press .
➥ Display indicates:
ENTER PASSWORD
0 * * *
6. Enter password:
→ Press 4 x = 0000 (default factory password).
➥ The current actuator position is displayed:
44
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Commissioning (basic settings)
:ACCEPT C:ESC
➥
SET LIMIT SWITC M100
CLOSED POSITION
0.0 %
:EDIT C:ESC
:ACCEPT C:ESC
➥
SET LIMIT SWITC M101
OPEN POSITION
100.0 %
:EDIT C:ESC
45
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive
Information The end positions can be approached (via push buttons and selector switch in posi-
tion LOCAL) even during motor operation. Position the selector switch to 0 (OFF)
for setting. Direct approaching of the mechanical end stops during motor operation
may cause valve damage. Consequently, during motor operation, the travel to the
mechanical end stop of valve/gearbox must be interrupted prior to reaching the
preset position (press push button STOP).
46
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Commissioning (basic settings)
The switch compartment must be opened to perform the following settings (options).
→ Loosen screws [2] and remove cover [1] from the switch compartment.
47
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Commissioning (basic settings) AC 01.1 Non-Intrusive
4. Hold lower indicator disc in position and turn upper disc with symbol (OPEN)
until it is in alignment with the mark on the cover.
48
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Commissioning (basic settings)
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
49
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Corrective action AC 01.1 Non-Intrusive
LOCAL MODE S0
OPEN
E2 100 %
FAULT IND.
50
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Corrective action
FAULT IND. S1
NO FAULT
WARNING IND. S2
NO WARNINGS
51
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Corrective action AC 01.1 Non-Intrusive
The causes for the NOT READY IND. fault signals (from status indication S0) are
displayed within status indication S3.
10.3 Fuses
Fuses F1 and F2 can be accessed after removing the cover [1] on the rear side.
Fuses F3, F4, and F5 are located on the power supply unit and can be accessed
after removing the electrical connection [2].
Hazardous voltage!
Risk of electric shock.
→ Disconnect device from the mains before opening.
52
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Corrective action
F3 Internal 24 V DC supply
F4 Internal 24 V AC supply (115 V AC) for:
● Heater, switch compartment, reversing contactors control
● PTC tripping device
● for 115 V AC also control inputs OPEN - STOP - CLOSE
53
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Corrective action AC 01.1 Non-Intrusive
Depending on the parameter setting, the fault signal is either automatically reset or
the fault signal has to be reset using the Reset push button in selector switch position
LOCAL.
For further information to this topic, please refer to the Manual (Operation and setting).
54
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Servicing and maintenance
AUMA
AUMA offer extensive service such as servicing and maintenance as well as customer
Service & Support product training. For the relevant contact addresses, please refer to <Addresses>
in this document or to the Internet (www.auma.com) .
55
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Technical data AC 01.1 Non-Intrusive
Power supply, mains frequency For mains voltage and mains frequency, refer to name plates at the controls and the motor
Permissible variation of the nominal voltage: ±10 %
Permissible variation of the mains frequency: ±5 %
Current consumption Motor current consumption: Refer to motor name plate
Current consumption of the controls depending on the mains voltage:
100 to 120 V AC = max. 650 mA
208 to 240 V AC = max. 325 mA
380 to 500 V AC = max. 190 mA
External supply of the electro- 24 V DC +20 %/–15 %
nics (option) Current consumption: Basic version approx. 200 mA, with options up to 500 mA
Rated power The controls are designed for the rated power of the motor, refer to motor name plate
Overvoltage category Category III according to IEC 60364-4–443
56
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Technical data
Switchgear1) Standard:
Reversing contactors (mechanically and electrically interlocked) for motor power up to power
class A1
Options:
● Thyristor unit for mains voltage up to 500 V AC (recommended for modulating actuators)
for AUMA power class B1
Control Standard:
Control inputs 24 V DC, OPEN - STOP - CLOSE - EMERGENCY (via opto-isolator, one
common), current consumption: Approx. 10 mA per input, observe minimum pulse duration
for modulating actuators
Option:
Control inputs 115 V AC, OPEN – STOP - CLOSE - EMERGENCY (via opto-isolator, one
common), current consumption: Approx. 15 mA per input
Output signals Standard:
6 output contacts with gold-plated contacts:
● 5 NO contacts with one common, max. 250 V AC, 1 A (resistive load)
- Default configuration: End position OPEN, end position CLOSED, selector switch in
REMOTE, torque fault CLOSE, torque fault OPEN
● 1 potential-free change-over contact, max. 250 V AC, 5 A (resistive load) for collective
fault signal
- Default configuration: Torque fault, phase failure, motor protection tripped
Option:
5 potential-free NO/NC contacts without one common, per contact max. 250 V AC, 5 A (re-
sistive load)
Voltage output Standard:
Auxiliary voltage 24 V DC, max. 100 mA for supply of the control inputs, galvanically isolated
from internal voltage supply
Option:
Auxiliary voltage 115 V AC, max. 30 mA to supply the control inputs2), galvanically isolated
from internal voltage supply
Local controls Standard:
● Selector switch LOCAL - OFF - REMOTE (lockable in all three positions)
● Push buttons OPEN - STOP - CLOSE - RESET
● 5 indication lights:
- End position CLOSED and running indication CLOSE (yellow), torque fault CLOSE
(red), motor protection tripped (red), torque fault OPEN (red), end position and running
indication OPEN (green)
● LC display, illuminated
● Programming interface (infra-red)
Options:
● Bluetooth programming interface is equipped with a class II Bluetooth chip with a range
of up to 10 m. The interface supports the Bluetooth protocol SPP (Serial Port Profile).
● Enabling the local controls via the digital input RELEASE. Thus, the actuator operation
can be enabled or disabled via push buttons on the local controls.
● Special colours for the 5 indication lights:
- End position CLOSED (green), torque fault CLOSE (blue), torque fault OPEN (yellow),
motor protection tripped (white), end position OPEN
● Protection cover, lockable
● Protection cover with indicator glass, lockable
57
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Technical data AC 01.1 Non-Intrusive
Functions Standard:
● Switch-off mode adjustable
- Limit or torque seating for end position OPEN and end position CLOSED
● Torque monitoring over the whole travel
● Torque by-pass, adjustable up to 5 seconds (no torque monitoring during this time)
● Phase failure monitoring3) with automatic phase correction
● Running indication via indication lights/LEDs
● EMERGENCY behaviour programmable
- Digital input low active, reaction can be selected: Stop, move to end position CLOSED,
move to end position OPEN, move to intermediate position
- Torque monitoring can be by-passed during EMERGENCY operation.
- Thermal protection can be by-passed during EMERGENCY operation (only in combi-
nation with thermoswitch in the actuator, not with PTC thermistor).
Options:
● Positioner4)
- Position setpoint via analogue input E1 = 0/4 – 20 mA
- Programmable behaviour on loss of signal
- Automatic adaptation of the dead band (adaptive behaviour can be selected)
- Split Range operation
- Change-over between open-close duty and modulating duty via digital MODE input
● Process controller, PID5)
- Process setpoint via analogue input E1 = 0/4 – 20 mA
- Actual process value via analogue input E4 = 0/4 – 20 mA
- Programmable behaviour on loss of signal
- Limitation of the control range
- Change-over between open-close duty and modulating duty via digital MODE input
Monitoring functions ● Programmable monitoring of the max. number of starts, generates warning signal
● Reaction monitoring for operation command (programmable from 1 to 15 seconds), ge-
nerates fault signal and results in switching off
● Operating time monitoring (programmable from 4 to 1,800 seconds), generates warning
signal
Electronic name plate ● Ordering data:
- AUMATIC commission number, actuator commission number, KKS number (definition
system for power plants), valve number, plant number
● Product data:
- Product name, actuator works number, AUMATIC works number, logic software ver-
sion, logic hardware version, date of final test, wiring diagram, terminal plan
● Project data:
- Project name, 2 freely definable customer fields with a max. of 19 characters each
● Service data:
- Service telephone, Internet address, service text 1, service text 2
Operating data logging A resettable counter and a lifetime counter each for:
Motor running time, number of starts, torque switch trippings in end position CLOSED, limit
switch trippings in end position CLOSED, torque switch trippings in end position OPEN, limit
switch trippings in end position OPEN, torque faults CLOSE, torque faults OPEN, motor
protection trippings
58
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Technical data
59
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Technical data AC 01.1 Non-Intrusive
12.4 Accessories
Wall bracket1) AUMATIC mounted separately from the actuator, including plug/socket connector. Connecting
cables on request. Recommended for high ambient temperatures, difficult access, or in case
of heavy vibration during service
EMERGENCY STOP button2) The control voltage of the reversing contactors is interrupted by operating the EMERGENCY
STOP button.
Programming software for PC COM-AC. An interface cable is required for the standard infra-red programming interface.
1) Cable distance between actuator and AUMATIC max. 100 m. Requires separate data cable for MWG. If actuator and AUMATIC are
separated at a later date, the max. cable length is 10 m.
2) Only in combination with reversing contactors and AUMATIC AC 01.1 in enclosure protection IP 67 or IP 68
60
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Spare parts
61
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Spare parts AC 01.1 Non-Intrusive
Information: Please state type and commission no. of the device (see name plate) when ordering spare parts.
Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts
AUMA from any liability. Delivered spare parts may slightly vary from the representation.
No. Designation Type
001.0 Housing
002.0 Worm shaft Sub-assembly
002.4 End stop nut (included in sub-assembly 002.0)
003.0 Manual drive worm Sub-assembly
004.0 Worm wheel Sub-assembly
005.0 Mounting flange Sub-assembly
010.0 End stop Sub-assembly
016.1 Protective cap
017.0 Torque finger Sub-assembly
021.0 Limit drive finger Sub-assembly
029.0 Manual drive bearing Sub-assembly
032.0 Planetary gearing Sub-assembly
034.0 Motor Sub-assembly
034.1 Motor brake Sub-assembly
034.2 Cover plate Sub-assembly
041.0 Socket carrier with motor cable harness Sub-assembly
061.0 Torque switching head Sub-assembly
500.0 Cover Sub-assembly
501.0 Socket carrier (complete with sockets) Sub-assembly
502.0 Pin carrier without pins Sub-assembly
503.0 Socket for controls Sub-assembly
504.0 Socket for motor Sub-assembly
505.0 Pin for controls Sub-assembly
506.0 Pin for motor Sub-assembly
507.0 Plug cover Sub-assembly
525.0 Coupling
542.0 Handwheel Sub-assembly
542.1 Ball handle Sub-assembly
553.0 Mechanical position indicator Sub-assembly
556.0 Potentiometer for position transmitter Sub-assembly
556.1 Potentiometer without slip clutch
557.0 Heater Sub-assembly
558.0 Blinker transmitter including pins at wires (without impulse disc and insulation plate) Sub-assembly
559.0-1 Control unit with torque switching heads and switches Sub-assembly
559.0-2 Control unit with magnetic limit and torque transmitter (MWG) for Non-intrusive version in combination Sub-assembly
with AUMATIC integral controls
560.0-1 Switch stack for direction OPEN Sub-assembly
560.0-2 Switch stack for direction CLOSE Sub-assembly
560.1 Switch for limit/torque switching
560.2 Switch case
566.0 Position transmitter RWG Sub-assembly
566.1 Potentiometer for RWG without slip clutch Sub-assembly
566.2 Electronic board RWG Sub-assembly
566.3 Wire harness for RWG Sub-assembly
567.1 Slip clutch for potentiometer Sub-assembly
S1 Seal kit, small Set
S2 Seal kit, large Set
62
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Spare parts
63
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Spare parts AC 01.1 Non-Intrusive
Information: Please state type and commission no. of the device (see name plate) when ordering spare parts.
Only original AUMA spare parts should be used. Failure to use original spare parts voids the warranty and exempts
AUMA from any liability. Delivered spare parts may slightly vary from the representation.
No. Designation Type
001.0 Housing Sub-assembly
002.0 Local controls Sub-assembly
002.3 Local controls board
006.0 Power supply Sub-assembly
008.1 Interface board
009.0 Logic board Sub-assembly
011.1 Relay board
500.0 Cover Sub-assembly
501.0 Socket carrier (complete with sockets) Sub-assembly
502.0 Pin carrier without pins Sub-assembly
503.0 Socket for controls Sub-assembly
504.0 Socket for motor Sub-assembly
505.0 Pin for controls Sub-assembly
506.0 Pin for motor Sub-assembly
507.0 Plug cover Sub-assembly
508.0 Switchgear Sub-assembly
509.1 Padlock
510.0 Fuse kit Set
S Seal kit Set
64
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Certificates
14. Certificates
14.1 Declaration of Incorporation and EC Declaration of Conformity
65
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive
66
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive
67
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
Index AC 01.1 Non-Intrusive
L
Index LEDs 29
Language in the display 26
A Limit switching 43 , 46
Accessories (electrical 19 Local control 22
connection) Local controls 22
Actuator operation from remo- 23 Low temperature version 32
te Lubrication 55
Ambient temperature 60
Applications 5 M
Assembly 11 Mains frequency 16
Mains voltage 16
C Maintenance 5 , 55 , 55
Cable set 19 Manual operation 22
Commission number 9 Mechanical position indicator 30 , 47
Commissioning 5 Menu navigation via push 24
Connecting cable 19 buttons
Control 9 Motor heater 18
Corrective action 50 Motor operation 22
Corrosion protection 10 , 59
Cross sections 16 N
Current consumption 15 Name plate 8 , 16
Non-Intrusive 9
D
Declaration of Incorporation 65 O
Direction of rotation 46 Operating time 48
Directives 5 Operation 5 , 22
Display (indications) 28 Operation command/setpoint 28
Disposal 55 display
Double sealed 21 Operation mode display 28
E P
EC Declaration of Conformity 65 Packaging 10
EMC 15 Parking frame 20
Electrical connection 15 Password entry 25
Enclosure protection 59 Position indicator 47
End position(s) reached dis- 28 Power supply 15 , 16
play Protection cover 21
End positions 36 Protection on site 15
End stops 32 Protective measures 5
Push buttons 24
F
Fault indications and warning 50 Q
indications Qualification of staff 5
Feedback signals (analogue) 31
R
H Range of application 5
Handwheel 11 Recycling 55
Heat-up time 32 Remote actuator operation 23
Running indication 30 , 30
I Running indication (in display) 28
Identification 8
Indication lights 29
Indications 28
Indicator disc 30 , 47
Inspection record 9
Intermediate frame 21
Intrusive 9
68
SG 05.1 – SG 12.1/SGR 05.1 – SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Index
S
S0/S6 - operation 28
S4 - torque 29
Safety instructions 5
Safety instructions/warnings 5
Service 55
Service conditions 59
Servicing 55
Short-circuit protection 15
Signals 31
Spare parts 61
Standards 5
Status indications (in the dis- 28
play)
Storage 10
Support 55
Swing angle 34
T
Technical data 56
Terminal plan 15
Test run 46
Torque indication 29 , 29
Torque switching 39
Transport 10
Tripping torque 36
Type and size 8
Type of current 16
Type of seating 36
V
Valve position display 28
W
Wall bracket 19
Wiring diagram 9 , 15
69
AUMA worldwide
70
AUMA worldwide
Asia Australia
AUMA Actuators (Tianjin) Co., Ltd. BARRON GJM Pty. Ltd.
CN 300457 Tianjin AU NSW 1570 Artarmon
Tel +86 22 6625 1310 Tel +61 294361088
Fax +86 22 6625 1320 Fax +61 294393413
mailbox@auma-china.com info@barron.com.au
www.auma-china.com www.barron.com.au
71
AUMA Riester GmbH & Co. KG
P.O.Box 1362
D 79373 Muellheim
Tel +49 7631 809 - 0
Fax +49 7631 809 - 1250
riester@auma.com
www.auma.com
Y004.748/003/en/4.12