Professional Documents
Culture Documents
5
SCRX ®
PSS E Model Library
6.57 SCRX
Bus Fed or Solid Fed Static Exciter
ECOMP
This model is located at system bus #_______ IBUS,
VOTHSG
Machine identifier #_______ ID,
VUEL
This model uses CONs starting with #_______ J, EFD
VOEL SCRX
and STATEs starting with #_______ K.
XADIFD
ETERM
J+6 CSWITCH1
J+7 rc / rfd2
1 Set C
SWITCH = 0 for bus fed.
Set CSWITCH = 1 for solid fed.
2 Set CON(J+7) = 0 for exciter with negative field current capability.
Set CON(J+7) > 0 for exciter without negative field current capability.
(Typical CON(J+7) = 10)
STATEs # Description
K First integrator
K+1 Second integrator
CSWITCH = 0 CSWITCH = 1
VREF
EMAX Et 1.0
+
Ebridge
– 1 + TAs K
EC X
(pu) 1 + TBs 1 + TEs Negative
EFD
Current Logic
LadIfd
+
EMIN