Two tanks are filled with same products. Draining materials from these two
tanks is depended on the requirement of storage tank. Implement logic for this
system in PLC using ladder diagram.
Problem Diagram
Problem Solution
Here two tanks are used for the system. For level measurement, two
sensors are used (level low sensors). As shown in figure we use here two
pumps for transferring the materials from tanks (Tank 1 & Tank 2) to
storage tanks.
Here we will use level transmitter for storage tank level measurement.
PUMP 1 & PUMP 2 will be controlled by level transmitter feedback.
Here we used two pumps for smooth operation. Both pumps will be
operated when level of the storage tanks is detected below its limit.
Note:-Here we are consider simple automation for this system. Level
transmitter is used in this system and it will measure the level of the
storage.
Storage tank is taken of 500cm height for simplicity and level transmitter
feedback is 4 to 20mA.
We will use PLC S7-300 for this application. We will use scaling for
programming purpose.
List of inputs/outputs
List of inputs
Pump 1 :- Q0.0
Pump 2 :- Q0.1
M memory
For this application we used S7-300 PLC and TIA portal software for
programming.
Network 1 :-
we used latching circuit for cycle ON (M0.0) output.it can be started by pressing
START PB (I0.0) and stop by pressing STOP PB (I0.1).
Network 2 :-
Here actual count or value coming from the transmitter is current (4 to 20mA) so
by using analog input channel in the PLC we can convert it into digital count.
This digit is in INT (MW10) format so we need to convert it into DINT (MD100)
for calculation or multiplication.
Network 3 :-
DINT value (MD100) is multiplied with max height (500cm) of the tank for
calculation purpose.
Network 4 :-