You are on page 1of 5

Parallel Tanks Level

Control using PLC Ladder


Diagram Tutorial
Parallel Tanks Level Control
This is PLC Program to control level of parallel tanks.

Problem Description
Two tanks are connected in parallel connection. We need to heat and cool the
incoming material into the tanks and simultaneously control the level of the
tanks. Implement the PLC program for this application.
Problem Diagram

Problem Solution

 Heating process is used to heat the material in the tank and cooling
process is used to cool the material. Here consider both material are same
as show in figure, inlet valve feeds material in both the tanks.
 Here we can use level switches for detecting the low levels and high
levels for both the tanks.
 Use two temperature sensors for measuring the temperature of both the
tanks.
 Outlet valves are used at the bottom of the tanks to drain the materials for
further process.
 We will write PLC program for this application.
List of inputs/outputs
Digital Inputs

 Cycle START :- I0.0


 Cycle STOP :- I0.1
 Low level tank 1(LL1) :- I0.3
 Low level tank 2(LL2) :- I0.4
 High level tank 1(LH1) :- I0.5
 High level tank 2(LH2) :- I0.6
Digital Outputs

 Inlet valve V2 for heating tank :- Q0.0


 Inlet valve V3 for cooling tank :- Q0.1
 Outlet valve V4 for heating tank :- Q0.2
 Outlet valve V5 for cooling tank :- Q0.3
M memory

 Cycle ON bit :- M0.0


 Register for temperature of heating tank :- MD10
 Register for temperature of cooling tank :- MD14
 Outlet valve V5 for cooling tank :- Q0.3
PLC Ladder diagram for level control of parallel tanks
Program Description

For this application we used S7-300 PLC and TIA portal software for
programming. We can implement this logic by using other PLC also.
Network 1 :-

This Network is for latching circuit. Whenever START button is pressed (I0.0),


Cycle ON (M0.0) bit will be ON. Cycle can be STOP by pressing STOP PB
(I0.1).
Network 2 :-

When heating tank level low (I0.3) is detected, inlet valve V2 (Q0.0) will be ON.
If level high of tank 1(I0.5) is not detected and START (I0.0) button is pressed,
inlet valve V2 (Q0.0) will be ON.
Network 3 :-

If level low of tank 2 (I0.4) is detected, inlet valve V3 (Q0.1) will be ON. If


START button is pressed and high level of tank 2 (I0.6) is not detected, inlet
valve V3 (Q0.1) will be ON.
Network 4 :-

If cycle is ON and actual temperature of heating tank (MD10) is greater or equal


than set temperature (70°C), outlet valve V4 (Q0.2) will be ON
Network 5 :-
If cycle is ON and actual temperature of cooling tank (MD14) is less or equal
than set temperature (20°C), outlet valve V5 (Q0.3) will be ON.

Note :- This example is only for explanation purpose only. We can implement
this logic in any PLC or using relay logic. Above application may be different
from actual application or may be a part of the plant logic.
Runtime Test Cases

You might also like