Simplified table
Calculations may be avoided by using Fig. G30 next page, which gives, with an
ampere, in terms of:
b Kinds of circuit use: motor circuits with cos φ close to 0.8, or lighting with a cos φ
close to 1.
b Type of circuit; single-phase or 3-phase
Voltage drop in a cable is then given by:
K x IB x L
K is given by the table,
IB is the full-load current in amps,
L is the length of cable in km.
The column motor power “cos φ = 0.35” of Fig. G30 may be used to compute the
voltage drop occurring during the start-up period of a motor (see example no. 1
[1] Values of r according to IEC60909-0 after the Fig. G30).
and Cenelec TR 50480. See Fig. G38.
Fig. G30 Phase-to-phase voltage drop ΔU for a circuit, in volts per ampere per km
G21
Examples
Example 1 (see Fig. G31)
A three-phase 35 mm2 copper cable 50 metres long supplies a 400 V motor taking:
DB422313_EN.eps
50 m / 70 mm² Cu
IB = 150 A
20 m / 2.5 mm² Cu
IB = 20 A