Filter Integrity Test Certificate Purpose: To Determine The Integrity of Installed Hepa Filters

The document reports the results of filter integrity tests conducted on HEPA filters installed in laminar airflow equipment and air handling units at a medical supplies manufacturing facility. Filters were tested using an aerosol photometer to measure upstream and downstream aerosol concentrations. All filters tested showed upstream concentrations between 20-80 μg/ltr and downstream concentrations less than 0.01%, indicating the filters passed the integrity test.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
831 views2 pages

Filter Integrity Test Certificate Purpose: To Determine The Integrity of Installed Hepa Filters

The document reports the results of filter integrity tests conducted on HEPA filters installed in laminar airflow equipment and air handling units at a medical supplies manufacturing facility. Filters were tested using an aerosol photometer to measure upstream and downstream aerosol concentrations. All filters tested showed upstream concentrations between 20-80 μg/ltr and downstream concentrations less than 0.01%, indicating the filters passed the integrity test.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

FILTER INTEGRITY TEST CERTIFICATE

PURPOSE: TO DETERMINE THE INTEGRITY OF INSTALLED HEPA FILTERS


Client M/[Link] Medical Stores (MFG) Reference No GMPLCS/SMS/FIT/21-22/B001
3,Sardar Ghat Lane,Bhadreshwar,Hooghly. Test Reference ISO 14644-3
West Bengal. Date of Test 13/09/2021
Area of Test Microbilogy Next Due Date 12/09/2022
Equipement ID No. SML/LAF/01 Equipement Name Laminar Air Flow
INSTRUMENT USED FOR TESTING
Instrument Name Aerosol Photometer Make TSI
Serial No 2975 Model PH-5
Calibrated on 03/06/2021 Calibration Due On 03/06/2022
Genarator Details
Instrument Name Aerosol Generator Make ATI
[Link] SEC/ASG-05 Model TDA-4B
OBTAINED TEST RESULTS
Upstream aerosol Upstream aerosol Downstream aerosol
Sr. Supply Filter Concentration
Room /Equipement Name Concentration in (µg/ltr) concentration in (%) Results
No. [Link] in (%) NLT 100%
20 to 80 (µg/ltr) (LT 0.01%)

laminar Air Flow


1 F1 32 100 0.0001 Passed
(SML/LAF/01)

REMARK : The HEPA filters installed in the above specified were Passed / Failed filter integrity test by
using PAO.
Conducted By Witnessed By Approved By

Balaji Bobade ENGINEERING QA


M/[Link] laboratories And Clean Room Solutions M/[Link] Medical Stores (MFG)
FILTER INTEGRITY TEST CERTIFICATE

PURPOSE: TO DETERMINE THE INTEGRITY OF INSTALLED HEPA FILTERS


Client M/[Link] Medical Stores (MFG) Reference No GMPLCS/SMS/FIT/21-22/B002
3,Sardar Ghat Lane,Bhadreshwar,Hooghly. Test Reference ISO 14644-3
West Bengal. Date of Test 13/09/2021
Area of Test Microbilogy Next Due Date 12/09/2022
AHU No. AHU-01 Area Second Floore
INSTRUMENT USED FOR TESTING
Instrument Name Aerosol Photometer Make TSI
Serial No 2975 Model PH-5
Calibrated on 03/06/2021 Calibration Due On 03/06/2022
Genarator Details
Instrument Name Aerosol Generator Make ATI
[Link] SEC/ASG-05 Model TDA-4B
OBTAINED TEST RESULTS
Upstream aerosol Upstream aerosol Downstream aerosol
Sr. Supply Filter Concentration
Room Name Concentration in (µg/ltr) concentration in (%) Results
No. [Link] in (%) NLT 100%
20 to 80 (µg/ltr) (LT 0.01%)

1 LAF ROOM F1 32 100 0.0001 Passed

2 AIR LOCK-1 F1 35 100 0.0040 Passed

3 INCUBATOR ROOM F1 30 100 0.0020 Passed

REMARK : The HEPA filters installed in the above specified were Passed / Failed filter integrity test by
using PAO.
Conducted By Witnessed By Approved By

Balaji Bobade ENGINEERING QA


M/[Link] laboratories And Clean Room Solutions M/[Link] Medical Stores (MFG)