Sheet1

Selected Supplied Air Fan 8000 CFM


Winter Temp -45 °C
Supply Temp 4 °C
Temp Rise 49 °C
Heat Coil 762048 Btu/h

Heat to Remove 149588 Btu/h


Max Outside Temp 30 C
Temp Rise Temp 10 C
Airflow Rate 7675 CFM
Safety 4%
Final Air flow Rate 8000 CFM

Heat to Remove 43868 W


Max Indoor Temp 40 C
Air flow Rate 3.637 m3/s
Specific Heat 1005 J/Kg.C
Air density 1.2 kg/m3

Heat generated by
Equipment

Compr HP 50 HP
Thermall efficiency 6%
Area Compressor outlet 6.6 ft2
Speed 466 fpm
Estimated Air flow 3076 CFM

Comp T in 30 °C
Comp T out 50 °C

Heat gains 119588 Btu/h

S/A in Winter 8000 CFM


S/A Min Temp 9 °C
Room Temp 15 °C
Winter O/A Temp -45 °C

R/A 7200 CFM


O/A 800 CFM

Heat gain from hydraulic 30000 Btu/h

Page 1
Sheet1

Fluid evap capture velocity 50 fpm


Tub Area 16 ft2

Exhaust from Watertub 800 CFM

Page 2
Sheet1

88.2 °F
223474.4868 W 223.4744868 kW

FPM Safety ft2 ft in m


450 10% 18.7611003 4.331408581 51.97690298 1.320213336

2.708333333 ft 2.4375 ft

35.0698563 kW

Page 3
Sheet1

4 ft 4 ft