Frequency: 50.0
System Data
Total Sf Cp Tf Tc Ts
Ambient Fault Division Projection for for Sizing for
Freq. Weight Temp. Current Factor Factor Total Fault Ground Available
Hz kg °C kA X/R % % Duration Conductors Body Current
50.0 50 40.00 1.000 10.00 50.0 100.0 1.00 1.00 0.50
Soil Data
Gravel 10000.0 0.200 Moist soil 1000.0 1.00 Moist soil 2000.0
Material Constants
Resistivity of Thermal
r Factor Fusing Ground Conductor Capacity
Conductivity @ 20 °C K0 @ Temperature @ 20°C Per Unit Volume
Conductor/Rod Type % 1/°C 0 °C °C micro ohm.cm J/(cm³.°C)
Conductor & Rod Copper, commercial hard-drawn 97.0 0.00381 242.0 1084.0 1.78 3.42
Rod Data
Grid Configuration
Cost
Conductor Rod
Total Total Length Cost Total Total Length Cost Total Cost
No. m $ No. m $ $
23 614 6140.80 20 60 2000.00 8140.80
Project: Banglore Metro -Cantonment ETAP Page: 3
Rg GPR
Touch Potential Step Potential
Ground Ground
Resistance Potential Rise Tolerable Calculated Tolerable Calculated
Maximum Grid Current: 0.508 kA Surface Layer Derating Factor (Cs): 0.835