ANALYSIS STUDY Nomor Doc-MIU-001

GROUND GRID SYSTEMS


Tanggal 18 Desember 2019
GI 150KV MOUTONG (NEW)
Rev 0

GROUND GRID INPUT DATA

A. SYSTEM DATA
Short-Circuit Current Fault Duration Current
Ts
Total Sf Cf Tf Tc
Ambient For
Freq. Weight Fault Division Projection For For Sizing
Temp. X/R Available
(Hz) (kg) Current Factor Factor Total Fault Ground
(0C) Body
(kA) (%) (%) Duration Conductor
Current
50.0 70 40 40 1 60 100 1.0 1.0 1.0

B. SOIL DATA
Surface Material Upper Layer Soil Lower Layer Soil
Depth Material Resistivity Depth Material
Material Resistivity Resistivity
(m) Type (Ohm.m) (m) Type
Wet Organic
Gravel 8534.4 0.1 Moist Soil 100 1 10
Soil

C. MATERIAL CONSTANTAS
Resistivity of
Thermal
αr Factor Fusing Ground
Conductor/ Conductivity K0 @ Capacity Per
Type @ 200C Temperature Conductor
Rod % 00C Unit Volume
1/0C 0
C @200C
J/(cm3.00C)
Micro ohm.cm
Cooper,
Conductor/ annealed
100.0 0.00393 234.0 1083.0 1.72 3.42
Rod soft-
drawn

D. ROD DATA
Diameter Length No. Of
Arrangement
cm m Roads
1.500 3.00 42 Rods Throughout Grid Area

E. GRID CONFIGURATION
Conductor Depth Grid Length m Number of Conductor Separation m
2
size mm m Lx Ly In X In X In x In Y
Direction Direction Direction Direction Direction Direction
150 0.80 93.80 39.50 9 21 4.7 4.9

Page 1 of 2
ANALYSIS STUDY Nomor Doc-MIU-001
GROUND GRID SYSTEMS
Tanggal 18 Desember 2019
GI 150KV MOUTONG (NEW)
Rev 0

Conductor Road
Total Total Length Total Total Length
No. m No. m
30 1674 42 126

F. GRID CONFIGURATION
Gg GPR Touch Potential Step Potential
Ground Ground Potential Calculated Calculated
Tolerable Tolerable
Resistance Rods
Volt Volts % Volts Volts %
ohm Volts
0.133 3195.7 2002.8 1879.7 93.9 7540.4 1469.5 19.5

Total Fault Current : 40.000 kA Reflection Factor (K) : -0.977


Maximum Grid Current : 24.038 kA Surface Layer Derating Factor (Cs) : 0.918
Decrement Factor (Df) : 1.002

Page 2 of 2