HVAC CALCULATIONS

Detailed Design Calculation Report


AMAAD BUSINESS PARK PARCEL-2

NOV.2019 1
SECTION 1: COOLING LOAD CALCULATION

1.1. Design Factors Input Data.


1.2. Cooling Load Calculation (Using Hourly Analysis Program 5.00).
1.3. Cooling Load Report.
1.4. Block Load.
1.5. Cooling Load Summary.
1.6. Heating load calculation.
1.1. Design Factors Input Data
1.1.1 U-Values

Based on the building external facade, the U-factors and glass shading coefficients is
determined according to the wall and glass specifications as set by the Architect:

 The external walls U-value = 0.32 W/m². °K.


 The roof U-value = 0.26 W/m². °K.
 The glass U-value = 1.5 W/m². °K & SC = 0.25.
 EXPOSED FLOORS of 0.30 W/m². °K.

1.1.2 External Design Conditions:


1.1.2.1 For the plant cooling load calculations (ASHRAE DATA (0.4%)):

The following outdoor conditions will be used in calculating the plant cooling load:
 Summer Design Dry Bulb Temp.: 45.2°C (113.4°F).
 Mean Coincident Wet Bulb Temp.: 23.4°C (74.1°F).
 Mean Daily Range: 13.4°C (24.1°F).

Fresh air dehumidification cooling load will be at following outdoor conditions:

 Summer Design Wet Bulb Temp.: 31.3°C (88.3°F).


 Mean Coincident Dry Bulb Temp.: 35.9°C (96.6°F).

1.1.2.2 For Heating load calculations (ARAMCO DATA (99%)):


 Winter Design Dry Bulb Temp.: 7°C (44.6°F).

1.1.3 Internal Design Conditions:


The internal design conditions with respect to temperature and humidity are based on
ASHRAE Comfort Standard, the client recommendation, and sub-consultant
recommendations.

NOV.2019 2
Summer
Maximum NC
Room
Level
Temp. (°C) RH (%)

Retail Areas 23 ± 1 50 ± 10 35
Stores & Service Corridors 24 ± 1 50 ± 10 40
Main Entrances 23 ± 1 50 ± 10 35
BOH 24 ± 2 50 ± 10 40
Prayer Rooms /Meeting Rooms/ Offices
23 ± 1 50 ± 10 30
/ Control Room
Main Telephone Room 21 ± 1 50 ± 10 Not Controlled

Telephone / Telecom Rooms 23 ± 2 50 ± 10 Not Controlled


IT / Server / UPS / IT Rack
20 ± 2 50 ± 5 Not Controlled
Rooms/Security Room

Toilets/Ablution Areas/ Staff Changing 24 ± 1 40 - 60 40

Electrical Plant Rooms 23 ± 2 50 ± 10 60


Mechanical Plant Rooms / Energy
25 ± 2 Not Controlled 60
Center
Wellness Center 22 ± 1 50 ± 10 30
Ball Room & Pre-function 23 ± 1 50 ± 10 30
Hotel Guestrooms 23 ± 1 50 ± 10 25
Serviced Apartments 23 ± 1 50 ± 10 25
Restaurants 23 ± 1 50 ± 10 35

1.1.4 Lighting and Miscellaneous Power Density:

Lighting and miscellaneous power load for different areas shall be considered as per
the electrical design requirements. The lighting values, however, shall be aligned with
ASHRAE Standard 90.1-2007 Recommendations.

NOV.2019 3
Lighting
Function Equipment load Task Lighting load w/m²
load w/m²
Retail Areas 30 w/m2 19 11
Guestroom/ Serviced
300 Watt 9 -
Apartment Bedroom
Restaurants/ Bar Lounge - 11 15
800 Watt (Kitchen
Apartment Living Room 16 -
included)
Prayer Rooms - 12 -
Main Entrance/ Reception/
- 9 -
Pre-function
Ball Room 9 Watt/m2 12 -
Wellness Center As Per Equipment 7 -
Kitchens As Per Equipment 9 -
Toilets/ Ablution - 7 -
Offices 125 W/PC 9 -
Meeting Rooms 500 Watt 10 -
Small Elec. & Tel rooms 500 W/Room 12 -
Main Electrical room 50 w/m2 12 -
Lift Machine rooms 1200 w/elevator 12 -
Main Telephone room 15000 watt 12 -

1.1.5 Population density:

In general, the population density shall be used as per ASHRAE standard


recommendations and operator guidelines. However, these densities are coordinated
with the space actual occupancy from Interior Design and are studied with respect to
the actual figures provided by the client, which may tolerate from ASHRAE figures.
Following are guidelines for occupancy rates of the main areas:

Area Occupancy
Retail Shops 15P / 100m²
Restaurants Restaurant Area/1.8 = Total number
of seats.
Lobby/Pre-function rooms 30P / 100m²
Multipurpose Hall 120P / 100m²
Offices Individual 10m2/person
Offices Sharing 5m2/person
Meeting Rooms 50P / 100m²
Prayer Rooms 140P / 100m²
Laundry Room 10P / 100m²

NOV.2019 4
1.1.6 Rate of Heat Gain from Occupants:

The heat gain from the occupants is considered as per ASHRAE standard
recommendations for each type of application. Following are guidelines for heat gain
rates of the main functions:

Function
sensible heat (w) latent heat (w)

Seated at rest (Guestrooms, Bedrooms) 67 35


Sedentary Work (Dining areas, Kitchen) 82 79
Office work (Retail areas, Management
72 60
offices)

1.2. Cooling Load Calculations:

Cooling load calculation are done by using HAP computer software latest version. The
software uses the procedure based on the transfer function coefficients as presented in
ASHRAE handbooks. The calculation shall be performed for 24 hours for the 12 months
of the year to determine the maximum cooling loads for the equipment selection.
Additional calculations shall be done during other intermediate and off season periods for
the purpose of humidity control investigation for the areas with high latent loads.

1.3. Cooling Load Report:

Refer to HAP report at appendix A.


1.4. Block Load:
 Plant 1:
systems which serviced by fresh air at 26 (°C):

Maximum Plant Load 1082.9 kW

System
Cooling
SYSTEM MULT.
Coil Load
[kW]
001- BS -LOST & FOUND 1 2.4
002-BS- H.K WORK STATION 1 3.9
003-BS- H.K OFFICE 1 1.6
004-BS- VALET LAUNDARY 1 21.8
005-BS- LIFT LOBBY-01 1 2.1
006-BS- CORRIDOR01UP 1 4.6
007-BS- UNIFORM 1 7.2
008-BS- CLEAN LINEN 1 4.7
009-BS- DIRTY LINEN 1 2.4
010-BS- ELEC 01 1 1
011-BS- IDF 01 1 7.8
012-BS- DEBOXING 1 5.1

NOV.2019 5
013-BS- GSM 1 49.7
014 -BS- Baverage STORE 1 0.7
015-BS- PUMP ROOM 1 6.3
016-BS- COST CONTROL 1 1.1
017-BS- PUR. 1 1.1
018-BS- RECV. 1 1.2
019-BS- SEC. 1 1.4
020-BS- FLOWER 1 0.8
021-BS- MEP 1 1
022 -BS-CARPENTER 1 3.2
023-BS- UPS 1 12.5
024 -BS- MAINTSTORE 1 2.4
025-BS- BMS 1 7.6
026-BS- CHEF. ENG. 1 1.7
027-BS- ASS. ENG. 1 3.4
028-BS- GENERAL WORKSHOP 1 4
029-BS- CORRIDOR02 1 3.6
030-BS- FURNITURE ST 1 3.9
031-BS- LIFT LOBBY-02 1 5.4
032-BS- RMU 1 9.2
033-BS- CORR.DN 1 1.9
034-BS- ELEC 02 1 3.6
035-BS- IDF 02 1 10.1
036-BS- WASTE ROOM 1 10.9
037-BS- M. ELEC ROOM 1 28.3
038-BS- M. TELECOM RM 1 20.8
039-BS- SECURITY 1 20.5
040-BS- SECURITY EQU. 1 36.1
041-BS- SERVER 1 72.3
042-BS- IT DIRECTOR 1 0.9
043-BS- IT TECHNICIANS 1 0.9
044-BS- PUMP ROOM 1 25.1
045-BS- STORE -05 1 4.6
045*-BS- STORE 1 4.6
046-BS- ETS ROOM 1 12.5
047-BS- PUMP ROOM 1 14.7
048-BS- IDF 05 1 9.4
049 -BS- LIFT LOBBY-03 1 10
050-BS- IDF 03 1 10.1
051-BS- ELEC 03 1 4.4
052-BS- IDF 04 1 10.6
053-BS- ELEC 04 1 4.4
054-BS- PUMP ROOM 1 16
055-BS- PUMP ROOM 1 13.9
056*-BS- PUMP ROOM 1 8
056-BS- PUMP ROOM 1 9.5
057-BS- CORRIDOR03 1 1.2
059-GR- FIRE COMAND 1 4.3

NOV.2019 6
060 - GR - STAFF ROOM 1 2.6
066- GR - KIT. WASTE 1 2.3
072 - GR - BACK OFFICE 1 2.5
073 - GR - STAFF ENTR 1 4.1
077 - GR- HK 1 2.8
078 - GR- SECURITY 1 1.1
081 - GR - STAFF. CORRIDOR 1 1.6
082 - GR - LIFT LOBBY 1 2.2
090- GR - hot KITCHEN 1 132.1
097- GR - KIT. ROOM SER 1 11.5
098 - GR - KIT. CHEF OFFICE 1 0.5
099 - GR - KIT. COLD KITCHEN 1 5.8
100 - GR - KIT. PREPARATION 1 17.6
803- GR - REGEN KITCHEN 1 25.7
804- GR - KIT WASH 1 7.7
805- GR - BEV. STORE 1 0.7
806- GR - BEV. DISPENSER 1 5.5
807- GR - CLEAN ST 01 1 1.7
808- GR - DAILY ST 1 0.5
809- GR - CLEAN ST 02 1 0.5
810- GR - STEW ST 1 0.9
811- GR -KIT VEG 1 3.3
812- GR - KIT D ST 1 1.3
813- GR - KIT PANTRY 1 6.3
101-1ST- HK 1 2.8
102-1ST- PANTRY 1 12.5
103-1ST- BUSINESS LOUNG 1 16
104-1ST- CORRIDOR 1 1.4
110 -1ST- STAFF 1 34.9
111 -1ST- M.PRAYER 1 5.4
113 -1ST- F.PRAYER 1 3.5
130 -1ST- SERVICE LOBBY 1 2.3
290-1ST- BAKERY 1 25
291-1ST- WASH 1 6.2
292-1ST- PANTRY 1 3.9
145 -2ND - DINING 1 100.3
146*-2ND- wash area 1 8.6
146-2ND- kitchen 1 62.1

NOV.2019 7
 Plant 2:

1. Plant Information:

Plant Name ............................................................................. PUBLIC AREA

Plant Type .................................................................. Generic Chilled Water

Design Weather ......................................................... Dhahran, Saudi Arabia

2. Cooling Plant Sizing Data:

Maximum Plant Load .............................................................................. 744.4 kW

Load occurs at .................................................................................. Jul 1600

m²/kW ......................................................................................................... 9.0 m²/kW

Floor area served by plant .................................................................... 6680.9 m²

3. Coincident Cooling Loads for Jul 1600

System

Cooling

Coil Load

Air System Name Mult. [kW]

058- GR - PREFUNCTION 1 39.5

061 - GR - STORE 1 0.8

062 - GR - BRIDE 1 2.6

063- GR - BALL ROOM 1 138.2

064- GR - RECEPTION &MEET 1 53.2

065- GR - HOTEL LOBBY 1 70.9

067-GR- IDF 1 7.7

068-GR- ELEC 1 0.9

069-GR- AV CONTROL RM 1 1.6

070- GR- AV EQUIP. 1 6.6

071 - GR - AIRLOCK 1 3.8

074 - GR - LUGGAGE 1 1.9

075 - GR- ELEC 1 1.5

076 - GR- IDF 1 8.0

079 - GR - LUGGAGE 1 1.3

083- GR - APPAR. LOBBY 1 35.0

085- GR - CLOAK 1 0.5

086- GR- IDF 1 8.0

087- GR- ELEC 1 1.1

088- GR- ELEC 1 1.0

089- GR - AHU RM 1 1.9

NOV.2019 8
System

Cooling

Coil Load

Air System Name Mult. [kW]

091- GR- F. TOILET 1 3.6

092- GR- M. TOILET 1 2.9

093- GR- M. TOILET 1 1.1

094- GR- F. TOILET 1 1.7

095- GR- F. TOILET 1 0.9

096- GR- M. TOILET 1 1.2

105 -1ST- MEETING 1 97.8

106-1ST- F.PRAYER 1 5.7

107 -1ST- F.ABULATION 1 0.4

108-1ST- M.PRAYER 1 7.5

109 -1ST- M.ABULATION 1 0.8

112 -1ST- M.ABULATION 1 0.5

114 -1ST- F.ABULATION 1 0.5

115 -1ST- ELEC 1 1.1

116 -1ST- IDF 1 7.9

117 -1ST- AHU 1 1.9

118 -1ST- M.LOCKER 1 2.0

119 -1ST- F.LOCKER 1 1.7

121-1ST- F.TOILET 1 0.9

122 -1ST- AHU 1 4.7

123-1ST- M.TOILET 1 1.0

124 - 1ST - M. TOILET 1 0.7

125 - 1ST - F. TOILET 1 0.5

126 -1ST- IDF 1 8.6

127 -1ST- ELEC 1 0.9

128 -1ST- ELEC 1 1.5

129 -1ST- IDF 1 8.0

131 -1ST- OFFICES 1 18.8

132 -1ST- SERVER 1 8.3

133 -1ST- AHUROOM 1 12.7

134 -1ST- ELEC 1 1.1

135 -1ST- IDF 1 7.9

136 -1ST- PUMP ROOM 1 6.2

NOV.2019 9
System

Cooling

Coil Load

Air System Name Mult. [kW]

137 -1ST- IDF 1 8.8

138 -1ST- ELEC 1 1.0

139 -1ST- PUMP RM CORR 1 0.6

140 -1ST- STORE 1 1.1

141 - 1ST - M. TOILET 1 1.0

142 - 1ST - F. TOILET 1 0.9

143 -2ND - SERVICE CORR 1 5.3

144 -2ND- AHU 1 7.5

147 - 2ND - M. TOILET 1 0.8

148 - 2ND - F. TOILET 1 1.1

149 - 2ND - M. Showers 1 2.5

150- 2ND - F. Showers 1 2.5

151- 2ND - M.Wellness center 1 16.0

152- 2ND - F.Wellness center 1 15.9

153 - 2ND - F. TOILET 1 2.2

154 - 2ND - M. TOILET 1 2.2

155 - 2ND - Kids area 1 5.6

156 -2ND- STORE 1 1.7

157 - 2ND - ELEC 1 1.4

158 - 2ND - IDF 1 8.2

159 - 2ND - HK 1 2.6

160 -2ND - SERVICE LOBBY 1 2.1

161 -2ND - SERVICE CORR 1 1.6

162 -2ND - SERVICE CORR 1 0.5

285-GR- IDF 1 8.6

286-STAIR 03 3 1.9

287-STAIR 02 3 1.9

288-STAIR 01 3 1.9

289-BSM-GAURD HOUSE 1 1.2

289-GAURD HOUSE 1 1.1

290A-BSM-GAURD HOUSE 1 1.3

291A-GF-GAURD HOUSE 1 1.2

292A-GF-GAURD HOUSE 1 1.2

NOV.2019 10
System

Cooling

Coil Load

Air System Name Mult. [kW]

293 - 2nd - M. TOILET 1 1.0

293A-GF-GAURD HOUSE 1 1.2

294 - 2ND - F. TOILET 1 0.9

294A-GF-GAURD HOUSE 1 1.3

295 - 2ND - IDF 1 8.6

 Plant 03:

1. Plant Information:

Plant Name ............................................................. HOTEL & APPARTMENT

Plant Type .................................................................. Generic Chilled Water

Design Weather ......................................................... Dhahran, Saudi Arabia

2. Cooling Plant Sizing Data:

Maximum Plant Load ............................................................................ 1754.6 kW

Load occurs at .................................................................................. Jul 1600

m²/kW ......................................................................................................... 9.2 m²/kW

Floor area served by plant .................................................................. 16205.5 m²

3. Coincident Cooling Loads for Jul 1600

System

Cooling

Coil Load

Air System Name Mult. [kW]

*163-GFL-GST-01-LIV./DIN. 1 6.4

*164-GFL-GST-01-BD 1 2.3

*165-GFL-GST-01-MBD 1 3.8

*166-GFL-GST-02-BD 1 2.9

*167-GFL-GST-02-LIV./DIN. 1 3.9

*168-GFL-ST-01 1 5.0

*169-GFL-MAIN CORR. 1 2.4

*170-F01-GST-02-MBD 1 2.6

*171-F01-GST-02-BD 1 1.6

*172-F01-GST-02-LIV/DIN 1 4.1

*173-F01-GST-01-MBD 1 2.9

NOV.2019 11
System

Cooling

Coil Load

Air System Name Mult. [kW]

*174-F01-GST-01-BD 1 1.8

*175-F01-GST-01-LIV/DIN 1 4.3

*176-F01-ST-01 1 3.4

*177-F01-GST-03-LIV/DIN 1 6.5

*178-F01-GST-03-BD 1 1.9

*179-F01-GST-03-MBD 1 2.7

*180-F01-GST-06-BD 1 2.0

*181-F01-GST-06-LIV/DIN 1 3.6

*182-F01-GST-08-LIV/DIN 1 3.6

*183-F01-GST-8-BD 1 2.0

*184-F01-GST-10-BD 1 2.0

*185A-F01-MAIN CORR. 1 6.2

*185-F01-GST-10-LIV/DIN 1 3.8

*186-F02-GST-02-MBD 1 2.6

*187-F02-GST-02-BD 1 1.6

*188-F02-GST-02-LIV/DIN 1 4.2

*189-F02-ST-02 1 3.0

*190-F02-GST-01-MBD 1 2.8

*191-F02-GST-01-BD 1 1.9

*192-F02-GST-01-LIV/DIN 1 4.4

*193-F02-ST-01 1 3.2

*194-F02-GST-03-LIV/DIN 1 5.8

*195-F02-GST-03-BD 1 1.9

*196-F02-GST-03-MBD 1 2.6

*197-F02-MAIN CORR. 1 4.3

*303-F03-STORE&LIFT'S 1 5.6

*301-F03-TYP-GUEST RM 7 2.6

*305-F03-TYP-IDF 7 8.4

*308-F03-TYP-LIFT LOBBY 7 3.9

*312-F03-TYP-GUEST RM 7 1.8

*314-F03-TYP-GUEST RM 7 1.8

*316-F03-TYP-GUEST RM 7 1.8

*318-F03-TYP-GUEST RM 7 1.8

NOV.2019 12
System

Cooling

Coil Load

Air System Name Mult. [kW]

*320-F03-TYP-GUEST RM 7 2.3

*327-F03-TYP-GUEST RM 7 2.3

*328-F03-TYP-SUITE-BD RM 7 2.7

*329-F03-TYP-ELEC RM 7 0.9

*330-F03-TYP-IDF 7 8.1

*331-F03-TYP-HK 7 1.2

*332-F03-TYP-SERV CORR 7 1.2

*333-F03-TYP-SERV LOBBY 7 2.0

*334-F03-TYP-CORRIDOR 7 8.7

*335-F03-TYP-SUITE-BD RM 7 4.0

*336-F03-TYP-GUEST RM 7 1.8

*339-F03-TYP-GUEST RM 7 2.6

*340-F03-TYP-GUEST RM 7 1.8

*343-F03-TYP-SUITE-LIV RM 7 2.7

*302-F03(03-08)-GUEST RM 6 1.9

*304-F03(03-08)-GUEST RM 6 1.9

*306-F03(03-08)-GUEST RM 6 1.9

*307-F03(03-08)- GUEST RM 6 1.9

*309-F03(03-08)-GUEST RM 6 1.9

*310-F03(03-08)GUEST RM 6 1.9

*311-F03(03-08)-GUEST RM 6 1.9

*313-F03(03-08)-GUEST RM 6 1.9

*315-F03(03-08)-GUEST RM 6 1.9

*317-F03(03-08)-GUEST RM 6 1.9

*319-F03(03-08)-GUEST RM 6 1.9

*321-F03(03-08)-GUEST RM 6 1.9

*322-F03(03-08)-GUEST RM 6 1.9

*323-F03(03-08)-GUEST RM 6 1.9

*324-F03(03-08)-GUEST RM 6 1.9

*325-F03(03-08)-GUEST RM 6 1.9

*337-F03-(03-08)-SUITE-BD RM 6 4.2

*338-F03(03-08)-GUEST RM 6 1.9

*341-F03(03-08)SUITE-LIV RM 6 3.0

NOV.2019 13
System

Cooling

Coil Load

Air System Name Mult. [kW]

*342-F03(03-08)-SUITE-LIV RM 6 2.9

*357-F03-(03-08)-ST-02 6 2.8

*358-F03-(03-08)-ST-01 6 3.0

*359-F03-(03-08)-GST-03-LIV/DIN 6 5.9

*360-F03-(03-08)-GST-03-BD 6 1.8

*361-F03-(03-08)-GST-03-MBD 6 2.3

*362-F03-(03-08)-ST-03 6 2.8

*363-F03-(03-08)-ST-04 6 4.3

*364-F03-(03-08)-GST-04-LIV/DIN 6 3.5

*365-F03-(03-08)-GST-06-LIV/DIN 6 3.6

*366-F03-(03-08)-GST-05-BD 6 1.7

*367-F03-(03-08)-GST-04-BD 6 1.9

*368-F03-(03-08)-GST-06-BD 6 1.9

*369-F03-(03-08)-GST-08-BD 6 1.7

*370-F03-(03-08)-GST-06-LIV/DIN 6 3.5

*371-F03-(03-08)-GST-07-LIV/DIN 6 3.3

*372-F03-(03-08)-GST-08-LIV/DIN 6 3.5

*373-F03-(03-08)-GST-8-BD 6 1.9

*374-F03-(03-08)-GST-09-LIV/DIN 6 3.3

*375-F03-(03-08)-GST-09-BD 6 1.7

*376-F03-(03-08)-GST-11-BD 6 1.7

*377-F03-(03-08)-GST-10-BD 6 1.9

*378-F03-(03-08)-GST-10-LIV/DIN 6 3.7

*379-F03-(03-08)-GST-11-LIV/DIN 6 3.6

*380-F03-(03-08)-MAIN CORRIDOR 6 9.0

*408-F04-(04-09)FAMILY ROOM 6 3.5

*351-F03(03-06)-GST-01-LIV/DIN 4 4.5

*352-F03-(03-06)GST-01-BD 4 1.8

*353-F03-(03-06)GST-01-MBD 4 2.5

*354-F03-(03-06)GST-02-MBD 4 2.4

*355-F03-(03-06)GST-02-BD 4 1.5

*356-F03-(03-06)GST-02-LIV/DIN 4 4.3

*601-F06-GST-02-MBD 1 2.8

NOV.2019 14
System

Cooling

Coil Load

Air System Name Mult. [kW]

*602-F06-GST-01-MBD 1 3.3

*701-F07-GST-01-MB 1 2.6

*702-F07-GST-01-BD 1 2.8

*801-F08-ST-01 1 3.3

*802-F08-ST-02 1 3.4

*902-F09-GUEST RM 1 2.2

*904-F09-GUEST RM 1 2.2

*906-F09-GUEST RM 1 2.2

*907-F09-GUEST RM 1 2.2

*909-F09-GUEST RM 1 2.2

*910-F09-GUEST RM 1 2.2

*911-F09-GUEST RM 1 2.2

*913-F09-GUEST RM 1 2.2

*915-F09-GUEST RM 1 2.2

*917-F09-GUEST RM 1 2.2

*919-F09-GUEST RM 1 2.2

*921-F09-GUEST RM 1 2.2

*922-F09-GUEST RM 1 2.2

*923-F09-GUEST RM 1 2.2

*924-F09-GUEST RM 1 2.2

*925-F09-GUEST RM 1 2.2

*937-F09-SUITE-BD RM 1 5.0

*938-F09-GUEST RM 1 2.2

*941-F09-SUITE-LIV RM 1 3.3

*942-F09-SUITE-LIV RM 1 3.3

*957-F09-ST-01 1 3.5

*958-F09-ST-02 1 4.1

*959-F09-GST-03-LIV/DIN 1 6.0

*960-F09-GST-03-BD 1 2.0

*961-F09-GST-03-MBD 1 2.5

*962-F0-ST-03 1 3.0

*963-F09-ST-04 1 4.6

*964-F09-GST-04-LIV/DIN 1 3.9

NOV.2019 15
System

Cooling

Coil Load

Air System Name Mult. [kW]

*965-F09-GST-06-LIV/DIN 1 3.9

*966-F09-GST-05-BD 1 1.9

*967-F09-GST-04-BD 1 2.0

*968-F0-GST-06-BD 1 2.1

*969-F09-GST-08-BD 1 1.9

*970-F09-GST-06-LIV/DIN 1 3.8

*971-F09-GST-07-LIV/DIN 1 3.6

*972-F09-GST-08-LIV/DIN 1 3.8

*973-F09-GST-8-BD 1 2.1

*974-F09-GST-09-LIV/DIN 1 3.7

*975-F09-GST-09-BD 1 1.9

*976-F08-GST-11-BD 1 1.9

*977-F09-GST-10-BD 1 2.1

*978-F09-GST-10-LIV/DIN 1 4.0

*979-F09-GST-11-LIV/DIN 1 4.0

*980-F09-MAIN CORRIDOR 1 10.1

RF-01-DINING 1 73.8

RF-02- ELEC 1 1.8

RF-03- IDF 1 8.4

RF-04- HK 1 1.2

RF-05-AHUROOM 1 10.6

RF-06- CORRIDOR 1 2.2

RF-07- CORRIDOR 1 1.2

RF-08 - M. TOILET 1 1.4

RF-09- M. TOILET 1 1.6

RF-10- SATTALITE KIT 1 26.7

RF-11- SERVICE LOBBY 1 2.5

RF-12- SERVICE LOBBY 1 7.8

RF-13 STORE 1 5.4

RF-14- IDF 1 8.8

RF-15- ELEC 1 1.6

RF-16-AHUROOM 1 13.7

RF-17- GSM 1 39.1

NOV.2019 16
System

Cooling

Coil Load

Air System Name Mult. [kW]

RF-18- PUMP ROOM 1 1.0

RF-19-STORE 1 3.3

RF-20- LIFT'S LOBBY 1 3.1

RF-21-STORE 1 2.0

RF-22-AHUROOM 1 4.0

RF-23- ELEC 1 1.4

RF-24- DISH WASH 1 7.7

RF-25-POT WASH 1 1.3

RF-26- SERV. CORRIDOR 1 5.0

RF-27- BOH. CORRIDOR 1 1.6

RF-28- CORRIDOR / LOBBY 1 2.8

RF-29- SHISHA PREP. 1 1.9

1.5. Cooling Load Summary:


Plumbing Chillers & Total TR with
Fresh air Plant Load Refrigerators Total Block Total diversity 90%
cooling load
load (KW) (KW) Load (KW) TR
(kw ) (cooling load kw )
2395.76 3579.1 175 85.1 6234.26 1772.68 1598

1.6. Heating load calculation:


Heater section will be added to fresh air handlers to raise the supply temperatures to an
acceptable level of around 18 °C during the cold seasons.

 Refer to Detailed Fresh Air heating load at appendix D.

SECTION 2: FRESH AIR AND EXHAUST AIR CALCULATIONS


2.1 Ventilation (Fresh air):

Ventilation requirements will be furnished in adequate quantities, filtered and tempered as


required, to maintain functional and comfortable space conditions. In general, the
ventilation rate is considered as per ASHRAE standard 62.1 2007 recommendations and
the client's design criteria for each type of application.

 Refer to Detailed Fresh Air calculations at appendix B.

NOV.2019 17
 For the fresh air handling units sizing, refer to appendix D.

Outdoor Air
Function Extract requirements Notes
requirements
Retail Areas 7.8 l/s/P Equal to FA -

Restaurant 7 l/s/P - Extract from


adjacent toilets and
kitchens
Public Toilets - 35 L/s / cubicle Makeup from
adjacent corridors
Prayer Rooms 2.8 l/s/P Same as FA quantity Extract from
ablution and shoe
rack areas
BOH Corridors 0.3 l/s/m2 - Extract from
adjacent toilets
Offices 8 l/s/P Same as FA quantity Extract from
adjacent toilets
Meeting 7 l/s/P Same as FA quantity Extract from
Rooms adjacent toilets
Ball Room 2.8 l/s/P 5% Lower than FA Extract adjacent
toilets
Hotel 30 L/s 25L/s Extract from
Guestrooms Guestroom toilet
Serviced Slightly positive 25 L/s from Bedroom
Apartments Toilets
15 L/s from Guest Toilet
10L/s from Laundry room
25 L/s From Kitchens
Laundry Room Minimum of 8.5 As per Kitchen consultant Make up air from
l/s/P design requirements adjacent corridors
Garbage Room - 5 ACH Make up air from
adjacent corridors

2.2 Infiltration
Despite that the whole building is kept under positive pressure, infiltration may still exist
from external facade walls, windows and skylights. To overcome the load added by this
infiltration, an infiltration rate of 0.3 l/s per square meter of external element will be
considered in the calculations.

NOV.2019 18
SECTION 3: SMOKE & PRESSURIZATION CALCULATIONS
3.1. Staircase & lift well pressurization:
Refer to Staircase pressurization calculations at appendix E.

NOV.2019 19
3.1 Smoke Extraction
 HOTEL

CORRIDOR
VENTILATION
Average
m
Height = 3.2
Extract / Smoke
Calculations

Total Area = 202 m2

4 ACH Normal case = 1,520 CFM


Fan (EXF-01) Capacity = 1,520 CFM
Fan (EXF-01) Capacity = 720 L/s

BED RM. FOR


SUITE
Average
m
Height = 3.2
Extract / Smoke
Calculations

Total Area = 19 m2

4 ACH Normal case = 144 CFM


Fan (EXF-01) Capacity = 144 CFM
Fan (EXF-01) Capacity = 70 L/s

NOV.2019 20
LIV./DIN. FOR
SUITE
Average
m
Height = 3.2
Extract / Smoke
Calculations

Total Area = 28 m2

4 ACH Normal case = 210 CFM


Fan (EXF-01) Capacity = 210 CFM
Fan (EXF-01) Capacity = 100 L/s

GUEST RM.

Average
m
Height = 3.2
Extract / Smoke
Calculations

Total Area = 23 m2

4 ACH Normal case = 169 CFM


Fan (EXF-01) Capacity = 169 CFM
Fan (EXF-01) Capacity = 80 L/s

FAMILY RM.
Average
m
Height = 3.2
Extract / Smoke
Calculations

Total Area = 26 m2

4 ACH Normal case = 193 CFM


Fan (EXF-01) Capacity = 193 CFM
Fan (EXF-01) Capacity = 95 L/s

NOV.2019 21
LIFT'S LOBBY
Average
m
Height = 3.2
Extract / Smoke
Calculations

Total Area = 23 m2

4 ACH Normal case = 175 CFM


Fan (EXF-01) Capacity = 175 CFM
Fan (EXF-01) Capacity = 85 L/s

H.K.
Extract / Smoke
Calculations
Average
m
Height = 3.2

Total Area =
4 ACH Normal case =
Fan (EXF-01) Capacity = 31 m2

Fan (EXF-01) Capacity = 237 CFM


237 CFM
115 L/s

SERV. LOBBY
Average
m
Height = 3.2
Extract / Smoke
Calculations

Total Area = 17 m2
4 ACH Normal case = 128 CFM
Fan (EXF-01) Capacity = 128 CFM
Fan (EXF-01) Capacity = 65 L/s

TOTAL SMOKE EXTRACT FROM HOTEL

TOTAL SMOKE EXTRACT = 3,670 L/s

NOV.2019 22
 APPARTMENT

CORRIDOR VENTILATION

Average Height = 3.2 m


Extract / Smoke Calculations

Total Area = 131 m2

4 ACH Normal case = 986 CFM


Fan (EXF-01) Capacity = 986 CFM
Fan (EXF-01) Capacity = 470 L/s

2 BD RM.(1) APARTMENT

Average Height = 3.2 m


Extract / Smoke Calculations

Total Area = 88 m2

4 ACH Normal case = 660 CFM


Fan (EXF-01) Capacity = 660 CFM
Fan (EXF-01) Capacity = 315 L/s

2 BD RM.(2) APARTMENT

Average Height = 3.2 m


Extract / Smoke Calculations

Total Area = 79 m2

4 ACH Normal case = 592 CFM


Fan (EXF-01) Capacity = 592 CFM
Fan (EXF-01) Capacity = 280 L/s

NOV.2019 23
STUDIO(1)

Average Height = 3.2 m


Extract / Smoke Calculations

Total Area = 35 m2

4 ACH Normal case = 265 CFM


Fan (EXF-01) Capacity = 265 CFM
Fan (EXF-01) Capacity = 125 L/s

STUDIO(2)

Average Height = 3.2 m


Extract / Smoke Calculations

Total Area = 39 m2

4 ACH Normal case = 297 CFM


Fan (EXF-01) Capacity = 297 CFM
Fan (EXF-01) Capacity = 145 L/s

NOV.2019 24
1 BD. RM. APARTMENT

Average Height = 3.2 m


Extract / Smoke Calculations

Total Area = 48 m2

4 ACH Normal case = 365 CFM


Fan (EXF-01) Capacity = 365 CFM
Fan (EXF-01) Capacity = 175 L/s

TOTAL SMOKE EXTRACT FROM


APPARTMENT

TOTAL SMOKE EXTRACT = 3,300 L/s

NOV.2019 25
SECTION 4: CAR PARK VENTILATION CALCULATIONS
4.1. Car Park Ventilation Calculations

Basements and parking areas shall be equipped with fire rated exhaust fans to ventilate the
non-air-conditioned spaces and to evacuate the smoke and clear up the way in case of fire.

FLOOR : BASEMENT

AVERAGE PARKING HEIGHT 4.8


TOTAL AREA 15610 m2
AC AREA 235 m2
NET AREA 15375 m2

NORMAL EXHAUST @ 6 ACH


TOTAL EXHAUST FLOW 260,471 CFM
122,933 L/SEC

SMOKE EXTRACTION @ 10 ACH


TOTAL EXHAUST FLOW 434,118 CFM
204,888 L/SEC

FRESH AIR @ 80% OF


CFM
EXHAUST AIR 208,376
98,346 L/SEC

NOV.2019 26
SECTION 5: CHILLED WATER PUMPS HEAD CALCULATIONS

Estimated Chilled water pump head

Total Head (pa) 187982

Total Head * 1.2 (safety factor) (pa) 225578

 Refer to Detailed Chilled water pump head calculations at appendix C.


 HEAD & MOTOR POWER ARE APPROXIMATE. THE CONTRACTOR SHALL
SUBMIT FINAL CALCULATIONS AFTER FINAL ROUTING OF CHW PIPES IS
DESIGNED. IF THE SELECTED MOTOR SIZE IS LARGER THAN THE DESIGN
MOTOR SIZE, THE CONTRACTOR SHALL MAKE THE NECESSARY
MODIFICATIONS INCLUDING ELECTRICAL WORKS AT NO ADDITIONAL
COST.

NOV.2019 27
HVAC CALCULATIONS

Cooling Load Report


APPENDIX A

   DEC.2019
Cooling Load Report
APPENDIX A

1. Weather

   

   DEC.2019
Design Weather Parameters & MSHGs
KFUPM 09/29/2019
KA 12:49PM

Design Parameters:

City Name ...................................................................................................... Dhahran


Location ................................................................................................. Saudi Arabia
Latitude ................................................................................................................. 26.2 Deg.
Longitude ............................................................................................................. -50.1 Deg.
Elevation ............................................................................................................... 89.0 m
Summer Design Dry-Bulb ..................................................................................... 45.2 °C
Summer Coincident Wet-Bulb .............................................................................. 23.4 °C
Summer Daily Range ........................................................................................... 13.4 K
Winter Design Dry-Bulb .......................................................................................... 7.0 °C
Winter Design Wet-Bulb ......................................................................................... 3.2 °C
Atmospheric Clearness Number ........................................................................... 1.00
Average Ground Reflectance ............................................................................... 0.20
Soil Conductivity ................................................................................................. 1.385 W/(m K)
Local Time Zone (GMT +/- N hours) ...................................................................... -3.0 hours
Consider Daylight Savings Time ............................................................................. No
Simulation Weather Data .................................................................................. (IWC)
Current Data is .................................................................................... User Modified
Design Cooling Months ........................................................... January to December

Design Day Maximum Solar Heat Gains

(The MSHG values are expressed in W/m² )

Month N NNE NE ENE E ESE SE SSE S


January 82.1 82.1 127.8 363.2 606.4 748.8 795.8 765.6 733.5
February 92.6 92.6 255.5 488.7 680.9 782.1 762.0 686.2 628.8
March 104.2 117.6 392.4 603.8 719.2 753.4 687.0 554.2 465.9
April 115.1 265.8 494.9 655.7 717.6 669.7 551.3 369.4 268.4
May 130.9 361.4 555.7 673.6 691.1 604.9 440.2 239.0 163.6
June 168.8 391.1 576.8 674.2 671.3 568.5 392.4 194.9 142.2
July 135.9 359.3 554.4 663.3 673.4 582.6 430.4 232.4 160.8
August 120.1 254.6 486.9 635.1 688.5 641.5 531.5 356.0 259.5
September 107.9 125.0 362.3 574.4 694.9 711.0 662.4 539.1 458.2
October 95.6 95.6 227.0 489.0 660.4 740.3 748.4 671.8 615.4
November 83.4 83.4 117.7 381.6 574.6 736.6 784.6 759.6 726.0
December 77.4 77.4 85.9 318.3 561.7 726.8 789.2 782.9 763.2
Month SSW SW WSW W WNW NW NNW HOR Mult
January 771.2 801.8 733.3 605.9 384.9 110.9 82.1 641.0 1.00
February 687.7 768.0 779.0 689.1 491.9 250.7 92.6 753.8 1.00
March 549.4 680.0 759.7 730.5 589.3 387.6 132.2 847.7 1.00
April 365.3 544.7 678.5 716.8 646.1 486.6 274.1 883.6 1.00
May 236.5 436.0 608.4 688.7 666.2 548.1 369.0 886.4 1.00
June 191.5 391.6 573.5 666.5 661.5 571.2 403.2 878.6 1.00
July 228.9 427.4 593.2 669.6 647.4 548.4 369.6 871.9 1.00
August 350.7 523.5 653.5 691.3 625.5 473.9 272.3 863.5 1.00
September 538.8 662.0 712.8 696.6 573.7 358.7 126.8 822.7 1.00
October 671.0 745.9 750.4 645.2 486.8 240.5 95.6 744.2 1.00
November 757.8 779.5 739.1 583.8 376.0 122.9 83.4 640.4 1.00
December 788.8 793.6 724.8 542.9 336.8 77.6 77.4 593.2 1.00
Mult. = User-defined solar multiplier factor.

Hourly Analysis Program vv5.00 Page 1 of 1


Cooling Load Report
APPENDIX A

2.Wall, roof, and window construction.

   DEC.2019
Wall Constructions
KFUPM 09/29/2019
KA 02:13PM

external wall

Wall Details
Outside Surface Color ....................................... Dark
Absorptivity ....................................................... 0.900
Overall U-Value ................................................ 0.320 W/(m²ꞏK)

Wall Layers Details (Inside to Outside)


Thickness Density Specific Ht. R-Value Weight
Layers mm kg/m³ kJ / (kg K) (m²ꞏK)/W kg/m²
Inside surface resistance 0.000 0.0 0.00 0.12064 0.0
Gypsum board 12.500 800.9 1.09 0.09862 10.0
Air space 20.000 0.0 0.00 2.00000 0.0
LW concrete block 100.000 608.7 0.84 0.51922 60.9
FACE BRICK 20.000 2002.3 0.92 0.18000 40.0
METAL FRAME 50.000 0.0 0.00 0.15889 0.0
Outside surface resistance 0.000 0.0 0.00 0.05000 0.0
Totals 202.500 - 3.12737 110.9

Hourly Analysis Program vv5.00 Page 1 of 1


Roof Constructions
KFUPM 11/27/2019
KA 12:56PM

RRoof

Roof Details
Outside Surface Color ....................................... Dark
Absorptivity ....................................................... 0.900
Overall U-Value ................................................ 0.260 W/(m²ꞏK)

Roof Layers Details (Inside to Outside)


Thickness Density Specific Ht. R-Value Weight
Layers mm kg/m³ kJ / (kg K) (m²ꞏK)/W kg/m²
Inside surface resistance 0.000 0.0 0.00 0.15000 0.0
LW concrete SLAB 26.667 640.7 0.84 0.79550 205.0
POLYFOAM 5.417 640.7 0.84 2.82600 41.6
PERLITE SCREED 4.167 32.0 0.92 0.03200 1.6
PORCELAIN TILES 6.667 1121.3 1.47 0.04300 89.7
Outside surface resistance 0.000 0.0 0.00 0.00500 0.0
Totals 42.917 - 3.85150 338.0

Hourly Analysis Program vv5.00 Page 1 of 1


Window Constructions
KFUPM 09/29/2019
KA 02:14PM

3.5MX0.95M

Window Details:
Detailed Input ....................................................... No
Height ................................................................. 3.50 m
Width .................................................................. 0.95 m
Overall U-Value ................................................ 1.500 W/(m²ꞏK)
Overall Shade Coefficient ................................ 0.250

3.5MX1M

Window Details:
Detailed Input ....................................................... No
Height ................................................................. 3.50 m
Width .................................................................. 1.00 m
Overall U-Value ................................................ 1.500 W/(m²ꞏK)
Overall Shade Coefficient ................................ 0.250

3.8MX1.025M

Window Details:
Detailed Input ....................................................... No
Height ................................................................. 3.80 m
Width .................................................................. 1.03 m
Overall U-Value ................................................ 1.500 W/(m²ꞏK)
Overall Shade Coefficient ................................ 0.250

3.8MX3.5M

Window Details:
Detailed Input ....................................................... No
Height ................................................................. 3.80 m
Width .................................................................. 3.50 m
Overall U-Value ................................................ 1.500 W/(m²ꞏK)
Overall Shade Coefficient ................................ 0.250

3MX0.8M

Window Details:
Detailed Input ....................................................... No
Height ................................................................. 3.00 m
Width .................................................................. 0.80 m
Overall U-Value ................................................ 1.500 W/(m²ꞏK)
Overall Shade Coefficient ................................ 0.250

3MX0.95M

Window Details:
Detailed Input ....................................................... No
Height ................................................................. 3.00 m
Width .................................................................. 0.95 m
Overall U-Value ................................................ 1.500 W/(m²ꞏK)
Overall Shade Coefficient ................................ 0.250

3MX0.9M

Window Details:
Detailed Input ....................................................... No
Height ................................................................. 3.00 m
Width .................................................................. 0.90 m
Overall U-Value ................................................ 1.500 W/(m²ꞏK)
Overall Shade Coefficient ................................ 0.250

Hourly Analysis Program vv5.00 Page 1 of 3


Window Constructions
KFUPM 09/29/2019
KA 02:14PM

3MX1.025M

Window Details:
Detailed Input ....................................................... No
Height ................................................................. 3.00 m
Width .................................................................. 1.03 m
Overall U-Value ................................................ 1.500 W/(m²ꞏK)
Overall Shade Coefficient ................................ 0.250

4.45MX1.8M

Window Details:
Detailed Input ....................................................... No
Height ................................................................. 4.45 m
Width .................................................................. 1.80 m
Overall U-Value ................................................ 1.500 W/(m²ꞏK)
Overall Shade Coefficient ................................ 0.250

4.7MX0.985M

Window Details:
Detailed Input ....................................................... No
Height ................................................................. 4.70 m
Width .................................................................. 0.99 m
Overall U-Value ................................................ 1.500 W/(m²ꞏK)
Overall Shade Coefficient ................................ 0.250

4MX1.025M

Window Details:
Detailed Input ....................................................... No
Height ................................................................. 4.00 m
Width .................................................................. 1.03 m
Overall U-Value ................................................ 1.500 W/(m²ꞏK)
Overall Shade Coefficient ................................ 0.250

5.35MX0.575M

Window Details:
Detailed Input ....................................................... No
Height ................................................................. 5.35 m
Width .................................................................. 0.58 m
Overall U-Value ................................................ 1.500 W/(m²ꞏK)
Overall Shade Coefficient ................................ 0.250

5.35MX0.925M

Window Details:
Detailed Input ....................................................... No
Height ................................................................. 5.35 m
Width .................................................................. 0.93 m
Overall U-Value ................................................ 1.500 W/(m²ꞏK)
Overall Shade Coefficient ................................ 0.250

5.35MX1.025M

Window Details:
Detailed Input ....................................................... No
Height ................................................................. 5.35 m
Width .................................................................. 1.03 m
Overall U-Value ................................................ 1.500 W/(m²ꞏK)
Overall Shade Coefficient ................................ 0.250

Hourly Analysis Program vv5.00 Page 2 of 3


Window Constructions
KFUPM 09/29/2019
KA 02:14PM

window (.1) m2

Window Details:
Detailed Input ....................................................... No
Height ................................................................. 0.50 m
Width .................................................................. 0.20 m
Overall U-Value ................................................ 1.500 W/(m²ꞏK)
Overall Shade Coefficient ................................ 0.250

window 1 m2

Window Details:
Detailed Input ....................................................... No
Height ................................................................. 1.00 m
Width .................................................................. 1.00 m
Overall U-Value ................................................ 1.500 W/(m²ꞏK)
Overall Shade Coefficient ................................ 0.250

Hourly Analysis Program vv5.00 Page 3 of 3


Cooling Load Report
APPENDIX A

3.Schedules.

   DEC.2019
Schedule Input Data
KFUPM 09/29/2019
KA 03:23PM

EQUIPMENT (Fractional)

Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4

LIGHTING (Fractional)

Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Hourly Analysis Program vv5.00 Page 1 of 3


Schedule Input Data
KFUPM 09/29/2019
KA 03:23PM

Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4

PEOPLE (Fractional)

Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4

THERMOSTAT (Fan / Thermostat)

Hourly Profiles:
1:Profile One
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O

2:Profile Two
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O

3:Profile Three
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O

4:Profile Four
Hour 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Value O O O O O O O O O O O O O O O O O O O O O O O O

Hourly Analysis Program vv5.00 Page 2 of 3


Schedule Input Data
KFUPM 09/29/2019
KA 03:23PM

O = Occupied; U = Unoccupied

Assignments:
Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Design 1 1 1 1 1 1 1 1 1 1 1 1
Monday 2 2 2 2 2 2 2 2 2 2 2 2
Tuesday 2 2 2 2 2 2 2 2 2 2 2 2
Wednesday 2 2 2 2 2 2 2 2 2 2 2 2
Thursday 2 2 2 2 2 2 2 2 2 2 2 2
Friday 2 2 2 2 2 2 2 2 2 2 2 2
Saturday 3 3 3 3 3 3 3 3 3 3 3 3
Sunday 4 4 4 4 4 4 4 4 4 4 4 4
Holiday 4 4 4 4 4 4 4 4 4 4 4 4

Hourly Analysis Program vv5.00 Page 3 of 3


Cooling Load Report
APPENDIX A

4.Space Input.

   DEC.2019
Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

001-BS-LOST & FOUND OFF

1. General Details:
Floor Area ........................................................... 8.7 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 10.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ........................................................... 8.7 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 28.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 1 of524 1


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

002-BS- H.K WORK STATION

1. General Details:
Floor Area ......................................................... 28.6 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 50.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 5.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 250.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 28.6 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 33.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 2 of524 2


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

003-BS- H.K OFFICE

1. General Details:
Floor Area ......................................................... 10.4 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 10.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 10.0 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.5 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 3 of524 3


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

004-BS- VALET LAUNDARY

1. General Details:
Floor Area ......................................................... 57.0 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .......................................... 740.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 6.0 People
Wattage ............................................................ 4.50 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ......................................................... 11035 W
Schedule ........................................................ None Schedule ............................................. EQUIPMENT
Latent .............................................................. 2950 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 57.0 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 57.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 4 of524 4


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

005-BS- LIFT LOBBY

1. General Details:
Floor Area ......................................................... 26.4 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 10.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 26.4 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 45.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 35.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 5 of524 5


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

006-BS- CORR 01UP

1. General Details:
Floor Area ......................................................... 67.6 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .......................................... 145.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 67.6 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 68.4 m² Area .................................................................. 16.6 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 35.2 °C Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 6 of524 6


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

007-BS- UNIFORM

1. General Details:
Floor Area ......................................................... 52.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .......................................... 115.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ............................................................... 67 W
Schedule ........................................................ None Schedule ............................................. EQUIPMENT
Latent .................................................................. 33 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 52.5 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 83.0 m² Area .................................................................. 18.2 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 7 of524 7


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

008-BS- CLEAN LINEN

1. General Details:
Floor Area ......................................................... 44.1 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 20.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 44.1 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 64.3 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 8 of524 8


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

009-BS- DIRTY LINEN

1. General Details:
Floor Area ......................................................... 49.7 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 70.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 6.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 49.7 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 21.6 m² Area .................................................................... 7.2 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 9 of524 9


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

010-BS- ELEC 01

1. General Details:
Floor Area ......................................................... 16.6 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 16.6 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 10 of524 10


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

011-BS- IDF 01

1. General Details:
Floor Area ........................................................... 8.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ........................................................... 8.5 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 11 of524 11


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

012-BS- DEBOXING

1. General Details:
Floor Area ......................................................... 31.8 m²
Avg. Ceiling Height ............................................. 4.0 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .......................................... 105.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ............................................................. 570 W
Schedule ........................................................ None Schedule ............................................. EQUIPMENT
Latent ................................................................ 262 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 31.8 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 31.8 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 17.2 m² Area .................................................................. 37.6 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 12 of524 12


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

013-BS- GSM

1. General Details:
Floor Area ......................................................... 15.4 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ...................................................... 36000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 15.4 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 15.4 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 32.2 m² Area .................................................................. 27.4 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 13 of524 13


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

014 -BS- Baverage STORE

1. General Details:
Floor Area ........................................................... 6.2 m²
Avg. Ceiling Height ............................................. 4.0 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 20.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ........................................................... 6.2 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 6.4 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 14 of524 14


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

015-BS- PUMP ROOM

1. General Details:
Floor Area ......................................................... 23.0 m²
Avg. Ceiling Height ............................................. 4.6 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 1200.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 23.0 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ............................... Ceiling Partition Partition Type .................................... Wall Partition
Area .................................................................. 53.8 m² Area .................................................................. 43.7 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 15 of524 15


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

016-BS- COST CONTROL

1. General Details:
Floor Area ........................................................... 6.5 m²
Avg. Ceiling Height ............................................. 3.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 10.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 6.5 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ........................................................... 6.5 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 10.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 16 of524 16


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

017-BS- PUR.

1. General Details:
Floor Area ........................................................... 6.0 m²
Avg. Ceiling Height ............................................. 3.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 10.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 6.0 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ........................................................... 6.0 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 9.2 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 17 of524 17


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

018-BS- RECV.

1. General Details:
Floor Area ........................................................... 6.4 m²
Avg. Ceiling Height ............................................. 4.0 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 10.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 6.4 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ........................................................... 6.4 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 10.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 18 of524 18


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

019-BS- SEC.

1. General Details:
Floor Area ......................................................... 11.1 m²
Avg. Ceiling Height ............................................. 4.0 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 10.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.8 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 10.8 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 12.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 19 of524 19


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

020-BS- FLOWER

1. General Details:
Floor Area ........................................................... 5.3 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 15.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ........................................................... 5.3 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 9.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 20 of524 20


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

021-BS- MEP

1. General Details:
Floor Area ......................................................... 11.4 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 10.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 8.30 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 11.4 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 18.7 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 21 of524 21


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

022 -BS-CARPENTER

1. General Details:
Floor Area ......................................................... 19.6 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 45.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 14.30 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 19.6 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 19.2 m² Area .................................................................. 24.5 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 22 of524 22


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

023-BS- UPS

1. General Details:
Floor Area ......................................................... 18.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .......................................... 130.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 250.00 W/m²
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 18.5 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 49.0 m² Area .................................................................. 10.6 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 23 of524 23


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

024 -BS- MAINTSTORE

1. General Details:
Floor Area ......................................................... 18.0 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 18.0 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 24.5 m² Area .................................................................. 16.8 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 24 of524 24


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

025-BS- BMS

1. General Details:
Floor Area ........................................................... 9.8 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 10.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 500.00 W/m²
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ........................................................... 9.8 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.5 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 25 of524 25


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

026-BS- CHEF. ENG.

1. General Details:
Floor Area ......................................................... 12.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 10.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 10.0 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type ................................ Ceiling Partition
Area .................................................................... 7.2 m² Area .................................................................. 16.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 26 of524 26


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

027-BS- ASS. ENG.

1. General Details:
Floor Area ......................................................... 14.0 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 20.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.1 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 10.4 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type ................................ Ceiling Partition
Area .................................................................. 33.6 m² Area .................................................................. 12.5 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 27 of524 27


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

028-BS- GENERAL WORKSHOP

1. General Details:
Floor Area ......................................................... 44.6 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .......................................... 100.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 9.0 People
Wattage .......................................................... 14.30 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.8 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 44.6 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type ................................ Ceiling Partition
Area .................................................................. 42.7 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 28 of524 28


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

029-BS- CORRIDOR02

1. General Details:
Floor Area ......................................................... 58.7 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 80.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.8 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 58.7 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 20.6 m² Area .................................................................. 40.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 29 of524 29


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

030-BS- FURNITURE ST

1. General Details:
Floor Area ......................................................... 82.8 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 6.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 82.8 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 82.8 m²
Exposed Perimeter ........................................... 18.3 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 4.8 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 87.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 30 of524 30


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

031-BS- LIFT LOBBY

1. General Details:
Floor Area ......................................................... 50.6 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 20.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 50.6 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 68.2 m² Area .................................................................. 39.4 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 31 of524 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

032-BS- RMU

1. General Details:
Floor Area ......................................................... 53.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 50.00 W/m²
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 20.4 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type .................................................... external wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 53.5 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 53.5 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 89.3 m² Area .................................................................. 19.2 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 32 of524 32


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

033-BS- CORR 01DN

1. General Details:
Floor Area ......................................................... 79.8 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .......................................... 195.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 42.8 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 79.8 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 11.5 m² Area .................................................................. 23.5 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 35.2 °C Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 33 of524 33


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

034-BS- ELEC 02

1. General Details:
Floor Area ........................................................... 6.8 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ........................................................... 6.8 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 38.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 34 of524 34


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

035-BS- IDF 02

1. General Details:
Floor Area ........................................................... 7.9 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ........................................................... 7.9 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 34.6 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 35 of524 35


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

036-BS- WASTE

1. General Details:
Floor Area ......................................................... 48.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .......................................... 210.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ............................................... 35.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 48.5 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 15.8 m² Area .................................................................. 71.5 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 36 of524 36


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

037-BS- M. ELEC ROOM

1. General Details:
Floor Area ....................................................... 204.7 m²
Avg. Ceiling Height ............................................. 3.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 50.00 W/m²
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 35.5 0 0 0

3.1. Construction Types for Exposure SSE


Wall Type .................................................... external wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 204.7 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ....................................................... 204.7 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area ................................................................ 124.6 m² Area .................................................................. 95.0 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 37 of524 37


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

038-BS- M. TELELECOM RM

1. General Details:
Floor Area ......................................................... 17.6 m²
Avg. Ceiling Height ............................................. 3.3 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ...................................................... 15000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.6 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 17.6 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 28.1 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 38 of524 38


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

039-BS- SECURITY

1. General Details:
Floor Area ......................................................... 31.1 m²
Avg. Ceiling Height ............................................. 3.1 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 25.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 500.00 W/m²
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 31.1 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 31.1 m²
Exposed Perimeter ............................................. 5.5 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 3.1 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 6.7 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 39 of524 39


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

040-BS- SECURITY EQU.

1. General Details:
Floor Area ......................................................... 23.7 m²
Avg. Ceiling Height ............................................. 3.3 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ...................................................... 27500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.7 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 23.7 m²
Exposed Perimeter ............................................. 4.6 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 3.3 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 40 of524 40


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

041-BS- SERVER

1. General Details:
Floor Area ......................................................... 46.1 m²
Avg. Ceiling Height ............................................. 3.3 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ............................................. EQUIPMENT
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ...................................................... 53750.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 46.1 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 46.1 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 22.4 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 41 of524 41


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

042-BS- IT DIRECTOR

1. General Details:
Floor Area ........................................................... 7.6 m²
Avg. Ceiling Height ............................................. 3.3 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 10.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 7.6 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ........................................................... 7.6 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 9.2 m² Area .................................................................... 8.6 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 42 of524 42


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

043-BS- IT TECHNICIANS

1. General Details:
Floor Area ......................................................... 11.6 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 10.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 250.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 11.6 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 11.6 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 43 of524 43


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

044-BS- PUMP ROOM

1. General Details:
Floor Area ....................................................... 227.6 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 9220.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 227.6 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ....................................................... 227.6 m²
Exposed Perimeter ........................................... 16.5 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 4.8 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area ................................................................ 153.6 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 44 of524 44


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

045*-BS- STORE

1. General Details:
Floor Area ......................................................... 31.2 m²
Avg. Ceiling Height ............................................. 3.1 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 31.2 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 31.2 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 9.3 m² Area .................................................................. 71.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 45 of524 45


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

045-BS- STORE -05

1. General Details:
Floor Area ......................................................... 14.8 m²
Avg. Ceiling Height ............................................. 3.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 14.8 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 14.8 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 63.8 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 46 of524 46


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

046-BS- ETS ROOM

1. General Details:
Floor Area ....................................................... 107.4 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 2500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ....................................................... 107.4 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 46.1 m² Area ................................................................ 119.0 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 47 of524 47


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

047-BS- PUMP ROOM

1. General Details:
Floor Area ......................................................... 76.2 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6750.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 76.2 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 18.7 m² Area .................................................................. 76.8 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 48 of524 48


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

048-BS- IDF 05

1. General Details:
Floor Area ........................................................... 5.8 m²
Avg. Ceiling Height ............................................. 3.1 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ........................................................... 5.8 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 16.7 m² Area .................................................................. 16.7 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 49 of524 49


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

049 -BS- LIFT LOBBY-02

1. General Details:
Floor Area ......................................................... 96.2 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 30.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 96.2 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area ................................................................ 136.8 m² Area .................................................................. 76.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 50 of524 50


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

050-BS- IDF 03

1. General Details:
Floor Area ........................................................... 8.3 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ........................................................... 8.3 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 12.5 m² Area .................................................................. 27.8 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 51 of524 51


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

051-BS- ELEC 03

1. General Details:
Floor Area ........................................................... 7.0 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ........................................................... 7.0 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 50.8 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 52 of524 52


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

052-BS- IDF 04

1. General Details:
Floor Area ........................................................... 5.6 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ........................................................... 5.6 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 7.2 m² Area .................................................................. 38.9 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 53 of524 53


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

053-BS- ELEC 04

1. General Details:
Floor Area ........................................................... 6.7 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ........................................................... 6.7 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 49.9 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 54 of524 54


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

054-BS- PUMP ROOM

1. General Details:
Floor Area ......................................................... 58.2 m²
Avg. Ceiling Height ............................................. 5.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 2170.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 58.2 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area ................................................................ 198.7 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 55 of524 55


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

055-BS- PUMP ROOM

1. General Details:
Floor Area ......................................................... 62.6 m²
Avg. Ceiling Height ............................................. 4.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 2500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 62.6 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 62.6 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area ................................................................ 149.6 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 56 of524 56


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

056*-BS- PUMP ROOM

1. General Details:
Floor Area ......................................................... 14.7 m²
Avg. Ceiling Height ............................................. 4.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 2400.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 33.1 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 14.7 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 71.3 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 57 of524 57


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

056-BS- PUMP ROOM

1. General Details:
Floor Area ......................................................... 33.1 m²
Avg. Ceiling Height ............................................. 4.0 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 3600.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 33.1 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 33.1 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 47.6 m² Area .................................................................. 47.6 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 58 of524 58


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

057-BS- CORRIDOR03

1. General Details:
Floor Area ......................................................... 35.5 m²
Avg. Ceiling Height ............................................. 4.0 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 15.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ............................................................... 75 W
Schedule ........................................................ None Schedule ............................................. EQUIPMENT
Latent .................................................................. 16 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 35.5 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................................ Slab Floor Below Grade
Floor Area ......................................................... 35.5 m²
Exposed Perimeter ............................................. 0.0 m
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Floor Depth ......................................................... 0.0 m
Basement Wall U-Value .................................. 0.568 W/(m²·K)
Wall Insulation R-Value ..................................... 0.00 (m²·K)/W
Wall Insulation Depth .......................................... 0.0 m

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 4.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 45.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 59 of524 59


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

058 - GR - FIRE COMM.

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 20.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 50.00 W/m²
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 27.0 0 0 0
NNW 21.5 19 3 0

3.1. Construction Types for Exposure WSW


Wall Type .................................................... external wall

3.2. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 60 of524 60


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

059 - GR - STAFF ROOM

1. General Details:
Floor Area ......................................................... 18.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 40.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 22.3 0 0 0
SSE 21.3 9 6 0

3.1. Construction Types for Exposure WSW


Wall Type .................................................... external wall

3.2. Construction Types for Exposure SSE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 9.2 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 61 of524 61


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

060 - GR - LUGG. ST

1. General Details:
Floor Area ......................................................... 12.2 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 15.6 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 10.6 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 62 of524 62


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

061- GR - PREFUNCTION

1. General Details:
Floor Area ....................................................... 368.8 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ...................................................... 111.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 79.6 61 7 0
SSE 16.3 7 0 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

3.2. Construction Types for Exposure SSE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ....................................................... 368.8 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area ................................................................ 241.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 63 of524 63


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

062 - GR - MERCHANDISE

1. General Details:
Floor Area ......................................................... 92.7 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 22.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 43.6 35 0 0
ENE 54.2 13 8 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2

3.2. Construction Types for Exposure ENE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 51.8 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area ................................................................ 101.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 64 of524 64


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

063 - GR - RECE. MEETING

1. General Details:
Floor Area ....................................................... 129.2 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 21.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 43.6 35 6 0
SSE 30.8 0 0 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
1st Window Shade Type .......................... SHADE-101 GR
2nd Window Type .................................... window (.1) m2
2nd Window Shade Type ......................... SHADE-101 GR

3.2. Construction Types for Exposure SSE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ....................................................... 129.2 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 39.7 m² Area .................................................................. 39.7 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 65 of524 65


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

064 - GR - AIR LOCK-01

1. General Details:
Floor Area ......................................................... 36.4 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 10.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 43.6 35 8 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 36.0 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 66 of524 66


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

065C - GR - BALL ROOM 2

1. General Details:
Floor Area ....................................................... 281.4 m²
Avg. Ceiling Height ............................................. 7.6 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ...................................................... 160.0 People
Wattage .......................................................... 12.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 9.00 W/m²
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 281.4 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ....................................................... 281.4 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 67 of524 67


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

065L - GR - BALL ROOM1

1. General Details:
Floor Area ....................................................... 359.1 m²
Avg. Ceiling Height ............................................. 7.6 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ...................................................... 160.0 People
Wattage .......................................................... 12.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 9.00 W/m²
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 195.2 106 8 0

3.1. Construction Types for Exposure SSE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 359.1 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ....................................................... 359.1 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 38.8 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 68 of524 68


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

065R - GR - BALL ROOM3

1. General Details:
Floor Area ....................................................... 343.3 m²
Avg. Ceiling Height ............................................. 7.6 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ...................................................... 160.0 People
Wattage .......................................................... 12.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 9.00 W/m²
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 343.3 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ....................................................... 343.3 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 69 of524 69


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

066 - GR - COWORKING

1. General Details:
Floor Area ......................................................... 80.6 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 25.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 43.6 35 6 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
1st Window Shade Type .......................... SHADE-102 GR
2nd Window Type .................................... window (.1) m2
2nd Window Shade Type ......................... SHADE-102 GR

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 34.4 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 14.7 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 70 of524 70


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

067 - GR - F&B DISPLAY

1. General Details:
Floor Area ......................................................... 82.0 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 12.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 47.2 35 6 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
1st Window Shade Type .......................... SHADE-103 GR
2nd Window Type .................................... window (.1) m2
2nd Window Shade Type ......................... SHADE-103 GR

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 47.2 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 27.9 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 71 of524 71


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

068- GR - AIR LOCK-02

1. General Details:
Floor Area ......................................................... 21.7 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 7.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.2 0 0 0
ENE 29.7 15 0 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall

3.2. Construction Types for Exposure ENE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 21.7 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 15.4 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 72 of524 72


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

069 - GR - LOBBY

1. General Details:
Floor Area ......................................................... 90.7 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 27.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 29.3 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 90.7 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 34.6 m² Area .................................................................. 38.8 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 73 of524 73


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

070- GR - VIP BRIDE

1. General Details:
Floor Area ......................................................... 36.8 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 6.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 36.8 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 68.3 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 74 of524 74


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

071 - GR - SOCIAL HUP

1. General Details:
Floor Area ....................................................... 168.7 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 21.0 People
Wattage .......................................................... 10.50 W/m² Activity Level ....................................... Heavy Work
Ballast Multiplier ............................................... 1.00 Sensible .......................................................... 153.9 W/person
Schedule ................................................ LIGHTING Latent ............................................................. 271.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 80.4 34 8 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 68.7 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 56.8 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 75 of524 75


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

072 - GR - HOTTEL LOBBY

1. General Details:
Floor Area ....................................................... 186.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 19.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 71.9 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 39.4 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 76 of524 76


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

073 - GR - AIR LOCK-03

1. General Details:
Floor Area ......................................................... 31.1 m²
Avg. Ceiling Height ............................................. 8.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 7.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 79.6 65 4 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
1st Window Shade Type ........................... Shade-201 GR
2nd Window Type .................................... window (.1) m2
2nd Window Shade Type .......................... Shade-201 GR

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.0 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 31.1 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 77 of524 77


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

074-GR- IDF

1. General Details:
Floor Area ........................................................... 4.8 m²
Avg. Ceiling Height ............................................. 4.3 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 4.6 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 78 of524 78


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

075 -GR- ELEC

1. General Details:
Floor Area ........................................................... 4.5 m²
Avg. Ceiling Height ............................................. 4.3 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 4.5 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 79 of524 79


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

076 -GR- AV CONTROL RM

1. General Details:
Floor Area ......................................................... 10.2 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 1000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 10.2 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 80 of524 80


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

077 -GR- AV EQUIP.

1. General Details:
Floor Area ......................................................... 11.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 5000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 11.5 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 81 of524 81


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

078 - GR - LECTURE. LIBR

1. General Details:
Floor Area ......................................................... 59.6 m²
Avg. Ceiling Height ............................................. 9.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 89.0 People
Wattage ............................................................ 9.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 34.4 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 82 of524 82


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

079 - GR - BACK OFFICE

1. General Details:
Floor Area ......................................................... 21.6 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 40.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 5.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 250.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 21.6 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 26.5 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 83 of524 83


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

080 - GR - STAFF ENTR

1. General Details:
Floor Area ......................................................... 58.4 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 35.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 6.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 16.3 12 5 0
WSW 10.6 8 6 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

3.2. Construction Types for Exposure WSW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 27.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 84 of524 84


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

081 - GR - LUGGAGE

1. General Details:
Floor Area ......................................................... 38.2 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 26.5 12 5 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 15.1 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 85 of524 85


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

082 -GR- ELEC

1. General Details:
Floor Area ......................................................... 14.3 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 16.1 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 86 of524 86


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

083-GR- IDF

1. General Details:
Floor Area ........................................................... 7.9 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 8.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 87 of524 87


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

084-GR- HK

1. General Details:
Floor Area ......................................................... 19.6 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 35.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ............................................................. 600 W
Schedule ........................................................ None Schedule ............................................. EQUIPMENT
Latent .............................................................. 1000 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 22.1 m² Area .................................................................. 18.9 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 88 of524 88


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

085-GR- SECURITY

1. General Details:
Floor Area ........................................................... 8.1 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 10.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 250.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 16.2 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 89 of524 89


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

086 - GR - LUGGAGE

1. General Details:
Floor Area ......................................................... 14.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 35.6 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 90 of524 90


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

087 - GR - AHU

1. General Details:
Floor Area ......................................................... 38.1 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 28.0 11 3 0

3.1. Construction Types for Exposure WSW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 35.1 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 8.2 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 91 of524 91


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

088-GR- STAFF. CORRIDOR

1. General Details:
Floor Area ......................................................... 45.8 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 15.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 29.3 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 35.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 92 of524 92


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

089-GR- LIFT LOBBY

1. General Details:
Floor Area ......................................................... 16.1 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 10.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 56.4 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 93 of524 93


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

090 - GR - APPART. LOBBY

1. General Details:
Floor Area ......................................................... 80.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 6.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 80.5 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 12.3 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 94 of524 94


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

091 - GR - AIR LOCK-04

1. General Details:
Floor Area ......................................................... 26.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 7.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 43.6 32 1 0

3.1. Construction Types for Exposure WSW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 26.5 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 95 of524 95


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

092-GR- APP. CORRIDOR1

1. General Details:
Floor Area ......................................................... 39.2 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 39.2 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 76.4 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 96 of524 96


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

092'-GR- APP. CORRIDOR2

1. General Details:
Floor Area ......................................................... 18.4 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 10.8 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 31.4 m² Area .................................................................... 7.8 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 97 of524 97


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

093-GR- SHOP / ATM

1. General Details:
Floor Area ......................................................... 14.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 19.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .......................................................... 11.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 30.00 W/m²
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 14.5 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 98 of524 98


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

094 - GR - CLOAK

1. General Details:
Floor Area ........................................................... 9.7 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 9.4 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.2 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 99 of524 99


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

095-GR- IDF

1. General Details:
Floor Area ........................................................... 3.7 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 9.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 100 of524 100


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

096-GR- ELEC

1. General Details:
Floor Area ........................................................... 3.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 3.5 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 9.3 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 101 of524 101


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

097-GR- ELEC

1. General Details:
Floor Area ......................................................... 10.6 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 10.6 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 102 of524 102


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

098-GR- AHU

1. General Details:
Floor Area ......................................................... 29.0 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 29.0 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 25.5 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 103 of524 103


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

099 - GR - KIT.WASH

1. General Details:
Floor Area ......................................................... 35.9 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 55.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 7.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ........................................................... 2978 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent .............................................................. 1927 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 35.9 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 7.2 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 104 of524 104


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

100 - GR - KIT. BEV. ST

1. General Details:
Floor Area ......................................................... 14.2 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 20.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 14.2 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 105 of524 105


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

1000-F09-GST-10-BD

1. General Details:
Floor Area ......................................................... 18.0 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 12.8 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.0 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.7 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 106 of524 106


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

1001-F09-GST-11-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 2.7 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 107 of524 107


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

1002-F09-GST-11-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 15.9 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 21.4 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 1.8 m² Area .................................................................... 3.7 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 108 of524 108


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

1003-F09-GST-11-KITCHEN

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 5.1 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 10.6 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 109 of524 109


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

1004-F09-GST-11-BD

1. General Details:
Floor Area ......................................................... 18.0 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 15.9 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.0 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.7 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 110 of524 110


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

1005-F09-MAIN CORR

1. General Details:
Floor Area ....................................................... 148.5 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ...................................... User defined
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 60.1 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 7.7 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 148.5 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area ................................................................ 124.0 m² Area ................................................................ 196.6 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 111 of524 111


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

101 - GR - KIT. WASTE

1. General Details:
Floor Area ......................................................... 11.6 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 20.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ............................................................. 781 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent ................................................................ 275 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 11.6 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 14.4 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 112 of524 112


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

102- GR - KIT. BEV. DIS

1. General Details:
Floor Area ......................................................... 18.8 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 30.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ........................................................... 2197 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent ................................................................ 796 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 30.1 8 2 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
1st Window Shade Type ................... Default Shade Type
2nd Window Type .................................... window (.1) m2
2nd Window Shade Type .................. Default Shade Type

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 18.8 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 113 of524 113


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

103- GR - KIT. REGEN

1. General Details:
Floor Area ......................................................... 59.0 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 85.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 12.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ......................................................... 16511 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent .............................................................. 1156 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 59.0 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 9.6 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 114 of524 114


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

104 - GR - KIT.CLEAN ST1

1. General Details:
Floor Area ......................................................... 16.3 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 25.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 16.3 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 29.3 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 115 of524 115


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

105 - GR - KIT. HOT KIT.

1. General Details:
Floor Area ......................................................... 54.4 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 80.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 11.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ......................................................... 51620 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent ............................................................ 33380 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 54.4 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 116 of524 116


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

106 - GR - KIT. COLD KIT

1. General Details:
Floor Area ......................................................... 27.9 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 40.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 6.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ........................................................... 2278 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent ................................................................ 872 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 27.9 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 117 of524 117


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

107 - GR - KIT. DAILY ST

1. General Details:
Floor Area ......................................................... 10.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 15.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 10.5 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 118 of524 118


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

108 - GR - KIT.CLEAN ST2

1. General Details:
Floor Area ......................................................... 11.2 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 20.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 11.2 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 119 of524 119


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

109 - GR - KIT.STEW ST

1. General Details:
Floor Area ......................................................... 15.0 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 25.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 15.0 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 14.4 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 120 of524 120


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

110 - GR - KIT. VEG

1. General Details:
Floor Area ......................................................... 14.8 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 25.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ........................................................... 1462 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent ................................................................ 528 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 14.8 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 121 of524 121


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

111 - GR - KIT. MEAT-POU

1. General Details:
Floor Area ......................................................... 13.8 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .......................................... 275.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ........................................................... 2255 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent ................................................................ 808 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 13.8 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 122 of524 122


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

112 - GR - KIT. SEAFOOD

1. General Details:
Floor Area ......................................................... 14.0 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .......................................... 400.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ........................................................... 3490 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent .............................................................. 1424 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 14.0 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 123 of524 123


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

113 - GR - KIT. D. STOR

1. General Details:
Floor Area ......................................................... 26.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 40.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 5.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 26.5 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 124 of524 124


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

114- GR -KIT. ROOM SER

1. General Details:
Floor Area ......................................................... 39.7 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 70.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 8.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ........................................................... 5378 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent .............................................................. 2031 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 39.7 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 125 of524 125


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

115 - GR - KIT. PANTRY

1. General Details:
Floor Area ......................................................... 22.1 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 35.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ........................................................... 3180 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent .............................................................. 1135 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 22.1 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 126 of524 126


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

116 - GR -KIT. CHEF OFF

1. General Details:
Floor Area ........................................................... 7.0 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 10.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 7.0 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 127 of524 127


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

117 - GR -KIT. ORDER TAK

1. General Details:
Floor Area ........................................................... 5.0 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 5.0 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 128 of524 128


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

118 - GR - KIT. CORR

1. General Details:
Floor Area ....................................................... 243.8 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 75.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 49.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ........................................................... 3017 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent .............................................................. 1060 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 11.5 0 0 0
SSE 22.3 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall

3.2. Construction Types for Exposure SSE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ....................................................... 243.8 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 9.2 m² Area .................................................................. 16.8 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 129 of524 129


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

119 - GR - APP. KIDS

1. General Details:
Floor Area ......................................................... 78.6 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 20.0 People
Wattage .......................................................... 10.50 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 43.6 34 2 0

3.1. Construction Types for Exposure WSW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 78.6 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 39.7 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 130 of524 130


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

120 - GR - APP. LOUNGE

1. General Details:
Floor Area ....................................................... 122.2 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 15.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 73.2 51 6 0

3.1. Construction Types for Exposure WSW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 37.8 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 59.8 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 131 of524 131


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

121 - GR - F.TOILET

1. General Details:
Floor Area ......................................................... 35.8 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 8.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 35.8 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 98.0 m² Area .................................................................. 23.0 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 132 of524 132


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

122 - GR - M.TOILET

1. General Details:
Floor Area ......................................................... 34.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 8.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 34.5 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 78.6 m² Area .................................................................... 9.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 133 of524 133


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

123 - GR - M.TOILET

1. General Details:
Floor Area ......................................................... 13.0 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 7.5 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 38.7 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 134 of524 134


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

124 - GR - F.TOILET

1. General Details:
Floor Area ......................................................... 15.2 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 10.3 0 0 0
SSE 31.3 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall

3.2. Construction Types for Exposure SSE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 15.2 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 23.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 135 of524 135


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

125 - GR - F.TOILET

1. General Details:
Floor Area ......................................................... 12.4 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 7.4 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 34.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 136 of524 136


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

126 - GR - M.TOILET

1. General Details:
Floor Area ......................................................... 11.9 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 45.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 137 of524 137


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

127 - GR -CAR LIFTSLOBBY

1. General Details:
Floor Area ......................................................... 17.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 78.7 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 138 of524 138


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

128 - GR - LIFTSLOBBY

1. General Details:
Floor Area ......................................................... 22.5 m²
Avg. Ceiling Height ............................................. 4.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 14.0 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 78.7 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 139 of524 139


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

129-1ST- HK

1. General Details:
Floor Area ......................................................... 18.7 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 35.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ............................................................. 600 W
Schedule ........................................................ None Schedule ............................................. EQUIPMENT
Latent .............................................................. 1000 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 24.2 m² Area .................................................................. 16.2 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 140 of524 140


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

130 - 1ST - KIT. PANTRY

1. General Details:
Floor Area ......................................................... 56.9 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .......................................... 130.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 11.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ........................................................... 4625 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent .............................................................. 1835 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 27.0 0 0 0
SSE 17.6 6 3 0

3.1. Construction Types for Exposure WSW


Wall Type .................................................... external wall

3.2. Construction Types for Exposure SSE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 39.9 m² Area .................................................................. 29.4 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 141 of524 141


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

131 - 1ST - M.TOILET

1. General Details:
Floor Area ........................................................... 8.8 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 16.6 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 142 of524 142


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

132 - 1ST - BUS. LOUNGE.

1. General Details:
Floor Area ....................................................... 220.6 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .......................................... 230.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 42.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 110.5 51 2 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 34.4 m² Area .................................................................. 18.9 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 143 of524 143


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

133 - 1ST - CORRIDOR

1. General Details:
Floor Area ......................................................... 48.8 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 15.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 25.6 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 144 of524 144


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

134 - 1ST - HOTTEL LOBBY

1. General Details:
Floor Area ....................................................... 228.2 m²
Avg. Ceiling Height ............................................. 9.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 17.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 79.6 65 3 0
ENE 19.4 0 0 0
WSW 19.4 0 0 0
NNW 79.6 65 3 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
1st Window Shade Type ............................ Shade-201 1st
2nd Window Type .................................... window (.1) m2
2nd Window Shade Type ........................... Shade-201 1st

3.2. Construction Types for Exposure ENE


Wall Type .................................................... external wall

3.3. Construction Types for Exposure WSW


Wall Type .................................................... external wall

3.4. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
1st Window Shade Type ............................ Shade-202 1st
2nd Window Type .................................... window (.1) m2
2nd Window Shade Type ........................... Shade-202 1st

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 34.6 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program vv5.00 Page 145 of524 145


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ....................................................... 133.0 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 146 of524 146


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

135 - 1ST - LEC. LOUNGE

1. General Details:
Floor Area ....................................................... 162.6 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 29.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 18.9 m² Area .................................................................. 37.8 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 147 of524 147


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

136 - 1ST - MEETING 1

1. General Details:
Floor Area ......................................................... 83.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 32.0 People
Wattage ............................................................ 9.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 36.9 15 0 0
SSE 36.9 32 2 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2

3.2. Construction Types for Exposure SSE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 148 of524 148


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

137 - 1ST - MEETING 2

1. General Details:
Floor Area ......................................................... 65.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 25.0 People
Wattage ............................................................ 9.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 36.9 6 1 0
NNW 36.9 32 2 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

3.2. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 149 of524 149


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

138 - 1ST - PLAYFUL MEET

1. General Details:
Floor Area ......................................................... 57.9 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 10.0 People
Wattage ............................................................ 9.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 36.9 25 8 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
1st Window Shade Type .......................... SHADE-102 1st
2nd Window Type .................................... window (.1) m2
2nd Window Shade Type ......................... SHADE-102 1st

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 150 of524 150


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

139 - 1ST -LOUNGE MEET

1. General Details:
Floor Area ......................................................... 63.8 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 17.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 36.9 25 8 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
1st Window Shade Type .......................... SHADE-103 1st
2nd Window Type .................................... window (.1) m2
2nd Window Shade Type ......................... SHADE-103 1st

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 151 of524 151


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

140 - 1ST - LOUNG

1. General Details:
Floor Area ....................................................... 105.6 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 10.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 36.9 25 8 0
SSE 32.8 14 9 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
1st Window Shade Type .......................... SHADE-101 1st
2nd Window Type .................................... window (.1) m2
2nd Window Shade Type ......................... SHADE-101 1st

3.2. Construction Types for Exposure SSE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 68.7 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 152 of524 152


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

140'- 1ST - MEET CORR.

1. General Details:
Floor Area ......................................................... 43.8 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 10.1 m² Area .................................................................. 27.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 153 of524 153


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

141 - 1ST - RLIFTS LOBBY

1. General Details:
Floor Area ......................................................... 21.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 81.4 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 154 of524 154


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

142 - 1ST -LLIFTS LOBBY

1. General Details:
Floor Area ......................................................... 22.8 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 68.9 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 155 of524 155


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

143 - 1ST - C LIFTLOBBY

1. General Details:
Floor Area ......................................................... 41.8 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 40.5 m² Area .................................................................. 34.4 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 156 of524 156


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

144 - 1ST - F.PRAYER

1. General Details:
Floor Area ......................................................... 23.6 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 33.0 People
Wattage .......................................................... 12.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 18.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 157 of524 157


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

145 - 1ST - F.ABULATION

1. General Details:
Floor Area ......................................................... 10.6 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 158 of524 158


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

146 - 1ST - M.PRAYER

1. General Details:
Floor Area ......................................................... 29.9 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 40.0 People
Wattage .......................................................... 12.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 23.9 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 11.8 m² Area .................................................................. 13.4 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 159 of524 159


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

147 - 1ST - M.ABULATION

1. General Details:
Floor Area ........................................................... 9.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 15.5 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 160 of524 160


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

148 - 1ST - KIT. BAKERY

1. General Details:
Floor Area ......................................................... 45.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .......................................... 140.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 9.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ......................................................... 14726 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent .............................................................. 2912 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 18.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 161 of524 161


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

150 - 1ST - STAFF DINING

1. General Details:
Floor Area ....................................................... 156.7 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .......................................... 450.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 64.0 People
Wattage .......................................................... 11.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .......................................................... 15.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 23.9 m² Area .................................................................. 28.9 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 162 of524 162


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

150* - 1ST - DIN SERV

1. General Details:
Floor Area ......................................................... 29.0 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 5.0 People
Wattage .......................................................... 11.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .......................................................... 15.00 W/m² Sensible ........................................................... 4380 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent .............................................................. 2274 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 32.0 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 163 of524 163


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

151 - 1ST - STAFF CORR.

1. General Details:
Floor Area ....................................................... 140.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 45.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 27.0 0 0 0

3.1. Construction Types for Exposure SSE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area ................................................................ 129.7 m² Area .................................................................. 37.8 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 164 of524 164


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

152 - 1ST - M.PRAYER

1. General Details:
Floor Area ......................................................... 20.9 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 85.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 29.0 People
Wattage .......................................................... 12.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 25.2 m² Area .................................................................. 16.0 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 165 of524 165


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

153 - 1ST - M.ABULAT

1. General Details:
Floor Area ........................................................... 8.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 166 of524 166


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

154 - 1ST - F.PRAYER

1. General Details:
Floor Area ......................................................... 12.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 50.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 17.0 People
Wattage .......................................................... 12.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 16.0 m² Area .................................................................. 16.0 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 167 of524 167


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

155 - 1ST - F.ABULATION

1. General Details:
Floor Area ........................................................... 8.0 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 168 of524 168


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

156 -1ST- ELEC

1. General Details:
Floor Area ........................................................... 5.0 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 8.4 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 169 of524 169


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

157 -1ST- IDF

1. General Details:
Floor Area ........................................................... 4.7 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 170 of524 170


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

158 -1ST- AHU

1. General Details:
Floor Area ......................................................... 29.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 29.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 171 of524 171


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

159 -1ST- M. LOCKER

1. General Details:
Floor Area ......................................................... 54.9 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 7.0 People
Wattage ............................................................ 4.50 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 5.0 m² Area .................................................................. 50.8 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 172 of524 172


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

160 -1ST- F. LOCKER

1. General Details:
Floor Area ......................................................... 25.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 5.0 People
Wattage ............................................................ 4.50 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 11.3 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 13.8 m² Area .................................................................. 22.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 173 of524 173


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

162 - 1ST - F.TOILET

1. General Details:
Floor Area ........................................................... 7.7 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 9.4 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.5 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 174 of524 174


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

163 -1ST- AHU

1. General Details:
Floor Area ......................................................... 58.0 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 1000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 36.9 14 2 0

3.1. Construction Types for Exposure WSW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 13.4 m² Area .................................................................. 22.7 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 175 of524 175


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

164 - 1ST - KIT. PANTRY

1. General Details:
Floor Area ......................................................... 20.5 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 65.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ........................................................... 1788 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent ................................................................ 729 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 176 of524 176


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

165 - 1ST - KIT. WASH

1. General Details:
Floor Area ......................................................... 18.0 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 55.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ........................................................... 2788 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent .............................................................. 2035 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 177 of524 177


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

166 - 1ST - M.TOILET

1. General Details:
Floor Area ......................................................... 10.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.2 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 178 of524 178


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

167 - 1ST - F.TOILET

1. General Details:
Floor Area ........................................................... 6.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 10.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 179 of524 179


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

168 -1ST- ELEC

1. General Details:
Floor Area ........................................................... 7.9 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 180 of524 180


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

169 -1ST- ELEC

1. General Details:
Floor Area ......................................................... 16.8 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 14.7 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 181 of524 181


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

170 -1ST- IDF

1. General Details:
Floor Area ........................................................... 8.5 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.2 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 182 of524 182


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

171 -1ST- SERVICE LOBBY

1. General Details:
Floor Area ......................................................... 14.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 10.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 52.3 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 183 of524 183


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

172 -1ST- OFF. FD

1. General Details:
Floor Area ........................................................... 7.8 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 184 of524 184


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

173 -1ST- OFF. OFFICE

1. General Details:
Floor Area ........................................................... 7.1 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 10.0 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 185 of524 185


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

174 -1ST- OFF. CORR

1. General Details:
Floor Area ......................................................... 83.1 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 18.5 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 186 of524 186


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

175 -1ST- OFF. TRAIN D.

1. General Details:
Floor Area ........................................................... 7.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 187 of524 187


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

176 -1ST- OFF. TRAINING

1. General Details:
Floor Area ......................................................... 33.0 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 7.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 875.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 188 of524 188


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

177 -1ST- OFF.HR. D.

1. General Details:
Floor Area ........................................................... 8.7 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 189 of524 189


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

178 -1ST- OFF.HR.ASS.

1. General Details:
Floor Area ........................................................... 8.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 190 of524 190


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

179 -1ST- OFF. OPEN OFF.

1. General Details:
Floor Area ......................................................... 76.5 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 13.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 1625.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 35.3 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 191 of524 191


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

180 -1ST- OFF. FINANCE

1. General Details:
Floor Area ......................................................... 32.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 192 of524 192


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

181 -1ST- OFF. ASS.

1. General Details:
Floor Area ......................................................... 11.7 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 5.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 4.2 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 193 of524 193


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

182 -1ST- OFF. DIRECTOR

1. General Details:
Floor Area ......................................................... 10.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 194 of524 194


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

183 -1ST- OFF. CASHER

1. General Details:
Floor Area ........................................................... 8.0 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 195 of524 195


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

184 -1ST- OFF. D. OPER.

1. General Details:
Floor Area ........................................................... 8.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 11.0 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 196 of524 196


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

185 - 1ST - OFF. PANTRY

1. General Details:
Floor Area ........................................................... 7.5 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ............................................................. 500 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 197 of524 197


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

186 -1ST- OFF. DOS M.

1. General Details:
Floor Area ........................................................... 7.8 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 8.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 125.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 198 of524 198


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

187 -1ST- OFF. SERVER

1. General Details:
Floor Area ......................................................... 19.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 199 of524 199


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

188 -1ST- AHU

1. General Details:
Floor Area ....................................................... 412.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 3500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 125.6 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 200 of524 200


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

189 -1ST- AHURM CORR.

1. General Details:
Floor Area ......................................................... 22.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 4.6 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 201 of524 201


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

190 -1ST- ELEC

1. General Details:
Floor Area ........................................................... 6.1 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 12.2 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 202 of524 202


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

191 -1ST- IDF

1. General Details:
Floor Area ........................................................... 6.0 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 8.2 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 203 of524 203


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

192 -1ST- PUMP ROOM

1. General Details:
Floor Area ......................................................... 62.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 3700.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 15.3 7 2 0

3.1. Construction Types for Exposure SSE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 204 of524 204


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

193 -1ST- IDF

1. General Details:
Floor Area ........................................................... 9.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 16.3 0 0 0

3.1. Construction Types for Exposure SSE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 23.1 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 205 of524 205


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

194 -1ST- ELEC

1. General Details:
Floor Area ......................................................... 15.1 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 206 of524 206


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

195 -1ST- PUMPRM CORR.

1. General Details:
Floor Area ......................................................... 28.1 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 11.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 207 of524 207


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

196 -1ST- STORE

1. General Details:
Floor Area ......................................................... 12.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 24.8 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 23.5 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 208 of524 208


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

197 -1ST- IDF

1. General Details:
Floor Area ........................................................... 5.0 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 27.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 209 of524 209


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

198 - 1ST - M.TOILET

1. General Details:
Floor Area ........................................................... 8.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 26.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 210 of524 210


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

199 - 1ST - F.TOILET

1. General Details:
Floor Area ........................................................... 7.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 21.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 211 of524 211


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

218-GFL-GST-01-ENT

1. General Details:
Floor Area ........................................................... 4.2 m²
Avg. Ceiling Height ............................................. 4.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 4.2 m²
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 23.9 °C
Ambient at Space Min Temp. ............................ 12.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 13.3 m² Area .................................................................... 3.8 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 212 of524 212


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

219-GFL-GST-01-LIV

1. General Details:
Floor Area ......................................................... 27.5 m²
Avg. Ceiling Height ............................................. 4.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 6.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 29.7 3 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type .................................... 4.7MX0.985M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 27.5 m²
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Unconditioned Space Max Temp. ..................... 23.9 °C
Ambient at Space Max Temp. ........................... 35.0 °C
Unconditioned Space Min Temp. ...................... 23.9 °C
Ambient at Space Min Temp. ............................ 12.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 9.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 213 of524 213


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

220-GFL-GST-01-KITCHEN

1. General Details:
Floor Area ......................................................... 10.8 m²
Avg. Ceiling Height ............................................. 4.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 10.8 m²
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 23.9 °C
Ambient at Space Min Temp. ............................ 12.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 13.4 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 214 of524 214


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

221-GFL-GST-01-CORRIDOR

1. General Details:
Floor Area ........................................................... 4.1 m²
Avg. Ceiling Height ............................................. 4.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 4.1 m²
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 23.9 °C
Ambient at Space Min Temp. ............................ 12.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 16.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 215 of524 215


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

222-GFL-GST-01-BD

1. General Details:
Floor Area ......................................................... 16.3 m²
Avg. Ceiling Height ............................................. 4.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 17.4 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type .................................... 4.7MX0.985M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 16.3 m²
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 23.9 °C
Ambient at Space Min Temp. ............................ 12.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 216 of524 216


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

223-GFL-GST-01-MBD

1. General Details:
Floor Area ......................................................... 22.0 m²
Avg. Ceiling Height ............................................. 4.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage .......................................................... 300.0 Watts Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 22.5 2 0 0
SSE 22.5 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type .................................... 4.7MX0.985M(5)

3.2. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 22.0 m²
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 23.9 °C
Ambient at Space Min Temp. ............................ 12.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 33.8 m² Area .................................................................... 5.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 217 of524 217


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

224-GFL-GST-02-BD

1. General Details:
Floor Area ......................................................... 18.2 m²
Avg. Ceiling Height ............................................. 4.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 23.9 0 0 0
ENE 18.4 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)

3.2. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type .................................... 4.7MX0.985M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 18.2 m²
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 23.9 °C
Ambient at Space Min Temp. ............................ 12.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 20.4 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 218 of524 218


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

225-GFL-GST-02-LIV

1. General Details:
Floor Area ......................................................... 21.0 m²
Avg. Ceiling Height ............................................. 4.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 300.0 Watts Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 21.2 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type .................................... 4.7MX0.985M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 21.0 m²
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 23.9 °C
Ambient at Space Min Temp. ............................ 12.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 2.4 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 219 of524 219


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

226-GFL-GST-02-KITCHEN

1. General Details:
Floor Area ........................................................... 4.9 m²
Avg. Ceiling Height ............................................. 4.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(29)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 4.9 m²
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 23.9 °C
Ambient at Space Min Temp. ............................ 12.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.7 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 220 of524 220


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

227-GFL-GST-02-ENT.

1. General Details:
Floor Area ........................................................... 2.6 m²
Avg. Ceiling Height ............................................. 4.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 2.6 m²
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 23.9 °C
Ambient at Space Min Temp. ............................ 12.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 10.1 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 221 of524 221


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

228-GFL-ST-01

1. General Details:
Floor Area ......................................................... 34.6 m²
Avg. Ceiling Height ............................................. 4.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 300.0 Watts Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 31.0 3 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type .................................... 4.7MX0.985M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 34.6 m²
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 23.9 °C
Ambient at Space Min Temp. ............................ 12.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 24.0 m² Area .................................................................. 22.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 222 of524 222


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

229-GFL-MAIN CORR.

1. General Details:
Floor Area ......................................................... 35.9 m²
Avg. Ceiling Height ............................................. 4.7 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ...................................... User defined
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 60.1 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 9.6 0 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ......................................................... 35.9 m²
Total Floor U-Value ......................................... 0.568 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 23.9 °C
Ambient at Space Min Temp. ............................ 12.8 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 45.4 m² Area .................................................................. 32.0 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 223 of524 223


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

230-F01-GST-02-MBD

1. General Details:
Floor Area ......................................................... 22.1 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 16.4 2 0 0
SSE 16.4 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

3.2. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 20.7 m² Area .................................................................... 8.2 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 224 of524 224


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

231-F01-GST-02-BD

1. General Details:
Floor Area ......................................................... 16.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 14.0 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 225 of524 225


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

232-F01-GST-02-CORRID

1. General Details:
Floor Area ........................................................... 4.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 9.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 226 of524 226


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

233-F01-GST-02-ENT

1. General Details:
Floor Area ........................................................... 4.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 227 of524 227


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

234-F01-GST-02-LIV

1. General Details:
Floor Area ......................................................... 27.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 6.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 21.9 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 228 of524 228


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

235-F01-GST-02-KITCHE

1. General Details:
Floor Area ......................................................... 10.5 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 10.4 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 229 of524 229


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

236-F01-GST-01-MBD

1. General Details:
Floor Area ......................................................... 22.1 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 16.4 2 0 0
SSE 16.4 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

3.2. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 20.7 m² Area .................................................................... 8.2 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 230 of524 230


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

237-F01-GST-01-BD

1. General Details:
Floor Area ......................................................... 16.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 14.0 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 231 of524 231


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

238-F01-GST-01-CORRIDOR

1. General Details:
Floor Area ........................................................... 4.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 12.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 232 of524 232


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

239-F01-GST-01-ENT

1. General Details:
Floor Area ........................................................... 4.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 233 of524 233


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

240-F01-GST-01-LIV

1. General Details:
Floor Area ......................................................... 27.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 6.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 21.9 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 234 of524 234


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

241-F01-GST-01-KITCHEN

1. General Details:
Floor Area ........................................................... 5.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 9.5 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 235 of524 235


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

242-F01-ST-01

1. General Details:
Floor Area ......................................................... 34.6 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 21.9 3 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 22.9 m² Area .................................................................... 5.2 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 236 of524 236


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

243-F01-GST-03-LIV

1. General Details:
Floor Area ......................................................... 20.6 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 6.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 22.9 3 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 21.3 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 237 of524 237


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

244-F01-GST-03-ENT

1. General Details:
Floor Area ........................................................... 5.7 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 5.3 m² Area .................................................................. 12.7 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 238 of524 238


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

245-F01-GST-03-KITCHE

1. General Details:
Floor Area ........................................................... 9.7 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 8.4 1 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 9.0 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 239 of524 239


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

246-F01-GST-03-CORRIDOR

1. General Details:
Floor Area ........................................................... 3.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 11.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 240 of524 240


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

247-F01-GST-03-BD

1. General Details:
Floor Area ......................................................... 16.6 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 12.9 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 3.5 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 241 of524 241


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

248-F01-GST-03-MBD

1. General Details:
Floor Area ......................................................... 23.6 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 16.2 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 29.0 m² Area .................................................................... 5.5 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 242 of524 242


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

249-F01-GST-06-BD

1. General Details:
Floor Area ......................................................... 18.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 13.7 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.0 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 243 of524 243


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

250-F01-GST-06-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 15.4 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 1.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 244 of524 244


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

251-F01-GST-06-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 245 of524 245


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

252-F01-GST-06-KITCHEN

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 5.2 m² Area .................................................................... 2.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 246 of524 246


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

253-F01-GST-08-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 15.4 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 1.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 247 of524 247


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

254-F01-GST-08-KITCHEN

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 5.2 m² Area .................................................................... 2.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 248 of524 248


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

255-F01-GST-08-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 249 of524 249


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

256-F01-GST-08-BD

1. General Details:
Floor Area ......................................................... 18.0 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 13.7 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 14.9 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 250 of524 250


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

257-F01-GST-10-BD

1. General Details:
Floor Area ......................................................... 18.0 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 13.7 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.0 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 251 of524 251


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

258-F01-GST-10-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 15.4 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 1.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 252 of524 252


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

259-F01-GST-10-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 253 of524 253


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

260A-F01-MAIN CORRIDOR

1. General Details:
Floor Area ....................................................... 127.6 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ...................................... User defined
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 60.1 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 75.2 m² Area ................................................................ 146.2 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 254 of524 254


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

260-F01-GST-10-KITCHEN

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 10.7 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 255 of524 255


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

261-F02-GST-02-MBD

1. General Details:
Floor Area ......................................................... 27.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 17.6 2 0 0
SSE 17.6 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

3.2. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 22.1 m² Area .................................................................... 4.7 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 256 of524 256


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

262-F02-GST-02-BD

1. General Details:
Floor Area ......................................................... 18.7 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 14.0 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 257 of524 257


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

263-F02-GST-02-CORRID

1. General Details:
Floor Area ........................................................... 3.1 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 11.1 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 258 of524 258


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

264-F02-GST-02-ENT

1. General Details:
Floor Area ........................................................... 8.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 4.0 m² Area .................................................................... 6.2 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 259 of524 259


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

265-F02-GST-02-LIV

1. General Details:
Floor Area ......................................................... 27.9 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 6.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 21.9 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 260 of524 260


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

266-F02-GST-02-KITCHEN

1. General Details:
Floor Area ........................................................... 7.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 3.4 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 261 of524 261


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

267-F02-ST-02

1. General Details:
Floor Area ......................................................... 34.6 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 12.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 21.9 3 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 22.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 262 of524 262


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

268-F02-GST-01-MBD

1. General Details:
Floor Area ......................................................... 27.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 16.4 2 0 0
SSE 16.4 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

3.2. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 22.1 m² Area .................................................................... 4.7 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 263 of524 263


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

269-F02-GST-01-BD

1. General Details:
Floor Area ......................................................... 18.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 14.0 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 264 of524 264


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

270-F02-GST-01-CORRID

1. General Details:
Floor Area ........................................................... 3.1 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 11.1 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 265 of524 265


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

271-F02-GST-01-LIV

1. General Details:
Floor Area ......................................................... 27.9 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 6.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 21.9 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 266 of524 266


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

272-F02-GST-01-KITCHEN

1. General Details:
Floor Area ........................................................... 7.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 3.4 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 267 of524 267


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

273-F02-GST-01-ENT

1. General Details:
Floor Area ........................................................... 8.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 4.0 m² Area .................................................................... 6.2 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 268 of524 268


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

274-F02-ST-01

1. General Details:
Floor Area ......................................................... 34.6 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 21.9 3 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 22.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 269 of524 269


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

275-F02-GST-03-LIV

1. General Details:
Floor Area ......................................................... 20.6 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 6.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 19.3 2 1 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)
2nd Window Type ........................................ 4MX0.26M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 16.5 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 270 of524 270


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

276-F02-GST-03-KITCHEN

1. General Details:
Floor Area ........................................................... 9.6 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 7.5 1 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.76M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 7.0 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 271 of524 271


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

277-F02-GST-03-ENT

1. General Details:
Floor Area ........................................................... 5.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 3.7 m² Area .................................................................. 12.7 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 272 of524 272


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

278-F02-GST-03-BD

1. General Details:
Floor Area ......................................................... 16.6 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 12.9 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 3.5 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 273 of524 273


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

279-F02-GST-03-CORRIDOR

1. General Details:
Floor Area ........................................................... 3.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 11.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 274 of524 274


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

280-F02-GST-03-MBD

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 16.2 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ......................................... 4MX0.95M(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 28.7 m² Area .................................................................... 4.7 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 275 of524 275


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

281-F02-MAIN CORRIDOR

1. General Details:
Floor Area ......................................................... 65.7 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ...................................... User defined
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 60.1 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 52.5 m² Area ................................................................ 105.0 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 276 of524 276


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

285-GR- IDF

1. General Details:
Floor Area ........................................................... 4.0 m²
Avg. Ceiling Height ............................................. 4.3 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 4.0 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 28.3 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 277 of524 277


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

286 - STAIR -03

1. General Details:
Floor Area ......................................................... 13.3 m²
Avg. Ceiling Height ........................................... 13.1 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 5.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 13.3 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 32.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 278 of524 278


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

287 - STAIR -02

1. General Details:
Floor Area ......................................................... 16.3 m²
Avg. Ceiling Height ........................................... 13.1 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 5.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 16.3 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 32.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 279 of524 279


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

288 - STAIR -01

1. General Details:
Floor Area ......................................................... 14.4 m²
Avg. Ceiling Height ........................................... 13.1 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 5.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 14.4 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 32.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 280 of524 280


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

289 - BSM - GAURD HOUSE

1. General Details:
Floor Area ........................................................... 4.0 m²
Avg. Ceiling Height ............................................. 2.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 12.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(11) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(10)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule .......................................... LIGHTING(11) Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 7.2 0 0 0
ENE 7.2 1 0 0
SSE 7.2 2 0 0
WSW 7.2 1 0 0

3.1. Construction Types for Exposure NNW


Wall Type ................................................ external wall(8)

3.2. Construction Types for Exposure ENE


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

3.3. Construction Types for Exposure SSE


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

3.4. Construction Types for Exposure WSW


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 4.0 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(3)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program vv5.00 Page 281 of524 281


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 4.0 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 282 of524 282


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

289 - GAURD HOUSE

1. General Details:
Floor Area ........................................................... 4.0 m²
Avg. Ceiling Height ............................................. 3.0 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 12.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 7.5 1 2 0
ENE 7.5 0 0 0
SSE 7.5 1 2 0
WSW 7.5 0 0 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
1st Window Shade Type ................... Default Shade Type
2nd Window Type ....................................... window 1 m2
2nd Window Shade Type .................. Default Shade Type

3.2. Construction Types for Exposure ENE


Wall Type .................................................... external wall

3.3. Construction Types for Exposure SSE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
1st Window Shade Type ................... Default Shade Type
2nd Window Type ................................ window (.1) m2(1)
2nd Window Shade Type .................. Default Shade Type

3.4. Construction Types for Exposure WSW


Wall Type .................................................... external wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 4.0 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program vv5.00 Page 283 of524 283


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 4.0 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 284 of524 284


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

290 - BSM - GAURD HOUSE

1. General Details:
Floor Area ........................................................... 4.0 m²
Avg. Ceiling Height ............................................. 2.6 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 12.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(11) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(10)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule .......................................... LIGHTING(11) Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 7.2 0 0 0
ENE 7.2 1 0 0
NNW 7.2 2 0 0
WSW 7.2 1 0 0

3.1. Construction Types for Exposure SSE


Wall Type ................................................ external wall(8)

3.2. Construction Types for Exposure ENE


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

3.3. Construction Types for Exposure NNW


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

3.4. Construction Types for Exposure WSW


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 4.0 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(3)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program vv5.00 Page 285 of524 285


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 4.0 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 286 of524 286


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

291 - GF- GAURD HOUSE

1. General Details:
Floor Area ........................................................... 4.0 m²
Avg. Ceiling Height ............................................. 2.6 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 12.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(11) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(10)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule .......................................... LIGHTING(11) Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 6.8 0 0 0
ENE 6.8 1 0 0
SSE 6.8 2 0 0
WSW 6.8 1 0 0

3.1. Construction Types for Exposure NNW


Wall Type ................................................ external wall(8)

3.2. Construction Types for Exposure ENE


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

3.3. Construction Types for Exposure SSE


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

3.4. Construction Types for Exposure WSW


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 4.0 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(3)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program vv5.00 Page 287 of524 287


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 4.0 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 288 of524 288


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

292 - GF- GAURD HOUSE

1. General Details:
Floor Area ........................................................... 4.0 m²
Avg. Ceiling Height ............................................. 2.6 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 12.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(11) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(10)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule .......................................... LIGHTING(11) Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 6.8 0 0 0
NNW 6.8 1 0 0
ENE 6.8 2 0 0
SSE 6.8 1 0 0

3.1. Construction Types for Exposure WSW


Wall Type ................................................ external wall(8)

3.2. Construction Types for Exposure NNW


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

3.3. Construction Types for Exposure ENE


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

3.4. Construction Types for Exposure SSE


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 4.0 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(3)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program vv5.00 Page 289 of524 289


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 4.0 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 290 of524 290


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

293 - GF- GAURD HOUSE

1. General Details:
Floor Area ........................................................... 4.0 m²
Avg. Ceiling Height ............................................. 2.6 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 12.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(11) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(10)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule .......................................... LIGHTING(11) Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 6.8 0 0 0
NNW 6.8 1 0 0
ENE 6.8 2 0 0
SSE 6.8 1 0 0

3.1. Construction Types for Exposure WSW


Wall Type ................................................ external wall(8)

3.2. Construction Types for Exposure NNW


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

3.3. Construction Types for Exposure ENE


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

3.4. Construction Types for Exposure SSE


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 4.0 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(3)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program vv5.00 Page 291 of524 291


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 4.0 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 292 of524 292


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

294 - GF- GAURD HOUSE

1. General Details:
Floor Area ........................................................... 4.0 m²
Avg. Ceiling Height ............................................. 2.6 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 12.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(11) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(10)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule .......................................... LIGHTING(11) Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 6.8 0 0 0
NNW 6.8 1 0 0
WSW 6.8 2 0 0
SSE 6.8 1 0 0

3.1. Construction Types for Exposure ENE


Wall Type ................................................ external wall(8)

3.2. Construction Types for Exposure NNW


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

3.3. Construction Types for Exposure WSW


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

3.4. Construction Types for Exposure SSE


Wall Type ................................................ external wall(8)
1st Window Type ........................................ 1.2MX1.135M

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 4.0 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(3)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program vv5.00 Page 293 of524 293


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

6. Floors:
Type .............. Floor Above Unconditioned Space
Floor Area ........................................................... 4.0 m²
Total Floor U-Value ......................................... 0.300 W/(m²·K)
Unconditioned Space Max Temp. ..................... 45.2 °C
Ambient at Space Max Temp. ........................... 45.2 °C
Unconditioned Space Min Temp. ...................... 15.0 °C
Ambient at Space Min Temp. .............................. 7.9 °C

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 294 of524 294


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

301-F03-TYP-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 14.8 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 15.8 m² Area .................................................................. 25.4 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 295 of524 295


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

302-F03(03-08)-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.8 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 296 of524 296


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

303A-F03-LIFT'S MACHINE

1. General Details:
Floor Area ......................................................... 10.1 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage .......................................................... 12.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 2400.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 14.7 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 297 of524 297


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

303-F03-STORE

1. General Details:
Floor Area ......................................................... 19.0 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 16.9 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 25.3 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 298 of524 298


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

304-F03(03-08)-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.8 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 299 of524 299


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

305-F03-TYP-IDF

1. General Details:
Floor Area ........................................................... 4.1 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage .......................................................... 12.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 19.5 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 300 of524 300


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

306-F03(03-08)-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.8 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 301 of524 301


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

307-F03(03-08)-GUEST RM

1. General Details:
Floor Area ......................................................... 22.3 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.8 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 302 of524 302


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

308-F03-TYP-LIFT LOBBY

1. General Details:
Floor Area ......................................................... 26.7 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 31.1 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 64.0 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 303 of524 303


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

309-F03(03-08)-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.8 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 304 of524 304


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

310-F03(03-08)-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.8 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 305 of524 305


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

311-F03(03-08)-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.8 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 306 of524 306


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

312-F03-TYP-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 14.8 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 307 of524 307


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

313-F03(03-08)-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.8 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 308 of524 308


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

314-F03-TYP-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 14.8 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 309 of524 309


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

315-F03(03-08)-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.8 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 310 of524 310


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

316-F03-TYP-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 14.8 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 311 of524 311


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

317-F03(03-08)-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.8 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 312 of524 312


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

318-F03-TYP-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 14.8 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 313 of524 313


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

319-F03(03-08)-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.8 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 314 of524 314


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

320-F03-TYP-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 14.8 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 15.8 m² Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 315 of524 315


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

321-F03(03-08)-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.8 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 316 of524 316


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

322-F03(03-08)-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.8 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 317 of524 317


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

323-F03(03-08)-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.8 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 318 of524 318


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

324-F03(03-08)-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.8 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 319 of524 319


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

325-F03(03-08)-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.8 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 320 of524 320


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

327-F03-TYP-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 14.8 2 0 0
WSW 28.9 0 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

3.2. Construction Types for Exposure WSW


Wall Type ............................... Default Wall Assembly(7)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 321 of524 321


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

328-F03-TYP-SUITE-BD RM

1. General Details:
Floor Area ......................................................... 20.5 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.8 4 0 0
WSW 18.0 0 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ........................................... 3.5MX1M(6)

3.2. Construction Types for Exposure WSW


Wall Type ............................... Default Wall Assembly(7)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 12.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 322 of524 322


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

329-F03-TYP-ELEC RM

1. General Details:
Floor Area ......................................................... 14.5 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage .......................................................... 12.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 10.4 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 323 of524 323


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

330-F03-TYP-IDF

1. General Details:
Floor Area ........................................................... 8.0 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 12.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 12.6 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 324 of524 324


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

331-F03-TYP-HK

1. General Details:
Floor Area ......................................................... 28.9 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 5.3 m² Area .................................................................. 25.8 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 325 of524 325


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

332-F03-TYP-SERV CORR

1. General Details:
Floor Area ......................................................... 38.2 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 24.6 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 326 of524 326


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

333-F03-TYP-SERV LOBBY

1. General Details:
Floor Area ......................................................... 20.2 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 53.0 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 327 of524 327


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

334-F03-TYP-CORRIDOR

1. General Details:
Floor Area ....................................................... 168.5 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 7.7 2 0 0
WSW 7.7 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

3.2. Construction Types for Exposure WSW


Wall Type ............................... Default Wall Assembly(7)
1st Window Type ....................................... 3MX1.025M(5)
1st Window Shade Type .............. Default Shade Type(6)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area ................................................................ 165.4 m² Area ................................................................ 107.1 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 328 of524 328


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

335A-F03-TYP-SUITE BD CO

1. General Details:
Floor Area ........................................................... 5.0 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 6.1 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.2 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 329 of524 329


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

335-F03-TYP-SUITE-BD RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 16.4 0 4 0
ENE 21.9 4 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
2nd Window Type ...................................... 3MX1.025M(5)

3.2. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ...................................... 3.5MX0.95M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 330 of524 330


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

336-F03-TYP-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 14.8 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 331 of524 331


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

337A-F03(03-08)SUIT.BD C

1. General Details:
Floor Area ........................................................... 5.0 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 6.1 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.2 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 332 of524 332


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

337-F03(03-08)SUITE-BD.R

1. General Details:
Floor Area ......................................................... 23.5 m²
Avg. Ceiling Height ............................................. 3.5 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.0 0 4 0
ENE 20.0 4 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
2nd Window Type ...................................... 3MX1.025M(5)

3.2. Construction Types for Exposure ENE


Wall Type ............................... Default Wall Assembly(7)
1st Window Type ...................................... 3.5MX0.95M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 333 of524 333


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

338-F03(03-08)-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.8 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 334 of524 334


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

339-F03-TYP-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 14.8 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 15.8 m² Area .................................................................. 25.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 335 of524 335


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

340-F03-TYP-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 14.7 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 336 of524 336


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

341-F03(03-08)-SUITE-LIV

1. General Details:
Floor Area ......................................................... 26.5 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.8 4 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ........................................... 3.5MX1M(6)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.3 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 337 of524 337


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

342-F03(03-08)-SUITE-LIV

1. General Details:
Floor Area ......................................................... 27.7 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 14.9 4 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 16.6 m² Area .................................................................... 1.1 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 338 of524 338


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

343-F03-TYP-SUITE-LIV RM

1. General Details:
Floor Area ......................................................... 27.7 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 14.9 4 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 16.6 m² Area .................................................................... 1.1 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 339 of524 339


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

351-F03-(03-06)GST-01-EN

1. General Details:
Floor Area ........................................................... 4.3 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 340 of524 340


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

352-F03-(03-06)GST-01-LI

1. General Details:
Floor Area ......................................................... 27.7 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 6.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 22.3 3 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 341 of524 341


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

353-F03-(03-06)GST-01-KI

1. General Details:
Floor Area ........................................................... 5.3 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 9.5 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 342 of524 342


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

354-F03-(03-06)GST-01-Co

1. General Details:
Floor Area ........................................................... 4.3 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 12.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 343 of524 343


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

355-F03-(03-06)GST-01-BD

1. General Details:
Floor Area ......................................................... 16.4 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 20.1 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 344 of524 344


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

356-F03-(03-06)GST-01-MB

1. General Details:
Floor Area ......................................................... 26.0 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 15.4 2 0 0
SSE 19.5 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

3.2. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 15.4 m² Area .................................................................... 3.8 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 345 of524 345


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

357-F03-(03-06)GST-02-EN

1. General Details:
Floor Area ........................................................... 4.3 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 346 of524 346


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

358-F03-(03-06)GST-02-LV

1. General Details:
Floor Area ......................................................... 27.7 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 6.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 22.3 3 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 347 of524 347


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

359-F03-(03-06)GST-02-KT

1. General Details:
Floor Area ......................................................... 10.5 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 10.4 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 348 of524 348


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

360-F03-(03-06)GST-02-CO

1. General Details:
Floor Area ........................................................... 4.3 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 9.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 349 of524 349


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

361-F03-(03-06)GST-02-BD

1. General Details:
Floor Area ......................................................... 18.4 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 14.2 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 350 of524 350


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

362-F03-(03-06)GST-02-MB

1. General Details:
Floor Area ......................................................... 26.0 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 15.4 2 0 0
SSE 19.5 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

3.2. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 15.4 m² Area .................................................................... 3.8 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 351 of524 351


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

363-F03-(03-08)-ST-01

1. General Details:
Floor Area ......................................................... 34.6 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 22.3 3 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 22.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 352 of524 352


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

364-F03-(03-08)-ST-02

1. General Details:
Floor Area ......................................................... 34.6 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 22.4 3 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 22.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 353 of524 353


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

365-F03-(03-08)-ST-03

1. General Details:
Floor Area ......................................................... 34.6 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 22.4 3 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 22.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 354 of524 354


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

366-F03-(03-08GST-03-ENT

1. General Details:
Floor Area ........................................................... 5.8 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 5.0 m² Area .................................................................. 10.9 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 355 of524 355


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

367-F03-(03-08)GST-03-LI

1. General Details:
Floor Area ......................................................... 20.7 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 6.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 19.7 3 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 16.5 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 356 of524 356


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

368-F03-(03-08)GST-03-KI

1. General Details:
Floor Area ........................................................... 9.9 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 7.7 1 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 8.1 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 357 of524 357


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

369-F03-(03-08)GST-03-CO

1. General Details:
Floor Area ........................................................... 4.3 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.5 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 358 of524 358


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

370-F03-(03-08)GST-03-BD

1. General Details:
Floor Area ......................................................... 16.6 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 13.2 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 3.5 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 359 of524 359


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

371-F03(03-08)GST-03-MBD

1. General Details:
Floor Area ......................................................... 22.1 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 16.5 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 18.8 m² Area .................................................................... 3.5 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 360 of524 360


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

372-F03-(03-08)-ST-04

1. General Details:
Floor Area ......................................................... 38.6 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 30.3 4 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 23.5 m² Area .................................................................. 31.6 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 361 of524 361


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

373-F03(03-08)GST-04-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 5.8 m² Area .................................................................... 1.0 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 362 of524 362


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

374-F03(03-08)GST-04-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 15.8 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 1.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 363 of524 363


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

375-F03(03-08)GST-04-KIT

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 5.2 m² Area .................................................................... 2.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 364 of524 364


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

376-F03(03-08)-GST-04-BD

1. General Details:
Floor Area ......................................................... 18.0 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 14.0 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.7 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 365 of524 365


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

377-F03(03-08)GST-05-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 366 of524 366


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

378-F03(03-08)GST-05-KIT

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 10.7 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 367 of524 367


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

379-F03(03-08)GST-05-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 15.8 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 1.6 m² Area .................................................................... 2.5 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 368 of524 368


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

380-F03(03-08)-GST-05-BD

1. General Details:
Floor Area ......................................................... 18.0 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 14.0 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.7 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 369 of524 369


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

381-F03(03-08)GST-06-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 370 of524 370


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

382-F03(03-08)GST-06-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 15.8 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 1.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 371 of524 371


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

383-F03(03-08)GST-06-KIT

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 5.2 m² Area .................................................................... 2.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 372 of524 372


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

384-F03(03-08)-GST-06-BD

1. General Details:
Floor Area ......................................................... 18.0 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 14.0 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.7 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 373 of524 373


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

385-F03(03-08)GST-07-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 374 of524 374


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

386-F03(03-08)GST-07-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 15.8 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 1.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 375 of524 375


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

387-F03(03-08)GST-07-KIT

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 5.2 m² Area .................................................................... 2.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 376 of524 376


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

388-F03(03-08)-GST-07-BD

1. General Details:
Floor Area ......................................................... 18.0 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 14.0 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.7 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 377 of524 377


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

389-F03(03-08)GST-08-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 378 of524 378


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

390-F03(03-08)GST-08-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 15.8 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 1.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 379 of524 379


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

391-F03(03-08)GST-08-KIT

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 5.2 m² Area .................................................................... 2.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 380 of524 380


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

392-F03(03-08)-GST-08-BD

1. General Details:
Floor Area ......................................................... 18.0 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 14.0 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.7 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 381 of524 381


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

393-F03(03-08)GST-09-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 382 of524 382


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

394-F03(03-08)GST-09-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 15.8 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 1.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 383 of524 383


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

395-F03(03-08)GST-09-KIT

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 5.2 m² Area .................................................................... 2.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 384 of524 384


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

396-F03(03-08)-GST-09-BD

1. General Details:
Floor Area ......................................................... 18.0 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 15.8 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.7 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 385 of524 385


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

397-F03(03-08)GST-10-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 386 of524 386


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

398-F03(03-08)GST-10-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 15.8 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 1.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 387 of524 387


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

399-F03(03-08)GST-10-KIT

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 10.7 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 388 of524 388


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

400-F03(03-08)-GST-10-BD

1. General Details:
Floor Area ......................................................... 18.0 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 14.0 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.7 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 389 of524 389


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

401-F03(03-08)GST-11-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 390 of524 390


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

402-F03(03-08)GST-11-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 15.8 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 1.8 m² Area .................................................................... 3.7 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 391 of524 391


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

403-F03(03-08)GST-11-KIT

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 10.6 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 392 of524 392


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

404-F03(03-08)-GST-11-BD

1. General Details:
Floor Area ......................................................... 18.0 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 15.8 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.7 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 393 of524 393


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

405-F03(03-08)-MAIN CORR

1. General Details:
Floor Area ....................................................... 148.5 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ...................................... User defined
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 60.1 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 7.7 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area ................................................................ 124.0 m² Area ................................................................ 196.6 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 394 of524 394


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

408-F04-(04-09)FAMILY RM

1. General Details:
Floor Area ......................................................... 27.4 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 19.2 2 0 0

3.1. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 18.0 m² Area .................................................................. 45.4 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 395 of524 395


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

601-F06-GST-02-MBD

1. General Details:
Floor Area ......................................................... 22.1 m²
Avg. Ceiling Height ............................................. 3.0 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 15.8 2 0 0
SSE 20.0 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

3.2. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 22.1 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 20.7 m² Area .................................................................... 8.2 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 396 of524 396


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

602-F06-GST-01-MBD

1. General Details:
Floor Area ......................................................... 22.1 m²
Avg. Ceiling Height ............................................. 3.0 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 15.8 2 0 0
SSE 20.0 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type .................................... 4.7MX0.985M(5)

3.2. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 22.1 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 20.7 m² Area .................................................................... 8.2 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 397 of524 397


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

701-F07-GST-01-BD

1. General Details:
Floor Area ......................................................... 23.0 m²
Avg. Ceiling Height ............................................. 3.1 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 13.9 2 0 0
SSE 21.0 0 0 2

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

3.2. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
Door Type ..................................................... 3M*0.75M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.0 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 10.9 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 398 of524 398


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

702-F07-GST-01-BD

1. General Details:
Floor Area ......................................................... 23.0 m²
Avg. Ceiling Height ............................................. 3.1 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 13.9 2 0 0
SSE 21.4 0 0 2

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

3.2. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
Door Type ..................................................... 3M*0.75M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.0 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 10.9 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 399 of524 399


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

801-F08-ST-01

1. General Details:
Floor Area ......................................................... 33.0 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 21.6 3 0 0
SSE 20.4 0 0 2

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ........................................... 3MX0.9M(5)

3.2. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
Door Type ..................................................... 3M*0.75M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 33.0 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 14.2 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 400 of524 400


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

802-F08-ST-02

1. General Details:
Floor Area ......................................................... 33.0 m²
Avg. Ceiling Height ............................................. 3.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 21.6 2 0 0
SSE 20.4 0 0 2

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ........................................... 3MX0.9M(5)

3.2. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
Door Type ..................................................... 3M*0.75M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 33.0 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 14.2 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 401 of524 401


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

803 -2ND- DINING AREA

1. General Details:
Floor Area ....................................................... 558.0 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ........................................ 1065.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ...................................................... 152.0 People
Wattage .......................................................... 11.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .......................................................... 15.00 W/m² Sensible ........................................................... 5665 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent .............................................................. 1990 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 109.4 88 2 0
NNW 184.5 64 8 0

3.1. Construction Types for Exposure SSE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

3.2. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 57.1 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 402 of524 402


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

803*-2ND- DININGshow kit

1. General Details:
Floor Area ......................................................... 38.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 8.0 People
Wattage .......................................................... 11.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .......................................................... 15.00 W/m² Sensible ......................................................... 16797 W
Schedule ................................................ LIGHTING Schedule ............................................. EQUIPMENT
Latent .............................................................. 3960 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 403 of524 403


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

804 -2ND- kitchen

1. General Details:
Floor Area ......................................................... 94.6 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .......................................... 285.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 19.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ............................................ LIGHTING(2) Latent ............................................................... 79.1 W/person
Schedule ............................................... PEOPLE(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ......................................................... 31668 W
Schedule ............................................ LIGHTING(2) Schedule ............................................. EQUIPMENT
Latent ............................................................ 15006 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 39.4 3 4 0
SSE 29.3 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

3.2. Construction Types for Exposure SSE


Wall Type .................................................... external wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 52.7 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................... RRoof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 21.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 404 of524 404


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

805 -2ND- KIT. DRY STORE

1. General Details:
Floor Area ........................................................... 7.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 25.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ............................................ LIGHTING(2) Latent ............................................................... 79.1 W/person
Schedule ............................................... PEOPLE(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ............................................ LIGHTING(2) Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 6.3 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 405 of524 405


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

806 -2ND- WASHING AREA

1. General Details:
Floor Area ......................................................... 19.1 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 ............................................ 60.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ............................................ LIGHTING(2) Latent ............................................................... 79.1 W/person
Schedule ............................................... PEOPLE(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ........................................................... 3580 W
Schedule ............................................ LIGHTING(2) Schedule ............................................. EQUIPMENT
Latent .............................................................. 2369 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 27.3 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 406 of524 406


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

807-2ND- M.Showers

1. General Details:
Floor Area ......................................................... 60.0 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 5.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ............................................ LIGHTING(2) Latent ............................................................... 60.1 W/person
Schedule ............................................... PEOPLE(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 58.3 m² Area .................................................................. 21.0 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 407 of524 407


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

808-2ND- F.Showers

1. General Details:
Floor Area ......................................................... 60.0 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 5.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ............................................ LIGHTING(2) Latent ............................................................... 60.1 W/person
Schedule ............................................... PEOPLE(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 58.3 m² Area .................................................................. 21.0 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 408 of524 408


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

809-2ND-M.Wellnesscenter

1. General Details:
Floor Area ......................................................... 72.9 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 18.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ............................................. Athletics
Ballast Multiplier ............................................... 1.00 Sensible .......................................................... 208.1 W/person
Schedule ............................................ LIGHTING(2) Latent ............................................................. 319.4 W/person
Schedule ............................................... PEOPLE(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 40.5 34 3 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 29.4 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 19.1 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 409 of524 409


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

810-2ND-F.Wellnesscenter

1. General Details:
Floor Area ......................................................... 72.9 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 18.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ............................................. Athletics
Ballast Multiplier ............................................... 1.00 Sensible .......................................................... 208.1 W/person
Schedule ............................................ LIGHTING(2) Latent ............................................................. 319.4 W/person
Schedule ............................................... PEOPLE(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ............................................................ 0.00 W/m²
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 40.5 34 3 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 31.3 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 33.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 19.1 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 410 of524 410


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

811-2ND- F.TOILET

1. General Details:
Floor Area ........................................................... 8.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ............................................ LIGHTING(2) Latent ............................................................... 60.1 W/person
Schedule ............................................... PEOPLE(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 12.6 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ............................................... 30.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 20.4 m² Area .................................................................... 8.9 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 411 of524 411


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

812-2ND- M.TOILET

1. General Details:
Floor Area ........................................................... 8.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ............................................ LIGHTING(2) Latent ............................................................... 60.1 W/person
Schedule ............................................... PEOPLE(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 12.6 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ............................................... 30.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 20.4 m² Area .................................................................... 8.9 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 412 of524 412


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

813-2ND- kids area

1. General Details:
Floor Area ......................................................... 59.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 15.0 People
Wattage .......................................................... 10.50 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ............................................ LIGHTING(2) Latent ............................................................... 60.1 W/person
Schedule ............................................... PEOPLE(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 37.0 14 8 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 12.4 m² Area .................................................................. 16.6 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 13.9 °C Uncondit. Space Min Temp ............................... 19.1 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 413 of524 413


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

814 - 2ND- STORE

1. General Details:
Floor Area ......................................................... 40.9 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 36.0 0 0 0
SSE 11.3 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type .................................................... external wall

3.2. Construction Types for Exposure SSE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 14.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 414 of524 414


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

815 -2ND - ELEC

1. General Details:
Floor Area ......................................................... 14.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 415 of524 415


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

816 -2ND- IDF

1. General Details:
Floor Area ........................................................... 7.9 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 14.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 416 of524 416


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

817- 2ND - HK

1. General Details:
Floor Area ......................................................... 12.8 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 79.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ............................................................. 600 W
Schedule ........................................................ None Schedule ............................................. EQUIPMENT
Latent .............................................................. 1000 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 5.9 0 0 0

3.1. Construction Types for Exposure SSE


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 10.5 m² Area .................................................................. 10.5 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 417 of524 417


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

818 - 2ND - LIFTS LOBBY

1. General Details:
Floor Area ......................................................... 16.1 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 48.3 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 418 of524 418


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

819 - 2ND - SER. CORR.-2

1. General Details:
Floor Area ......................................................... 41.1 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 34.4 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 419 of524 419


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

820 - 2ND - SER. CORR.-1

1. General Details:
Floor Area ........................................................... 8.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 420 of524 420


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

821 - 2ND - MEETING 1

1. General Details:
Floor Area ......................................................... 83.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 32.0 People
Wattage ............................................................ 9.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 46.9 15 0 0
SSE 36.9 32 2 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2

3.2. Construction Types for Exposure SSE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 421 of524 421


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

822 - 2ND - MEETING 2

1. General Details:
Floor Area ......................................................... 65.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 25.0 People
Wattage ............................................................ 9.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 36.9 6 1 0
NNW 36.9 32 2 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

3.2. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 422 of524 422


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

823 - 2ND - PLAYFUL MEET

1. General Details:
Floor Area ......................................................... 58.5 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 10.0 People
Wattage ............................................................ 9.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 36.9 14 4 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 423 of524 423


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

824 - 2ND -LOUNGE MEET

1. General Details:
Floor Area ......................................................... 62.9 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 17.0 People
Wattage ............................................................ 8.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 36.9 12 2 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 424 of524 424


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

825 - 2ND - LOUNGE

1. General Details:
Floor Area ....................................................... 106.7 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ........................................................ 10.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 36.9 15 4 0
SSE 32.8 14 9 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

3.2. Construction Types for Exposure SSE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 68.7 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 425 of524 425


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

826 - 2ND - MEET CORR.

1. General Details:
Floor Area ......................................................... 43.8 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 10.1 m² Area .................................................................. 27.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 426 of524 426


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

827 - 2ND - RLIFTS LOOBY

1. General Details:
Floor Area ......................................................... 40.8 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 81.1 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 427 of524 427


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

828 - 2ND -LLIFTS LOBBY

1. General Details:
Floor Area ......................................................... 42.3 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 68.9 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 428 of524 428


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

829 - 2ND -CLIFTS LOBBY

1. General Details:
Floor Area ......................................................... 41.1 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 64.4 51 9 0
WSW 11.4 8 8 0
ENE 11.4 8 8 0

3.1. Construction Types for Exposure SSE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

3.2. Construction Types for Exposure WSW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

3.3. Construction Types for Exposure ENE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 34.0 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 429 of524 429


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

830-2ND- AHU

1. General Details:
Floor Area ....................................................... 120.9 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 1500.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 54.9 32 1 0
WSW 33.8 0 0 0

3.1. Construction Types for Exposure NNW


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
1st Window Shade Type ................... Default Shade Type
2nd Window Type .................................... window (.1) m2
2nd Window Shade Type .................. Default Shade Type

3.2. Construction Types for Exposure WSW


Wall Type .................................................... external wall

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 35.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 430 of524 430


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

831 - 2ND - SER. CORR-4

1. General Details:
Floor Area ......................................................... 82.7 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 25.6 12 6 0

3.1. Construction Types for Exposure ENE


Wall Type .................................................... external wall
1st Window Type ........................................ window 1 m2
2nd Window Type .................................... window (.1) m2

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 95.3 m² Area .................................................................. 29.4 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 431 of524 431


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

832-2ND- M.TOILET

1. General Details:
Floor Area ........................................................... 9.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ............................................ LIGHTING(2) Latent ............................................................... 60.1 W/person
Schedule ............................................... PEOPLE(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 9.5 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type ................................................ external wall(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 18.5 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 432 of524 432


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

833-2ND- F.TOILET

1. General Details:
Floor Area ........................................................... 9.8 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ............................................ LIGHTING(2) Latent ............................................................... 60.1 W/person
Schedule ............................................... PEOPLE(1)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 10.0 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type ................................................ external wall(1)

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs only when the fan is off.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 37.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 433 of524 433


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

834 - 2nd - M.TOILET

1. General Details:
Floor Area ........................................................... 8.4 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 26.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 434 of524 434


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

835 - 2nd - F.TOILET

1. General Details:
Floor Area ........................................................... 7.2 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ................................................ LIGHTING Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 21.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 435 of524 435


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

836 -2ND- IDF

1. General Details:
Floor Area ........................................................... 4.1 m²
Avg. Ceiling Height ............................................. 4.2 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule ................................................ LIGHTING Latent ............................................................... 60.1 W/person
Schedule ................................................... PEOPLE

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ............................................ EQUIPMENT

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:
(No Roof or Skylight data).

5. Infiltration:
Design Cooling ................................................. 0.00 L/s
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 28.2 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 436 of524 436


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

902-F09-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.6 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 437 of524 437


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

904-F09-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.6 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 438 of524 438


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

906-F09-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.6 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 439 of524 439


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

907-F09-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.6 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 440 of524 440


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

909-F09-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.6 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 441 of524 441


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

910-F09-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.6 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 442 of524 442


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

911-F09-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.6 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 443 of524 443


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

913-F09-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.6 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 444 of524 444


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

915-F09-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.6 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 445 of524 445


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

917-F09-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.6 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 446 of524 446


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

919-F09-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.6 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 447 of524 447


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

921-F09-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.6 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 448 of524 448


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

922-F09-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.6 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 449 of524 449


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

923-F09-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.6 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 450 of524 450


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

924-F09-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.6 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 451 of524 451


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

925-F09-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.6 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 452 of524 452


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

937A-F09-SUITE.BD CORRID

1. General Details:
Floor Area ........................................................... 5.0 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 6.5 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 5.0 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.2 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 453 of524 453


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

937-F09-SUITE-BD

1. General Details:
Floor Area ......................................................... 23.5 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 17.3 0 4 0
ENE 23.0 4 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
2nd Window Type ...................................... 3MX1.025M(5)

3.2. Construction Types for Exposure ENE


Wall Type ............................... Default Wall Assembly(7)
1st Window Type ...................................... 3.5MX0.95M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.5 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 454 of524 454


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

938-F09-GUEST RM

1. General Details:
Floor Area ......................................................... 23.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.6 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 23.8 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 455 of524 455


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

941-F09-SUITE-LIV

1. General Details:
Floor Area ......................................................... 26.5 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 16.6 4 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ........................................... 3.5MX1M(6)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 26.5 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 15.3 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 456 of524 456


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

942-F09-SUITE-LIV

1. General Details:
Floor Area ......................................................... 27.7 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(22) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(21)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(27)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.7 4 0 0

3.1. Construction Types for Exposure NNW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 27.7 0 0

4.1. Construction Types for Exposure H


Roof Type ................................................................. Roof

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 16.6 m² Area .................................................................... 1.1 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 457 of524 457


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

963-F09-ST-02

1. General Details:
Floor Area ......................................................... 35.0 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 21.0 3 0 0
SSE 27.6 0 0 2

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

3.2. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
Door Type ..................................................... 3M*0.75M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 35.0 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 16.1 m² Area .................................................................... 4.5 m²
U-Value .......................................................... 2.100 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 458 of524 458


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

964-F09-ST-01

1. General Details:
Floor Area ......................................................... 35.0 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 21.0 2 0 0
SSE 27.6 0 0 2

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

3.2. Construction Types for Exposure SSE


Wall Type ..................................... EXTERNAL WALL(20)
Door Type ..................................................... 3M*0.75M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 35.0 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 16.1 m² Area .................................................................... 4.5 m²
U-Value .......................................................... 2.100 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 459 of524 459


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

965-F09-ST-03

1. General Details:
Floor Area ......................................................... 31.8 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 21.5 3 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 31.8 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 20.5 m² Area .................................................................... 2.8 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 460 of524 460


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

966-F09-GST-03-ENT

1. General Details:
Floor Area ........................................................... 5.9 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 5.9 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 3.2 m² Area .................................................................. 11.2 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 461 of524 461


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

967-F09-GST-03-LIV

1. General Details:
Floor Area ......................................................... 21.3 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 6.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 19.4 3 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 21.3 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 16.8 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 462 of524 462


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

968-F09-GST-03-KITCHE

1. General Details:
Floor Area ........................................................... 9.7 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 7.0 1 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 9.7 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 7.9 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 463 of524 463


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

970-F09-GST-03-BD

1. General Details:
Floor Area ......................................................... 16.6 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 12.7 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 16.6 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 3.2 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 464 of524 464


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

971-F09-GST-03-MBD

1. General Details:
Floor Area ......................................................... 22.4 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 16.0 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 22.4 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 22.5 m² Area .................................................................... 3.6 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 465 of524 465


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

972-F09-ST-04

1. General Details:
Floor Area ......................................................... 38.7 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 29.2 4 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 38.7 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................. 17.5 m² Area .................................................................. 31.8 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 466 of524 466


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

973-F09-GST-04-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 2.7 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 6.3 m² Area .................................................................... 1.3 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 467 of524 467


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

974-F09-GST-04-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 15.0 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 21.4 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 2.2 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 468 of524 468


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

975-F09-GST-04-KITCHE

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 5.1 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 5.1 m² Area .................................................................... 5.4 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 469 of524 469


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

976-F09-GST-04-BD

1. General Details:
Floor Area ......................................................... 18.3 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 13.6 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.3 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 11.8 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 470 of524 470


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

977-F09-GST-05-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 2.7 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 6.0 m² Area .................................................................... 1.0 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 471 of524 471


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

978-F09-GST-05-KITCHE

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 5.1 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 10.4 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 472 of524 472


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

979-F09-GST-05-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 15.4 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 21.4 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 1.6 m² Area .................................................................... 2.6 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 473 of524 473


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

980-F09-GST-05-BD

1. General Details:
Floor Area ......................................................... 18.3 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 13.9 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.3 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.9 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 474 of524 474


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

981-F09-GST-06-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 2.7 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 6.0 m² Area .................................................................... 1.0 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 475 of524 475


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

982-F09-GST-06-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 15.0 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 21.4 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 1.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 476 of524 476


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

983-F09-GST-06-KITCHE

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 5.1 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 5.4 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 477 of524 477


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

984-F09-GST-06-BD

1. General Details:
Floor Area ......................................................... 18.3 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 13.6 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.3 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.8 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 478 of524 478


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

985-F09-GST-07-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 2.7 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 6.0 m² Area .................................................................... 1.4 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 479 of524 479


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

986-F09-GST-07-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 15.1 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 21.4 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 1.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 480 of524 480


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

987-F09-GST-07-KITCHE

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 5.1 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 5.3 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 481 of524 481


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

988-F09-GST-07-BD

1. General Details:
Floor Area ......................................................... 18.4 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 13.9 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.4 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.9 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 482 of524 482


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

989-F09-GST-08-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 2.7 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 6.0 m² Area .................................................................... 1.4 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 483 of524 483


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

990-F09-GST-08-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 15.0 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 21.4 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 1.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 484 of524 484


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

991-F09-GST-08-KITCHE

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 5.1 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 5.4 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 485 of524 485


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

992-F09-GST-08-BD

1. General Details:
Floor Area ......................................................... 18.3 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 13.9 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.3 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.7 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 486 of524 486


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

993-F09-GST-09-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 2.7 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 6.0 m² Area .................................................................... 1.4 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 487 of524 487


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

994-F09-GST-09-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 15.1 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 21.4 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 1.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 488 of524 488


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

995-F09-GST-09-KITCHE

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 5.1 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................... 5.3 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 489 of524 489


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

996-F09-GST-09-BD

1. General Details:
Floor Area ......................................................... 18.3 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 13.9 2 0 0

3.1. Construction Types for Exposure ENE


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.3 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 13.7 m²
U-Value .......................................................... 2.100 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 490 of524 490


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

997-F09-GST-10-ENT

1. General Details:
Floor Area ........................................................... 2.7 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 0.0 Person
Wattage ............................................................ 3.80 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ......................................................... None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 2.7 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition Partition Type .................................... Wall Partition
Area .................................................................... 6.0 m² Area .................................................................... 1.4 m²
U-Value .......................................................... 2.839 W/(m²·K) U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 491 of524 491


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

998-F09-GST-10-LIV

1. General Details:
Floor Area ......................................................... 21.4 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage .......................................................... 16.00 W/m² Activity Level ................................... Seated at Rest
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 67.4 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 35.2 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 300.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 15.1 2 0 0

3.1. Construction Types for Exposure WSW


Wall Type ..................................... EXTERNAL WALL(20)
1st Window Type ....................................... 3MX1.025M(5)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 21.4 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 1.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 492 of524 492


Space Input Data
KFUPM LOAD CALCULATION 100% DD 12/18/2019
KA 09:38AM

999-F09-GST-10-KITCHEN

1. General Details:
Floor Area ........................................................... 5.1 m²
Avg. Ceiling Height ............................................. 3.9 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(23) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(22)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(28)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 5.1 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + RSI-2.5 Bd + 102mm LW Concret(6)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 10.7 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 23.9 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 493 of524 493


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R01- DINING AREA

1. General Details:
Floor Area ....................................................... 270.1 m²
Avg. Ceiling Height ............................................. 5.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy ...................................................... 150.0 People
Wattage .......................................................... 11.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage .......................................................... 15.00 W/m² Sensible ........................................................... 2166 W
Schedule .......................................... LIGHTING(21) Schedule ............................................. EQUIPMENT
Latent ................................................................ 780 W
Schedule ............................................. EQUIPMENT
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 160.8 28 0 0
NNW 312.9 25 0 0

3.1. Construction Types for Exposure SSE


Wall Type .............................................. external wall(19)
1st Window Type .................................. 5.35MX1.025M(4)

3.2. Construction Types for Exposure NNW


Wall Type .............................................. external wall(19)
1st Window Type .................................. 5.35MX1.025M(4)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 270.1 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 87.3 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 1 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R02- ELEC

1. General Details:
Floor Area ......................................................... 14.8 m²
Avg. Ceiling Height ............................................. 5.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(30)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 14.8 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 17.7 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 2 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R03- IDF

1. General Details:
Floor Area ........................................................... 7.9 m²
Avg. Ceiling Height ............................................. 5.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ...................................... EQUIPMENT(30)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 7.9 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 17.1 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 3 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R04- HK

1. General Details:
Floor Area ......................................................... 14.9 m²
Avg. Ceiling Height ............................................. 5.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 14.9 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 27.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 4 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R05-AHU

1. General Details:
Floor Area ......................................................... 97.6 m²
Avg. Ceiling Height ............................................. 5.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 1000.0 Watts
Schedule ...................................... EQUIPMENT(26)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 36.9 5 1 0
WSW 91.3 1 0 0
SSE 30.5 2 0 0

3.1. Construction Types for Exposure NNW


Wall Type .............................................. external wall(19)
1st Window Type .................................. 5.35MX1.025M(4)
2nd Window Type ................................. 5.35MX0.925M(4)

3.2. Construction Types for Exposure WSW


Wall Type .............................................. external wall(19)
1st Window Type ...................................... 4.45MX1.8M(4)

3.3. Construction Types for Exposure SSE


Wall Type .............................................. external wall(19)
1st Window Type .................................... 3.8MX1.025M(4)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 97.6 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: Ambient at Space Min Temp ............................... 7.0 °C
Partition Type ................................... Wall Partition
Area .................................................................. 24.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C

Hourly Analysis Program vv5.00 Page 5 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

7.2. 2nd Partition Details: (No partition data).

Hourly Analysis Program vv5.00 Page 6 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R06-CORRIDOR

1. General Details:
Floor Area ......................................................... 29.8 m²
Avg. Ceiling Height ............................................. 5.3 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 29.8 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 39.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 7 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R07-CORRIDOR

1. General Details:
Floor Area ......................................................... 17.3 m²
Avg. Ceiling Height ............................................. 3.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 8.0 0 0 0

3.1. Construction Types for Exposure SSE


Wall Type .............................................. external wall(18)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.3 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
(No partition data). Partition Type .................................... Wall Partition
Area .................................................................. 28.9 m²
U-Value ........................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 8 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R08 - M.TOILET

1. General Details:
Floor Area ......................................................... 18.0 m²
Avg. Ceiling Height ............................................. 3.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule .......................................... LIGHTING(21) Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 16.2 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type .............................................. external wall(19)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 18.0 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.30 L/(s·m²)
Energy Analysis ................................................ 0.30 L/(s·m²)
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 9 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R09 - F.TOILET

1. General Details:
Floor Area ......................................................... 17.0 m²
Avg. Ceiling Height ............................................. 3.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 7.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule .......................................... LIGHTING(21) Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
WSW 15.6 0 0 0
SSE 17.4 0 0 0

3.1. Construction Types for Exposure WSW


Wall Type .............................................. external wall(19)

3.2. Construction Types for Exposure SSE


Wall Type .............................................. external wall(19)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.0 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.30 L/(s·m²)
Energy Analysis ................................................ 0.30 L/(s·m²)
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 7.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 29.0 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 10 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R10-SATTALITE KIT

1. General Details:
Floor Area ......................................................... 31.3 m²
Avg. Ceiling Height ............................................. 3.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 8.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ......................................................... 15700 W
Schedule .......................................... LIGHTING(21) Schedule ...................................... EQUIPMENT(30)
Latent .............................................................. 4270 W
Schedule ...................................... EQUIPMENT(30)
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ...................................... EQUIPMENT(30)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 20.0 0 0 0
SSE 25.2 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .............................................. external wall(19)

3.2. Construction Types for Exposure SSE


Wall Type .............................................. external wall(19)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 31.3 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.30 L/(s·m²)
Energy Analysis ................................................ 0.30 L/(s·m²)
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 11 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R11- SERVICE LOB

1. General Details:
Floor Area ......................................................... 16.6 m²
Avg. Ceiling Height ............................................. 5.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 16.6 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 60.2 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 12 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R12- LIFT'S LOBBY

1. General Details:
Floor Area ......................................................... 33.0 m²
Avg. Ceiling Height ............................................. 5.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 15.5 2 0 0
NNW 34.5 6 0 0

3.1. Construction Types for Exposure SSE


Wall Type .............................................. external wall(19)
1st Window Type .................................. 5.35MX1.025M(4)

3.2. Construction Types for Exposure NNW


Wall Type .............................................. external wall(19)
1st Window Type .................................. 5.35MX1.025M(4)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 33.0 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 99.3 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 13 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R13- STORE

1. General Details:
Floor Area ......................................................... 26.5 m²
Avg. Ceiling Height ............................................. 5.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 26.9 4 1 0

3.1. Construction Types for Exposure SSE


Wall Type .............................................. external wall(19)
1st Window Type .................................. 5.35MX1.025M(4)
2nd Window Type ................................. 5.35MX0.575M(4)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 26.5 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.30 L/(s·m²)
Energy Analysis ................................................ 0.30 L/(s·m²)
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 92.8 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 14 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R14- IDF

1. General Details:
Floor Area ........................................................... 4.1 m²
Avg. Ceiling Height ............................................. 5.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 6000.0 Watts
Schedule ...................................... EQUIPMENT(30)

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 4.1 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 32.0 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 15 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R15- ELEC

1. General Details:
Floor Area ........................................................... 4.8 m²
Avg. Ceiling Height ............................................. 5.3 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(30)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 15.5 0 0 0

3.1. Construction Types for Exposure NNW


Wall Type .............................................. external wall(18)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 4.8 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 10.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 16 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R16-AHU

1. General Details:
Floor Area ....................................................... 117.5 m²
Avg. Ceiling Height ............................................. 5.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ........................................................ 1000.0 Watts
Schedule ...................................... EQUIPMENT(26)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 56.8 0 0 0
ENE 51.9 4 1 0
SSE 83.0 14 0 0

3.1. Construction Types for Exposure NNW


Wall Type .............................................. external wall(19)

3.2. Construction Types for Exposure ENE


Wall Type .............................................. external wall(19)
1st Window Type ......................................... 3MX0.95M(4)
2nd Window Type ..................................... 4.45MX1.8M(4)

3.3. Construction Types for Exposure SSE


Wall Type .............................................. external wall(19)
1st Window Type .................................. 5.35MX1.025M(4)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 117.5 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.30 L/(s·m²)
Energy Analysis ................................................ 0.30 L/(s·m²)
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 17.1 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 17 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

Hourly Analysis Program vv5.00 Page 18 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R17- GSM

1. General Details:
Floor Area ......................................................... 10.5 m²
Avg. Ceiling Height ............................................. 3.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage ...................................................... 30000.0 Watts
Schedule ...................................... EQUIPMENT(30)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 11.4 0 0 0
WSW 15.8 0 0 0

3.1. Construction Types for Exposure NNW


Wall Type .............................................. external wall(19)

3.2. Construction Types for Exposure WSW


Wall Type .............................................. external wall(19)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 10.5 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/(s·m²)
Energy Analysis ................................................ 0.00 L/(s·m²)
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 19 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R18- PUMP ROOM

1. General Details:
Floor Area ......................................................... 12.5 m²
Avg. Ceiling Height ............................................. 3.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 11.7 0 0 0

3.1. Construction Types for Exposure NNW


Wall Type .............................................. external wall(19)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 12.5 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.30 L/(s·m²)
Energy Analysis ................................................ 0.30 L/(s·m²)
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 20 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R19- STORE

1. General Details:
Floor Area ......................................................... 44.7 m²
Avg. Ceiling Height ............................................. 3.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 10.0 0 0 0
WSW 47.7 0 0 0

3.1. Construction Types for Exposure SSE


Wall Type .............................................. external wall(19)

3.2. Construction Types for Exposure WSW


Wall Type .............................................. external wall(19)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 44.7 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.30 L/(s·m²)
Energy Analysis ................................................ 0.30 L/(s·m²)
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 38.2 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 21 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R20- LIFT'S LOBBY

1. General Details:
Floor Area ......................................................... 33.3 m²
Avg. Ceiling Height ............................................. 3.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 11.2 0 0 0

3.1. Construction Types for Exposure NNW


Wall Type .............................................. external wall(18)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 33.3 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 64.2 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 22 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R21- STORE

1. General Details:
Floor Area ......................................................... 15.2 m²
Avg. Ceiling Height ............................................. 3.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage ............................................................ 6.00 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 22.7 0 0 0
NNW 12.0 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .............................................. external wall(19)

3.2. Construction Types for Exposure NNW


Wall Type .............................................. external wall(19)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 15.2 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.30 L/(s·m²)
Energy Analysis ................................................ 0.30 L/(s·m²)
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 31.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 23 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R22-AHU

1. General Details:
Floor Area ......................................................... 43.9 m²
Avg. Ceiling Height ............................................. 3.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 3.0 People
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(26)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 32.8 0 0 0
SSE 23.8 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .............................................. external wall(19)

3.2. Construction Types for Exposure SSE


Wall Type .............................................. external wall(19)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 43.9 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.30 L/(s·m²)
Energy Analysis ................................................ 0.30 L/(s·m²)
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 35.5 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 24 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R23- ELEC

1. General Details:
Floor Area ........................................................... 4.8 m²
Avg. Ceiling Height ............................................. 3.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 1.0 Person
Wattage .......................................................... 11.30 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .......................................................... 500.0 Watts
Schedule ...................................... EQUIPMENT(30)

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 8.0 0 0 0

3.1. Construction Types for Exposure SSE


Wall Type .............................................. external wall(19)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 4.8 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.30 L/(s·m²)
Energy Analysis ................................................ 0.30 L/(s·m²)
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................... 8.9 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.0 °C

Hourly Analysis Program vv5.00 Page 25 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R24 - DISH WASH

1. General Details:
Floor Area ......................................................... 17.2 m²
Avg. Ceiling Height ............................................. 5.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 4.0 People
Wattage ............................................................ 9.00 W/m² Activity Level .................................... Medium Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 86.5 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................. 133.3 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ........................................................... 2660 W
Schedule .......................................... LIGHTING(21) Schedule ...................................... EQUIPMENT(26)
Latent .............................................................. 1990 W
Schedule ...................................... EQUIPMENT(26)
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 37.8 0 0 0
WSW 15.4 0 0 0
ENE 15.4 0 0 0

3.1. Construction Types for Exposure NNW


Wall Type .............................................. external wall(19)

3.2. Construction Types for Exposure WSW


Wall Type .............................................. external wall(19)

3.3. Construction Types for Exposure ENE


Wall Type .............................................. external wall(19)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.2 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 26 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R25 - POT WASH

1. General Details:
Floor Area ........................................................... 8.5 m²
Avg. Ceiling Height ............................................. 3.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level .................................... Medium Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 86.5 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................. 133.3 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ............................................................. 265 W
Schedule .......................................... LIGHTING(21) Schedule ...................................... EQUIPMENT(26)
Latent .................................................................. 95 W
Schedule ...................................... EQUIPMENT(26)
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
ENE 11.8 0 0 0

3.1. Construction Types for Exposure ENE


Wall Type .............................................. external wall(18)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 8.5 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 27 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R26-SERV. CORRIDOR

1. General Details:
Floor Area ......................................................... 35.8 m²
Avg. Ceiling Height ............................................. 3.8 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 5.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 11.0 1 1 0
NNW 63.0 0 0 0

3.1. Construction Types for Exposure SSE


Wall Type .............................................. external wall(19)
1st Window Type .................................. 5.35MX1.025M(4)
2nd Window Type .................................. 0.875m*5.35m(2)

3.2. Construction Types for Exposure NNW


Wall Type .............................................. external wall(19)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 35.8 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 62.3 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 28 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R27-BOH. CORRIDOR

1. General Details:
Floor Area ......................................................... 20.0 m²
Avg. Ceiling Height ............................................. 5.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 5.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 20.0 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 16.6 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 29 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R28-CORRIDOR / LOBBY

1. General Details:
Floor Area ......................................................... 13.2 m²
Avg. Ceiling Height ............................................. 5.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s/person
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 5.0 People
Wattage ............................................................ 3.80 W/m² Activity Level ........................................ Office Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 71.8 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 60.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ................................................................. 0 W
Schedule ........................................................ None Schedule ......................................................... None
Latent .................................................................... 0 W
Schedule ......................................................... None
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SSE 38.9 0 0 0

3.1. Construction Types for Exposure SSE


Wall Type .............................................. external wall(18)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 13.2 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type ................................... Wall Partition (No partition data).
Area .................................................................. 42.3 m²
U-Value .......................................................... 2.839 W/(m²·K)
Uncondit. Space Max Temp .............................. 34.2 °C
Ambient at Space Max Temp ............................ 45.2 °C
Uncondit. Space Min Temp ............................... 15.0 °C
Ambient at Space Min Temp ............................... 7.9 °C

Hourly Analysis Program vv5.00 Page 30 of 31


Space Input Data
KFUPM LOAD CALCULATION 100% DD 22-12-2019 12/22/2019
KA 12:40PM

R29 - SHISHA PREP.

1. General Details:
Floor Area ......................................................... 12.5 m²
Avg. Ceiling Height ............................................. 5.4 m
Building Weight ............................................... 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage ..................................... User-Defined
OA Requirement 1 .............................................. 0.0 L/s
OA Requirement 2 ............................................ 0.00 L/(s·m²)
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type ........................ Recessed (Unvented) Occupancy .......................................................... 2.0 People
Wattage ............................................................ 9.00 W/m² Activity Level ................................. Sedentary Work
Ballast Multiplier ............................................... 1.00 Sensible ............................................................ 82.1 W/person
Schedule .......................................... LIGHTING(21) Latent ............................................................... 79.1 W/person
Schedule ............................................. PEOPLE(20)

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage ............................................................ 0.00 W/m² Sensible ............................................................. 310 W
Schedule .......................................... LIGHTING(21) Schedule ...................................... EQUIPMENT(26)
Latent ................................................................ 110 W
Schedule ...................................... EQUIPMENT(26)
2.3. Electrical Equipment:
Wattage .............................................................. 0.0 Watts
Schedule ........................................................ None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NNW 29.2 0 0 0
ENE 14.9 0 0 0

3.1. Construction Types for Exposure NNW


Wall Type .............................................. external wall(19)

3.2. Construction Types for Exposure ENE


Wall Type .............................................. external wall(19)

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 12.5 0 0

4.1. Construction Types for Exposure H


Roof Type ............................................................. Roof(9)

5. Infiltration:
Design Cooling ................................................. 0.30 L/(s·m²)
Design Heating ................................................. 0.00 L/s
Energy Analysis ................................................ 0.00 L/s
Infiltration occurs at all hours.

6. Floors:
Type ................... Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
(No partition data).

Hourly Analysis Program vv5.00 Page 31 of 31


Cooling Load Report
APPENDIX A

5. Air System Inputs.

   DEC.2019
*163-GFL-GST-01-LIV./DIN. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................. *163-GFL-GST-01-LIV./DIN.
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
218-GFL-GST-01-ENT x1
219-GFL-GST-01-LIV x1
220-GFL-GST-01-KITCHEN x1
221-GFL-GST-01-CORRIDOR x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %

Hourly Analysis Program v5.00 Page 1 of 436


*163-GFL-GST-01-LIV./DIN. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Direct Exhaust Airflow ............................................................................. 0.0 L/s


Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 2 of 436


*164-GFL-GST-01-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ...................................................... *164-GFL-GST-01-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
222-GFL-GST-01-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 3 of 436


*164-GFL-GST-01-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 4 of 436


*165-GFL-GST-01-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................... *165-GFL-GST-01-MBD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
223-GFL-GST-01-MBD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 5 of 436


*165-GFL-GST-01-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 6 of 436


*166-GFL-GST-02-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ...................................................... *166-GFL-GST-02-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
224-GFL-GST-02-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 7 of 436


*166-GFL-GST-02-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 8 of 436


*167-GFL-GST-02-LIV./DIN. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................. *167-GFL-GST-02-LIV./DIN.
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
225-GFL-GST-02-LIV x1
226-GFL-GST-02-KITCHEN x1
227-GFL-GST-02-ENT. x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Hourly Analysis Program v5.00 Page 9 of 436


*167-GFL-GST-02-LIV./DIN. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 10 of 436


*168-GFL-ST-01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................................... *168-GFL-ST-01
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
228-GFL-ST-01 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 24.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 11 of 436


*168-GFL-ST-01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 12 of 436


*169-GFL-MAIN CORR. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................... *169-GFL-MAIN CORR.
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
229-GFL-MAIN CORR. x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 24.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 13 of 436


*169-GFL-MAIN CORR. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 14 of 436


*170-F01-GST-02-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................................... *170-F01-GST-02-MBD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
230-F01-GST-02-MBD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 15 of 436


*170-F01-GST-02-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 16 of 436


*171-F01-GST-02-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *171-F01-GST-02-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
231-F01-GST-02-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 17 of 436


*171-F01-GST-02-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 18 of 436


*172-F01-GST-02-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................ *172-F01-GST-02-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
232-F01-GST-02-CORRID x1
233-F01-GST-02-ENT x1
234-F01-GST-02-LIV x1
235-F01-GST-02-KITCHE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s

Hourly Analysis Program v5.00 Page 19 of 436


*172-F01-GST-02-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 20 of 436


*173-F01-GST-01-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................................... *173-F01-GST-01-MBD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
236-F01-GST-01-MBD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 21 of 436


*173-F01-GST-01-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 22 of 436


*174-F01-GST-01-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *174-F01-GST-01-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
237-F01-GST-01-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 23 of 436


*174-F01-GST-01-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 24 of 436


*175-F01-GST-01-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................ *175-F01-GST-01-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
238-F01-GST-01-CORRIDOR x1
239-F01-GST-01-ENT x1
240-F01-GST-01-LIV x1
241-F01-GST-01-KITCHEN x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)

1 23.0 23.0 21.1 18.3 1.00 100 0.0 0.0

Hourly Analysis Program v5.00 Page 25 of 436


*175-F01-GST-01-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................ VAV box
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 26 of 436


*176-F01-ST-01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................................ *176-F01-ST-01
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
242-F01-ST-01 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 27 of 436


*176-F01-ST-01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 28 of 436


*177-F01-GST-03-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................ *177-F01-GST-03-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
243-F01-GST-03-LIV x1
244-F01-GST-03-ENT x1
245-F01-GST-03-KITCHE x1
246-F01-GST-03-CORRIDOR x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s

Hourly Analysis Program v5.00 Page 29 of 436


*177-F01-GST-03-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................ VAV box
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 30 of 436


*178-F01-GST-03-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *178-F01-GST-03-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
247-F01-GST-03-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 31 of 436


*178-F01-GST-03-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 32 of 436


*179-F01-GST-03-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................................... *179-F01-GST-03-MBD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
248-F01-GST-03-MBD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 33 of 436


*179-F01-GST-03-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 34 of 436


*180-F01-GST-06-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *180-F01-GST-06-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
249-F01-GST-06-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 35 of 436


*180-F01-GST-06-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 36 of 436


*181-F01-GST-06-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................ *181-F01-GST-06-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
250-F01-GST-06-LIV x1
251-F01-GST-06-ENT x1
252-F01-GST-06-KITCHEN x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Hourly Analysis Program v5.00 Page 37 of 436


*181-F01-GST-06-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 38 of 436


*182-F01-GST-08-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................ *182-F01-GST-08-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
253-F01-GST-08-LIV x1
254-F01-GST-08-KITCHEN x1
255-F01-GST-08-ENT x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Hourly Analysis Program v5.00 Page 39 of 436


*182-F01-GST-08-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................ VAV box
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 40 of 436


*183-F01-GST-8-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ......................................................... *183-F01-GST-8-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
256-F01-GST-08-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 41 of 436


*183-F01-GST-8-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 42 of 436


*184-F01-GST-10-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *184-F01-GST-10-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
257-F01-GST-10-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 43 of 436


*184-F01-GST-10-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 44 of 436


*185A-F01-MAIN CORR. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................................. *185A-F01-MAIN CORR.
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
260A-F01-MAIN CORRIDOR x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 24.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 45 of 436


*185A-F01-MAIN CORR. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 46 of 436


*185-F01-GST-10-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................ *185-F01-GST-10-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
258-F01-GST-10-LIV x1
259-F01-GST-10-ENT x1
260-F01-GST-10-KITCHEN x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Hourly Analysis Program v5.00 Page 47 of 436


*185-F01-GST-10-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 48 of 436


*186-F02-GST-02-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................................... *186-F02-GST-02-MBD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
261-F02-GST-02-MBD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 49 of 436


*186-F02-GST-02-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 50 of 436


*187-F02-GST-02-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *187-F02-GST-02-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
262-F02-GST-02-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 51 of 436


*187-F02-GST-02-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 52 of 436


*188-F02-GST-02-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................ *188-F02-GST-02-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
263-F02-GST-02-CORRID x1
264-F02-GST-02-ENT x1
265-F02-GST-02-LIV x1
266-F02-GST-02-KITCHEN x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s

Hourly Analysis Program v5.00 Page 53 of 436


*188-F02-GST-02-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 54 of 436


*189-F02-ST-02 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................................ *189-F02-ST-02
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
267-F02-ST-02 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 55 of 436


*189-F02-ST-02 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 56 of 436


*190-F02-GST-01-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................................... *190-F02-GST-01-MBD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
268-F02-GST-01-MBD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 57 of 436


*190-F02-GST-01-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 58 of 436


*191-F02-GST-01-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *191-F02-GST-01-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
269-F02-GST-01-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 59 of 436


*191-F02-GST-01-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 60 of 436


*192-F02-GST-01-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................ *192-F02-GST-01-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
270-F02-GST-01-CORRID x1
271-F02-GST-01-LIV x1
272-F02-GST-01-KITCHEN x1
273-F02-GST-01-ENT x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)

1 23.0 23.0 21.1 18.3 1.00 100 0.0 0.0

Hourly Analysis Program v5.00 Page 61 of 436


*192-F02-GST-01-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................ VAV box
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 62 of 436


*193-F02-ST-01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................................ *193-F02-ST-01
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
274-F02-ST-01 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 63 of 436


*193-F02-ST-01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 64 of 436


*194-F02-GST-03-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................ *194-F02-GST-03-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
275-F02-GST-03-LIV x1
276-F02-GST-03-KITCHEN x1
277-F02-GST-03-ENT x1
279-F02-GST-03-CORRIDOR x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s

Hourly Analysis Program v5.00 Page 65 of 436


*194-F02-GST-03-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................ VAV box
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 66 of 436


*195-F02-GST-03-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *195-F02-GST-03-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
278-F02-GST-03-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 67 of 436


*195-F02-GST-03-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 68 of 436


*196-F02-GST-03-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................................... *196-F02-GST-03-MBD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
280-F02-GST-03-MBD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 69 of 436


*196-F02-GST-03-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 70 of 436


*197-F02-MAIN CORR. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................................... *197-F02-MAIN CORR.
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
281-F02-MAIN CORRIDOR x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 24.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 71 of 436


*197-F02-MAIN CORR. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 72 of 436


*301-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................... *301-F03-TYP-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
301-F03-TYP-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 73 of 436


*301-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 74 of 436


*302-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *302-F03(03-08)-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
302-F03(03-08)-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 75 of 436


*302-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 76 of 436


*303-F03-STORE&LIFT'S Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................ *303-F03-STORE&LIFT'S
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
303-F03-STORE x1
303A-F03-LIFT'S MACHINE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Hourly Analysis Program v5.00 Page 77 of 436


*303-F03-STORE&LIFT'S Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 78 of 436


*304-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *304-F03(03-08)-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
304-F03(03-08)-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 79 of 436


*304-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 80 of 436


*305-F03-TYP-IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................................ *305-F03-TYP-IDF
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
305-F03-TYP-IDF x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 81 of 436


*305-F03-TYP-IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 82 of 436


*306-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *306-F03(03-08)-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
306-F03(03-08)-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 83 of 436


*306-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 84 of 436


*307-F03(03-08)- GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ........................................... *307-F03(03-08)- GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
307-F03(03-08)-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 85 of 436


*307-F03(03-08)- GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 86 of 436


*308-F03-TYP-LIFT LOBBY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................. *308-F03-TYP-LIFT LOBBY
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
308-F03-TYP-LIFT LOBBY x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 87 of 436


*308-F03-TYP-LIFT LOBBY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 88 of 436


*309-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *309-F03(03-08)-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
309-F03(03-08)-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 89 of 436


*309-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 90 of 436


*310-F03(03-08)GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................. *310-F03(03-08)GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
310-F03(03-08)-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 91 of 436


*310-F03(03-08)GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 92 of 436


*311-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *311-F03(03-08)-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
311-F03(03-08)-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 93 of 436


*311-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 94 of 436


*312-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................... *312-F03-TYP-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
312-F03-TYP-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 95 of 436


*312-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 96 of 436


*313-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *313-F03(03-08)-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
313-F03(03-08)-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 97 of 436


*313-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 98 of 436


*314-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................... *314-F03-TYP-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
314-F03-TYP-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 99 of 436


*314-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 100 of 436


*315-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *315-F03(03-08)-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
315-F03(03-08)-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 101 of 436


*315-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 102 of 436


*316-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................... *316-F03-TYP-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
316-F03-TYP-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 103 of 436


*316-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 104 of 436


*317-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *317-F03(03-08)-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
317-F03(03-08)-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 105 of 436


*317-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 106 of 436


*318-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................... *318-F03-TYP-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
318-F03-TYP-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 107 of 436


*318-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 108 of 436


*319-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *319-F03(03-08)-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
319-F03(03-08)-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 109 of 436


*319-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 110 of 436


*320-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................... *320-F03-TYP-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
320-F03-TYP-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 111 of 436


*320-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 112 of 436


*321-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *321-F03(03-08)-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
321-F03(03-08)-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 113 of 436


*321-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 114 of 436


*322-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *322-F03(03-08)-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
322-F03(03-08)-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 115 of 436


*322-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 116 of 436


*323-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *323-F03(03-08)-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
323-F03(03-08)-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 117 of 436


*323-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 118 of 436


*324-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *324-F03(03-08)-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
324-F03(03-08)-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 119 of 436


*324-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 120 of 436


*325-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *325-F03(03-08)-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
325-F03(03-08)-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 121 of 436


*325-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 122 of 436


*327-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................... *327-F03-TYP-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
327-F03-TYP-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 123 of 436


*327-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 124 of 436


*328-F03-TYP-SUITE-BD RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .......................................... *328-F03-TYP-SUITE-BD RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
328-F03-TYP-SUITE-BD RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 125 of 436


*328-F03-TYP-SUITE-BD RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 126 of 436


*329-F03-TYP-ELEC RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................................. *329-F03-TYP-ELEC RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
329-F03-TYP-ELEC RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 127 of 436


*329-F03-TYP-ELEC RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 128 of 436


*330-F03-TYP-IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................................ *330-F03-TYP-IDF
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
330-F03-TYP-IDF x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 129 of 436


*330-F03-TYP-IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 130 of 436


*331-F03-TYP-HK Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................................ *331-F03-TYP-HK
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
331-F03-TYP-HK x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 131 of 436


*331-F03-TYP-HK Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 132 of 436


*332-F03-TYP-SERV CORR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................. *332-F03-TYP-SERV CORR
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
332-F03-TYP-SERV CORR x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 133 of 436


*332-F03-TYP-SERV CORR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 134 of 436


*333-F03-TYP-SERV LOBBY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ........................................... *333-F03-TYP-SERV LOBBY
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
333-F03-TYP-SERV LOBBY x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 135 of 436


*333-F03-TYP-SERV LOBBY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 136 of 436


*334-F03-TYP-CORRIDOR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .............................................. *334-F03-TYP-CORRIDOR
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
334-F03-TYP-CORRIDOR x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 137 of 436


*334-F03-TYP-CORRIDOR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 138 of 436


*335-F03-TYP-SUITE-BD RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .......................................... *335-F03-TYP-SUITE-BD RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
335-F03-TYP-SUITE-BD RM x1
335A-F03-TYP-SUITE BD CO x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Hourly Analysis Program v5.00 Page 139 of 436


*335-F03-TYP-SUITE-BD RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 140 of 436


*336-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................... *336-F03-TYP-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
336-F03-TYP-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 141 of 436


*336-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 142 of 436


*337-F03-(03-08)-SUITE-BD RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ...................................... *337-F03-(03-08)-SUITE-BD RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
337-F03(03-08)SUITE-BD.R x1
337A-F03(03-08)SUIT.BD C x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Hourly Analysis Program v5.00 Page 143 of 436


*337-F03-(03-08)-SUITE-BD RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 144 of 436


*338-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *338-F03(03-08)-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
338-F03(03-08)-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 145 of 436


*338-F03(03-08)-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 146 of 436


*339-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................... *339-F03-TYP-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
339-F03-TYP-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 147 of 436


*339-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 148 of 436


*340-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................... *340-F03-TYP-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
340-F03-TYP-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 149 of 436


*340-F03-TYP-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 150 of 436


*341-F03(03-08)SUITE-LIV RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ........................................ *341-F03(03-08)SUITE-LIV RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
341-F03(03-08)-SUITE-LIV x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 151 of 436


*341-F03(03-08)SUITE-LIV RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 152 of 436


*342-F03(03-08)-SUITE-LIV RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................... *342-F03(03-08)-SUITE-LIV RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
342-F03(03-08)-SUITE-LIV x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 153 of 436


*342-F03(03-08)-SUITE-LIV RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 154 of 436


*343-F03-TYP-SUITE-LIV RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .......................................... *343-F03-TYP-SUITE-LIV RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
343-F03-TYP-SUITE-LIV RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 155 of 436


*343-F03-TYP-SUITE-LIV RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 156 of 436


*351-F03(03-06)-GST-01-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................... *351-F03(03-06)-GST-01-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
351-F03-(03-06)GST-01-EN x1
352-F03-(03-06)GST-01-LI x1
353-F03-(03-06)GST-01-KI x1
354-F03-(03-06)GST-01-Co x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)

1 23.0 23.0 21.1 18.3 1.00 100 0.0 0.0

Hourly Analysis Program v5.00 Page 157 of 436


*351-F03(03-06)-GST-01-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................ VAV box
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 158 of 436


*352-F03-(03-06)GST-01-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *352-F03-(03-06)GST-01-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
355-F03-(03-06)GST-01-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 159 of 436


*352-F03-(03-06)GST-01-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 160 of 436


*353-F03-(03-06)GST-01-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ......................................... *353-F03-(03-06)GST-01-MBD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
356-F03-(03-06)GST-01-MB x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 161 of 436


*353-F03-(03-06)GST-01-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 162 of 436


*354-F03-(03-06)GST-02-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ......................................... *354-F03-(03-06)GST-02-MBD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
362-F03-(03-06)GST-02-MB x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 163 of 436


*354-F03-(03-06)GST-02-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 164 of 436


*355-F03-(03-06)GST-02-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *355-F03-(03-06)GST-02-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
361-F03-(03-06)GST-02-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 165 of 436


*355-F03-(03-06)GST-02-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 166 of 436


*356-F03-(03-06)GST-02-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................... *356-F03-(03-06)GST-02-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
357-F03-(03-06)GST-02-EN x1
358-F03-(03-06)GST-02-LV x1
359-F03-(03-06)GST-02-KT x1
360-F03-(03-06)GST-02-CO x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s

Hourly Analysis Program v5.00 Page 167 of 436


*356-F03-(03-06)GST-02-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 168 of 436


*357-F03-(03-08)-ST-02 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................... *357-F03-(03-08)-ST-02
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
364-F03-(03-08)-ST-02 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 169 of 436


*357-F03-(03-08)-ST-02 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 170 of 436


*358-F03-(03-08)-ST-01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................... *358-F03-(03-08)-ST-01
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
363-F03-(03-08)-ST-01 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 171 of 436


*358-F03-(03-08)-ST-01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 172 of 436


*359-F03-(03-08)-GST-03-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................... *359-F03-(03-08)-GST-03-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
366-F03-(03-08GST-03-ENT x1
367-F03-(03-08)GST-03-LI x1
368-F03-(03-08)GST-03-KI x1
369-F03-(03-08)GST-03-CO x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s

Hourly Analysis Program v5.00 Page 173 of 436


*359-F03-(03-08)-GST-03-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................ VAV box
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 174 of 436


*360-F03-(03-08)-GST-03-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .......................................... *360-F03-(03-08)-GST-03-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
370-F03-(03-08)GST-03-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 175 of 436


*360-F03-(03-08)-GST-03-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 176 of 436


*361-F03-(03-08)-GST-03-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ........................................ *361-F03-(03-08)-GST-03-MBD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
371-F03(03-08)GST-03-MBD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 177 of 436


*361-F03-(03-08)-GST-03-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 178 of 436


*362-F03-(03-08)-ST-03 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................... *362-F03-(03-08)-ST-03
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
365-F03-(03-08)-ST-03 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 179 of 436


*362-F03-(03-08)-ST-03 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 180 of 436


*363-F03-(03-08)-ST-04 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................... *363-F03-(03-08)-ST-04
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
372-F03-(03-08)-ST-04 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 181 of 436


*363-F03-(03-08)-ST-04 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 182 of 436


*364-F03-(03-08)-GST-04-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................... *364-F03-(03-08)-GST-04-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ........................................................................ Proportional
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Minimum Airflow ........................................................................................ 0 %
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
373-F03(03-08)GST-04-ENT x1
374-F03(03-08)GST-04-LIV x1
375-F03(03-08)GST-04-KIT x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s

Hourly Analysis Program v5.00 Page 183 of 436


*364-F03-(03-08)-GST-04-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................ VAV box
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 184 of 436


*365-F03-(03-08)-GST-06-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................... *365-F03-(03-08)-GST-06-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
377-F03(03-08)GST-05-ENT x1
378-F03(03-08)GST-05-KIT x1
379-F03(03-08)GST-05-LIV x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)

1 23.0 23.0 21.1 18.3 1.00 100 0.0 0.0

Thermostat Schedule .................................................... THERMOSTAT(22)

Hourly Analysis Program v5.00 Page 185 of 436


*365-F03-(03-08)-GST-06-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................ VAV box
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 186 of 436


*366-F03-(03-08)-GST-05-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .......................................... *366-F03-(03-08)-GST-05-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
380-F03(03-08)-GST-05-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 187 of 436


*366-F03-(03-08)-GST-05-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 188 of 436


*367-F03-(03-08)-GST-04-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .......................................... *367-F03-(03-08)-GST-04-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
376-F03(03-08)-GST-04-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 189 of 436


*367-F03-(03-08)-GST-04-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 190 of 436


*368-F03-(03-08)-GST-06-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .......................................... *368-F03-(03-08)-GST-06-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
384-F03(03-08)-GST-06-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 191 of 436


*368-F03-(03-08)-GST-06-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 192 of 436


*369-F03-(03-08)-GST-08-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .......................................... *369-F03-(03-08)-GST-08-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
388-F03(03-08)-GST-07-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 193 of 436


*369-F03-(03-08)-GST-08-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 194 of 436


*370-F03-(03-08)-GST-06-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................... *370-F03-(03-08)-GST-06-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
381-F03(03-08)GST-06-ENT x1
382-F03(03-08)GST-06-LIV x1
383-F03(03-08)GST-06-KIT x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Hourly Analysis Program v5.00 Page 195 of 436


*370-F03-(03-08)-GST-06-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 196 of 436


*371-F03-(03-08)-GST-07-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................... *371-F03-(03-08)-GST-07-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
385-F03(03-08)GST-07-ENT x1
386-F03(03-08)GST-07-LIV x1
387-F03(03-08)GST-07-KIT x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)

1 23.0 23.0 21.1 18.3 1.00 100 0.0 0.0

Thermostat Schedule .................................................... THERMOSTAT(22)

Hourly Analysis Program v5.00 Page 197 of 436


*371-F03-(03-08)-GST-07-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................ VAV box
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 198 of 436


*372-F03-(03-08)-GST-08-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................... *372-F03-(03-08)-GST-08-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
389-F03(03-08)GST-08-ENT x1
390-F03(03-08)GST-08-LIV x1
391-F03(03-08)GST-08-KIT x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Hourly Analysis Program v5.00 Page 199 of 436


*372-F03-(03-08)-GST-08-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................ VAV box
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 200 of 436


*373-F03-(03-08)-GST-8-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ............................................ *373-F03-(03-08)-GST-8-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
392-F03(03-08)-GST-08-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 201 of 436


*373-F03-(03-08)-GST-8-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 202 of 436


*374-F03-(03-08)-GST-09-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................... *374-F03-(03-08)-GST-09-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
393-F03(03-08)GST-09-ENT x1
394-F03(03-08)GST-09-LIV x1
395-F03(03-08)GST-09-KIT x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Hourly Analysis Program v5.00 Page 203 of 436


*374-F03-(03-08)-GST-09-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 204 of 436


*375-F03-(03-08)-GST-09-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .......................................... *375-F03-(03-08)-GST-09-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
396-F03(03-08)-GST-09-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 205 of 436


*375-F03-(03-08)-GST-09-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 206 of 436


*376-F03-(03-08)-GST-11-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .......................................... *376-F03-(03-08)-GST-11-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
404-F03(03-08)-GST-11-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 207 of 436


*376-F03-(03-08)-GST-11-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 208 of 436


*377-F03-(03-08)-GST-10-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .......................................... *377-F03-(03-08)-GST-10-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
400-F03(03-08)-GST-10-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 209 of 436


*377-F03-(03-08)-GST-10-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 210 of 436


*378-F03-(03-08)-GST-10-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................... *378-F03-(03-08)-GST-10-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
397-F03(03-08)GST-10-ENT x1
398-F03(03-08)GST-10-LIV x1
399-F03(03-08)GST-10-KIT x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Hourly Analysis Program v5.00 Page 211 of 436


*378-F03-(03-08)-GST-10-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 212 of 436


*379-F03-(03-08)-GST-11-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................... *379-F03-(03-08)-GST-11-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
401-F03(03-08)GST-11-ENT x1
402-F03(03-08)GST-11-LIV x1
403-F03(03-08)GST-11-KIT x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Hourly Analysis Program v5.00 Page 213 of 436


*379-F03-(03-08)-GST-11-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 214 of 436


*380-F03-(03-08)-MAIN CORRIDOR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................ *380-F03-(03-08)-MAIN CORRIDOR
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
405-F03(03-08)-MAIN CORR x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 24.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 215 of 436


*380-F03-(03-08)-MAIN CORRIDOR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 216 of 436


*408-F04-(04-09)FAMILY ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ..................................... *408-F04-(04-09)FAMILY ROOM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
408-F04-(04-09)FAMILY RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 217 of 436


*408-F04-(04-09)FAMILY ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 218 of 436


*601-F06-GST-02-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................................... *601-F06-GST-02-MBD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
601-F06-GST-02-MBD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 219 of 436


*601-F06-GST-02-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 220 of 436


*602-F06-GST-01-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................................... *602-F06-GST-01-MBD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
602-F06-GST-01-MBD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 221 of 436


*602-F06-GST-01-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 222 of 436


*701-F07-GST-01-MB Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *701-F07-GST-01-MB
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
701-F07-GST-01-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 223 of 436


*701-F07-GST-01-MB Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 224 of 436


*702-F07-GST-01-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *702-F07-GST-01-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
702-F07-GST-01-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 225 of 436


*702-F07-GST-01-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 226 of 436


*801-F08-ST-01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................................ *801-F08-ST-01
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
801-F08-ST-01 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 227 of 436


*801-F08-ST-01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 228 of 436


*802-F08-ST-02 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................................ *802-F08-ST-02
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
802-F08-ST-02 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 229 of 436


*802-F08-ST-02 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 230 of 436


*902-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *902-F09-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
902-F09-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 231 of 436


*902-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 232 of 436


*904-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *904-F09-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
904-F09-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 233 of 436


*904-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 234 of 436


*906-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *906-F09-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
906-F09-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 235 of 436


*906-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 236 of 436


*907-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *907-F09-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
907-F09-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 237 of 436


*907-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 238 of 436


*909-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *909-F09-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
909-F09-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 239 of 436


*909-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 240 of 436


*910-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *910-F09-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
910-F09-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 241 of 436


*910-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 242 of 436


*911-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *911-F09-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
911-F09-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 243 of 436


*911-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 244 of 436


*913-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *913-F09-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
913-F09-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 245 of 436


*913-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 246 of 436


*915-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *915-F09-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
915-F09-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 247 of 436


*915-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 248 of 436


*917-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *917-F09-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
917-F09-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 249 of 436


*917-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 250 of 436


*919-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *919-F09-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
919-F09-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 251 of 436


*919-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 252 of 436


*921-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *921-F09-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
921-F09-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 253 of 436


*921-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 254 of 436


*922-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *922-F09-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
922-F09-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 255 of 436


*922-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 256 of 436


*923-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *923-F09-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
923-F09-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 257 of 436


*923-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 258 of 436


*924-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *924-F09-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
924-F09-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 259 of 436


*924-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 260 of 436


*925-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *925-F09-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
925-F09-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 261 of 436


*925-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 262 of 436


*937-F09-SUITE-BD RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................................. *937-F09-SUITE-BD RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
937-F09-SUITE-BD x1
937A-F09-SUITE.BD CORRID x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Hourly Analysis Program v5.00 Page 263 of 436


*937-F09-SUITE-BD RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 264 of 436


*938-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *938-F09-GUEST RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
938-F09-GUEST RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 265 of 436


*938-F09-GUEST RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 266 of 436


*941-F09-SUITE-LIV RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................................. *941-F09-SUITE-LIV RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
941-F09-SUITE-LIV x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 267 of 436


*941-F09-SUITE-LIV RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 268 of 436


*942-F09-SUITE-LIV RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................................. *942-F09-SUITE-LIV RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
942-F09-SUITE-LIV x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(21)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 269 of 436


*942-F09-SUITE-LIV RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 270 of 436


*957-F09-ST-01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................................ *957-F09-ST-01
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
964-F09-ST-01 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 271 of 436


*957-F09-ST-01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 272 of 436


*958-F09-ST-02 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................................ *958-F09-ST-02
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
963-F09-ST-02 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 273 of 436


*958-F09-ST-02 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 274 of 436


*959-F09-GST-03-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................ *959-F09-GST-03-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
966-F09-GST-03-ENT x1
967-F09-GST-03-LIV x1
968-F09-GST-03-KITCHE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Hourly Analysis Program v5.00 Page 275 of 436


*959-F09-GST-03-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................ VAV box
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 276 of 436


*960-F09-GST-03-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *960-F09-GST-03-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
970-F09-GST-03-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 277 of 436


*960-F09-GST-03-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 278 of 436


*961-F09-GST-03-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................................... *961-F09-GST-03-MBD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
971-F09-GST-03-MBD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 279 of 436


*961-F09-GST-03-MBD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 280 of 436


*962-F0-ST-03 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name .................................................................. *962-F0-ST-03
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
965-F09-ST-03 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 281 of 436


*962-F0-ST-03 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 282 of 436


*963-F09-ST-04 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................................ *963-F09-ST-04
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
972-F09-ST-04 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 283 of 436


*963-F09-ST-04 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 284 of 436


*964-F09-GST-04-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................ *964-F09-GST-04-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ........................................................................ Proportional
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Minimum Airflow ........................................................................................ 0 %
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
973-F09-GST-04-ENT x1
974-F09-GST-04-LIV x1
975-F09-GST-04-KITCHE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s

Hourly Analysis Program v5.00 Page 285 of 436


*964-F09-GST-04-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................ VAV box
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 286 of 436


*965-F09-GST-06-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................ *965-F09-GST-06-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
977-F09-GST-05-ENT x1
978-F09-GST-05-KITCHE x1
979-F09-GST-05-LIV x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)

1 23.0 23.0 21.1 18.3 1.00 100 0.0 0.0

Thermostat Schedule .................................................... THERMOSTAT(22)

Hourly Analysis Program v5.00 Page 287 of 436


*965-F09-GST-06-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................ VAV box
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 288 of 436


*966-F09-GST-05-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *966-F09-GST-05-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
980-F09-GST-05-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 289 of 436


*966-F09-GST-05-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 290 of 436


*967-F09-GST-04-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *967-F09-GST-04-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
976-F09-GST-04-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 291 of 436


*967-F09-GST-04-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 292 of 436


*968-F0-GST-06-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ......................................................... *968-F0-GST-06-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
984-F09-GST-06-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 293 of 436


*968-F0-GST-06-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 294 of 436


*969-F09-GST-08-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *969-F09-GST-08-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
988-F09-GST-07-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 295 of 436


*969-F09-GST-08-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 296 of 436


*970-F09-GST-06-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................ *970-F09-GST-06-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
981-F09-GST-06-ENT x1
982-F09-GST-06-LIV x1
983-F09-GST-06-KITCHE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Hourly Analysis Program v5.00 Page 297 of 436


*970-F09-GST-06-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 298 of 436


*971-F09-GST-07-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................ *971-F09-GST-07-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
985-F09-GST-07-ENT x1
986-F09-GST-07-LIV x1
987-F09-GST-07-KITCHE x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)

1 23.0 23.0 21.1 18.3 1.00 100 0.0 0.0

Thermostat Schedule .................................................... THERMOSTAT(22)

Hourly Analysis Program v5.00 Page 299 of 436


*971-F09-GST-07-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................ VAV box
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 300 of 436


*972-F09-GST-08-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................ *972-F09-GST-08-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
989-F09-GST-08-ENT x1
990-F09-GST-08-LIV x1
991-F09-GST-08-KITCHE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Hourly Analysis Program v5.00 Page 301 of 436


*972-F09-GST-08-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................ VAV box
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 302 of 436


*973-F09-GST-8-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ......................................................... *973-F09-GST-8-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
992-F09-GST-08-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 303 of 436


*973-F09-GST-8-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 304 of 436


*974-F09-GST-09-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ................................................ *974-F09-GST-09-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
993-F09-GST-09-ENT x1
994-F09-GST-09-LIV x1
995-F09-GST-09-KITCHE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Hourly Analysis Program v5.00 Page 305 of 436


*974-F09-GST-09-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 306 of 436


*975-F09-GST-09-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *975-F09-GST-09-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
996-F09-GST-09-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 307 of 436


*975-F09-GST-09-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 308 of 436


*976-F08-GST-11-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *976-F08-GST-11-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
1004-F09-GST-11-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 309 of 436


*976-F08-GST-11-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 310 of 436


*977-F09-GST-10-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

1. General Details:
Air System Name ....................................................... *977-F09-GST-10-BD
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
1000-F09-GST-10-BD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 23.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 311 of 436


*977-F09-GST-10-BD Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:55AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 312 of 436


*978-F09-GST-10-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................ *978-F09-GST-10-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
997-F09-GST-10-ENT x1
998-F09-GST-10-LIV x1
999-F09-GST-10-KITCHEN x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Hourly Analysis Program v5.00 Page 313 of 436


*978-F09-GST-10-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 314 of 436


*979-F09-GST-11-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................ *979-F09-GST-11-LIV/DIN
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
1001-F09-GST-11-ENT x1
1002-F09-GST-11-LIV x1
1003-F09-GST-11-KITCHEN x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Hourly Analysis Program v5.00 Page 315 of 436


*979-F09-GST-11-LIV/DIN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 316 of 436


*980-F09-MAIN CORRIDOR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ............................................ *980-F09-MAIN CORRIDOR
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
1005-F09-MAIN CORR x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 24.0 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule .................................................... THERMOSTAT(22)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:

Hourly Analysis Program v5.00 Page 317 of 436


*980-F09-MAIN CORRIDOR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Zone ........................................................................................................ All


Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 318 of 436


001- BS -LOST & FOUND Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................ 001- BS -LOST & FOUND
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
001-BS-LOST & FOUND OFF x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 319 of 436


001- BS -LOST & FOUND Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 320 of 436


002-BS- H.K WORK STATION Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ......................................... 002-BS- H.K WORK STATION
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
002-BS- H.K WORK STATION x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 321 of 436


002-BS- H.K WORK STATION Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 322 of 436


003-BS- H.K OFFICE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ....................................................... 003-BS- H.K OFFICE
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
003-BS- H.K OFFICE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 323 of 436


003-BS- H.K OFFICE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 324 of 436


004-BS- VALET LAUNDARY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ........................................... 004-BS- VALET LAUNDARY
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 14.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
004-BS- VALET LAUNDARY x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.30 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 325 of 436


004-BS- VALET LAUNDARY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 326 of 436


005-BS- LIFT LOBBY-01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................. 005-BS- LIFT LOBBY-01
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
005-BS- LIFT LOBBY x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 327 of 436


005-BS- LIFT LOBBY-01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 328 of 436


006-BS- CORRIDOR01UP Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ............................................... 006-BS- CORRIDOR01UP
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
006-BS- CORR 01UP x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 329 of 436


006-BS- CORRIDOR01UP Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 330 of 436


007-BS- UNIFORM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ........................................................... 007-BS- UNIFORM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
007-BS- UNIFORM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 331 of 436


007-BS- UNIFORM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 332 of 436


008-BS- CLEAN LINEN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................... 008-BS- CLEAN LINEN
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
008-BS- CLEAN LINEN x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 333 of 436


008-BS- CLEAN LINEN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 334 of 436


009-BS- DIRTY LINEN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ..................................................... 009-BS- DIRTY LINEN
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
009-BS- DIRTY LINEN x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 335 of 436


009-BS- DIRTY LINEN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 336 of 436


010-BS- ELEC 01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ............................................................. 010-BS- ELEC 01
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
010-BS- ELEC 01 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 337 of 436


010-BS- ELEC 01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 338 of 436


011-BS- IDF 01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................................. 011-BS- IDF 01
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
011-BS- IDF 01 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 339 of 436


011-BS- IDF 01 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 340 of 436


012-BS- DEBOXING Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ........................................................ 012-BS- DEBOXING
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 14.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
012-BS- DEBOXING x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 341 of 436


012-BS- DEBOXING Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 342 of 436


013-BS- GSM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................................... 013-BS- GSM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
013-BS- GSM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 21.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 20.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 343 of 436


013-BS- GSM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 344 of 436


014 -BS- Baverage STORE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ............................................. 014 -BS- Baverage STORE
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
014 -BS- Baverage STORE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 345 of 436


014 -BS- Baverage STORE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 346 of 436


015-BS- PUMP ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ..................................................... 015-BS- PUMP ROOM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
015-BS- PUMP ROOM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 25.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 347 of 436


015-BS- PUMP ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 348 of 436


016-BS- COST CONTROL Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ............................................... 016-BS- COST CONTROL
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
016-BS- COST CONTROL x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 349 of 436


016-BS- COST CONTROL Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 350 of 436


017-BS- PUR. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................................... 017-BS- PUR.
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
017-BS- PUR. x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 351 of 436


017-BS- PUR. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 352 of 436


018-BS- RECV. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................................ 018-BS- RECV.
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
018-BS- RECV. x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 353 of 436


018-BS- RECV. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 354 of 436


019-BS- SEC. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................................... 019-BS- SEC.
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
019-BS- SEC. x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 355 of 436


019-BS- SEC. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 356 of 436


020-BS- FLOWER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ............................................................ 020-BS- FLOWER
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
020-BS- FLOWER x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 357 of 436


020-BS- FLOWER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 358 of 436


021-BS- MEP Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................................... 021-BS- MEP
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
021-BS- MEP x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 359 of 436


021-BS- MEP Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 360 of 436


022 -BS-CARPENTER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ..................................................... 022 -BS-CARPENTER
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
022 -BS-CARPENTER x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 361 of 436


022 -BS-CARPENTER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 362 of 436


023-BS- UPS Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name .................................................................... 023-BS- UPS
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
023-BS- UPS x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 20.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 19.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 363 of 436


023-BS- UPS Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 364 of 436


024 -BS- MAINTSTORE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................... 024 -BS- MAINTSTORE
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
024 -BS- MAINTSTORE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 365 of 436


024 -BS- MAINTSTORE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 366 of 436


025-BS- BMS Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................................... 025-BS- BMS
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
025-BS- BMS x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 22.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 19.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 367 of 436


025-BS- BMS Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 368 of 436


026-BS- CHEF. ENG. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ....................................................... 026-BS- CHEF. ENG.
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
026-BS- CHEF. ENG. x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 369 of 436


026-BS- CHEF. ENG. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 370 of 436


027-BS- ASS. ENG. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ......................................................... 027-BS- ASS. ENG.
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
027-BS- ASS. ENG. x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 371 of 436


027-BS- ASS. ENG. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 372 of 436


028-BS- GENERAL WORKSHOP Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name .................................... 028-BS- GENERAL WORKSHOP
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
028-BS- GENERAL WORKSHOP x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 373 of 436


028-BS- GENERAL WORKSHOP Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 374 of 436


029-BS- CORRIDOR02 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name .................................................... 029-BS- CORRIDOR02
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
029-BS- CORRIDOR02 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 375 of 436


029-BS- CORRIDOR02 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 376 of 436


030-BS- FURNITURE ST Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................. 030-BS- FURNITURE ST
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
030-BS- FURNITURE ST x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 377 of 436


030-BS- FURNITURE ST Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 378 of 436


031-BS- LIFT LOBBY-02 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................. 031-BS- LIFT LOBBY-02
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
031-BS- LIFT LOBBY x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 379 of 436


031-BS- LIFT LOBBY-02 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 380 of 436


032-BS- RMU Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................................... 032-BS- RMU
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
032-BS- RMU x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 381 of 436


032-BS- RMU Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 382 of 436


033-BS- CORR.DN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ........................................................... 033-BS- CORR.DN
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
033-BS- CORR 01DN x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 383 of 436


033-BS- CORR.DN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 384 of 436


034-BS- ELEC 02 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ............................................................. 034-BS- ELEC 02
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
034-BS- ELEC 02 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 385 of 436


034-BS- ELEC 02 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 386 of 436


035-BS- IDF 02 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................................. 035-BS- IDF 02
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
035-BS- IDF 02 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 387 of 436


035-BS- IDF 02 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 388 of 436


036-BS- WASTE ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name .................................................. 036-BS- WASTE ROOM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
036-BS- WASTE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 20.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 17.0 °C
Heating T-stat: Unocc. .......................................................................... 16.5 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 389 of 436


036-BS- WASTE ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 390 of 436


037-BS- M. ELEC ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................. 037-BS- M. ELEC ROOM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
037-BS- M. ELEC ROOM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 391 of 436


037-BS- M. ELEC ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 392 of 436


038-BS- M. TELECOM RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ............................................... 038-BS- M. TELECOM RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
038-BS- M. TELELECOM RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 21.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 20.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 393 of 436


038-BS- M. TELECOM RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 394 of 436


039-BS- SECURITY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ......................................................... 039-BS- SECURITY
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
039-BS- SECURITY x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 395 of 436


039-BS- SECURITY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 396 of 436


040-BS- SECURITY EQU. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................ 040-BS- SECURITY EQU.
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
040-BS- SECURITY EQU. x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 20.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 19.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ........................................................ THERMOSTATE


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 397 of 436


040-BS- SECURITY EQU. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 398 of 436


041-BS- SERVER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ............................................................. 041-BS- SERVER
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Dehumidification Data:
Maximum RH Setpoint ............................................................................. 50 %
Heating Source ..................................................................................... Any

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
041-BS- SERVER x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 20.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 19.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 399 of 436


041-BS- SERVER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ................................................................ 12.0 °C
Supply Fan Airflow ............................................................................ 6466.7 L/s
Ventilation Airflow ................................................................................... 0.0 L/s

Hydronic Sizing Specifications:


Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil -


(L/s) (kW) (kW) (L/s)
1 6466.7 - -

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 400 of 436


042-BS- IT DIRECTOR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ..................................................... 042-BS- IT DIRECTOR
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
042-BS- IT DIRECTOR x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 401 of 436


042-BS- IT DIRECTOR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 402 of 436


043-BS- IT TECHNICIANS Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ............................................... 043-BS- IT TECHNICIANS
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
043-BS- IT TECHNICIANS x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 403 of 436


043-BS- IT TECHNICIANS Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 404 of 436


044-BS- PUMP ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ..................................................... 044-BS- PUMP ROOM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
044-BS- PUMP ROOM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 25.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 405 of 436


044-BS- PUMP ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 406 of 436


045*-BS- STORE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name .............................................................. 045*-BS- STORE
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
045-BS- STORE -05 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 407 of 436


045*-BS- STORE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 408 of 436


045-BS- STORE -05 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ......................................................... 045-BS- STORE -05
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
045-BS- STORE -05 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 409 of 436


045-BS- STORE -05 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 410 of 436


046-BS- ETS ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ........................................................ 046-BS- ETS ROOM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
046-BS- ETS ROOM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 25.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 411 of 436


046-BS- ETS ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 412 of 436


047-BS- PUMP ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ..................................................... 047-BS- PUMP ROOM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
047-BS- PUMP ROOM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 25.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.10 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 413 of 436


047-BS- PUMP ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 414 of 436


048-BS- IDF 05 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................................. 048-BS- IDF 05
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
048-BS- IDF 05 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 415 of 436


048-BS- IDF 05 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 416 of 436


049 -BS- LIFT LOBBY-03 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................ 049 -BS- LIFT LOBBY-03
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
049 -BS- LIFT LOBBY-02 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 417 of 436


049 -BS- LIFT LOBBY-03 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 418 of 436


050-BS- IDF 03 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................................. 050-BS- IDF 03
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
050-BS- IDF 03 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 419 of 436


050-BS- IDF 03 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 420 of 436


051-BS- ELEC 03 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ............................................................. 051-BS- ELEC 03
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
051-BS- ELEC 03 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 421 of 436


051-BS- ELEC 03 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 422 of 436


052-BS- IDF 04 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ................................................................. 052-BS- IDF 04
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
052-BS- IDF 04 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 423 of 436


052-BS- IDF 04 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 424 of 436


053-BS- ELEC 04 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ............................................................. 053-BS- ELEC 04
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
053-BS- ELEC 04 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 425 of 436


053-BS- ELEC 04 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 426 of 436


054-BS- PUMP ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ..................................................... 054-BS- PUMP ROOM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
054-BS- PUMP ROOM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 25.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 427 of 436


054-BS- PUMP ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 428 of 436


055-BS- PUMP ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ..................................................... 055-BS- PUMP ROOM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
055-BS- PUMP ROOM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 25.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 429 of 436


055-BS- PUMP ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 430 of 436


056*-BS- PUMP ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name .................................................... 056*-BS- PUMP ROOM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
056*-BS- PUMP ROOM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 25.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 431 of 436


056*-BS- PUMP ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 432 of 436


056-BS- PUMP ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name ..................................................... 056-BS- PUMP ROOM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
056-BS- PUMP ROOM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 25.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 433 of 436


056-BS- PUMP ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 434 of 436


057-BS- CORRIDOR03 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

1. General Details:
Air System Name .................................................... 057-BS- CORRIDOR03
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
057-BS- CORRIDOR03 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 435 of 436


057-BS- CORRIDOR03 Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:56AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 436 of 436


058- GR - PREFUNCTION Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ............................................... 058- GR - PREFUNCTION
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ........................................................................ Proportional
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Minimum Airflow ........................................................................................ 0 %
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Dehumidification Data:
Maximum RH Setpoint ............................................................................. 60 %
Heating Source ..................................................................................... Any

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.5 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
061- GR - PREFUNCTION x1
064 - GR - AIR LOCK-01 x1

Hourly Analysis Program v5.00 Page 1 of 322


058- GR - PREFUNCTION Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ........................................................ THERMOSTATE


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 2 of 322


059-GR- FIRE COMAND Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name .................................................. 059-GR- FIRE COMAND
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
058 - GR - FIRE COMM. x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 3 of 322


059-GR- FIRE COMAND Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 4 of 322


060 - GR - STAFF ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ................................................. 060 - GR - STAFF ROOM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
059 - GR - STAFF ROOM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 5 of 322


060 - GR - STAFF ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 6 of 322


061 - GR - STORE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ............................................................ 061 - GR - STORE
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
060 - GR - LUGG. ST x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 7 of 322


061 - GR - STORE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 8 of 322


062 - GR - BRIDE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name .......................................................... 062 - GR - BRIDE
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
070- GR - VIP BRIDE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 9 of 322


062 - GR - BRIDE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 10 of 322


063- GR - BALL ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ................................................... 063- GR - BALL ROOM
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 3

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ........................................................................ Proportional
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Minimum Airflow ........................................................................................ 0 %
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Dehumidification Data:
Maximum RH Setpoint ............................................................................. 60 %
Heating Source ..................................................................................... Any

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.5 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
065L - GR - BALL ROOM1 x1
Zone 2: Zone 2

Hourly Analysis Program v5.00 Page 11 of 322


063- GR - BALL ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

065C - GR - BALL ROOM 2 x1


Zone 3: Zone 3
065R - GR - BALL ROOM3 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ........................................................ THERMOSTATE


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 12 of 322


064- GR - RECEPTION &MEET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ....................................... 064- GR - RECEPTION &MEET
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 6

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ........................................................................ Proportional
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Minimum Airflow ........................................................................................ 0 %
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.5 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
063 - GR - RECE. MEETING x1
Zone 2: Zone 2
067 - GR - F&B DISPLAY x1
Zone 3: Zone 3
127 - GR -CAR LIFTSLOBBY x1

Hourly Analysis Program v5.00 Page 13 of 322


064- GR - RECEPTION &MEET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

128 - GR - LIFTSLOBBY x1
Zone 4: Zone 4
066 - GR - COWORKING x1
Zone 5: Zone 5
062 - GR - MERCHANDISE x1
Zone 6: Zone 6
069 - GR - LOBBY x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)

1 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0


2 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
3 24.0 26.7 21.1 18.3 0.83 100 0.0 0.0
4 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
5 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
6 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0

Thermostat Schedule ........................................................ THERMOSTATE


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 14 of 322


065- GR - HOTEL LOBBY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ................................................ 065- GR - HOTEL LOBBY
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ....................................................................................... 6

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ........................................................................ Proportional
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Minimum Airflow ........................................................................................ 0 %
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.5 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
071 - GR - SOCIAL HUP x1
Zone 2: Zone 2
072 - GR - HOTTEL LOBBY x1
Zone 3: Zone 3
073 - GR - AIR LOCK-03 x1

Hourly Analysis Program v5.00 Page 15 of 322


065- GR - HOTEL LOBBY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Zone 4: Zone 4
078 - GR - LECTURE. LIBR x1
Zone 5: Zone 5
134 - 1ST - HOTTEL LOBBY x1
Zone 6: Zone 6
135 - 1ST - LEC. LOUNGE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ........................................................ THERMOSTATE


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 16 of 322


066- GR - KIT. WASTE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name .................................................. 066- GR - KIT. WASTE
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
101 - GR - KIT. WASTE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 20.0 °C
Cooling T-stat: Unocc. .......................................................................... 22.0 °C
Heating T-stat: Occ. ................................................................................ 9.0 °C
Heating T-stat: Unocc. ............................................................................ 8.0 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 17 of 322


066- GR - KIT. WASTE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 18 of 322


067-GR- IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ..................................................................... 067-GR- IDF
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
074-GR- IDF x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 19 of 322


067-GR- IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 20 of 322


068-GR- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ................................................................. 068-GR- ELEC
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
075 -GR- ELEC x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 21 of 322


068-GR- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 22 of 322


069-GR- AV CONTROL RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ............................................. 069-GR- AV CONTROL RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
076 -GR- AV CONTROL RM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 23 of 322


069-GR- AV CONTROL RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 24 of 322


070- GR- AV EQUIP. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ........................................................ 070- GR- AV EQUIP.
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
077 -GR- AV EQUIP. x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 25 of 322


070- GR- AV EQUIP. Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 26 of 322


071 - GR - AIRLOCK Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ..................................................... 071 - GR - AIRLOCK
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
068- GR - AIR LOCK-02 x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 27 of 322


071 - GR - AIRLOCK Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 28 of 322


072 - GR - BACK OFFICE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ................................................ 072 - GR - BACK OFFICE
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
079 - GR - BACK OFFICE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 29 of 322


072 - GR - BACK OFFICE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 30 of 322


073 - GR - STAFF ENTR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name .................................................. 073 - GR - STAFF ENTR
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
080 - GR - STAFF ENTR x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 31 of 322


073 - GR - STAFF ENTR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 32 of 322


074 - GR - LUGGAGE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ...................................................... 074 - GR - LUGGAGE
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
081 - GR - LUGGAGE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 33 of 322


074 - GR - LUGGAGE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 34 of 322


075 - GR- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ............................................................... 075 - GR- ELEC
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
082 -GR- ELEC x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 35 of 322


075 - GR- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 36 of 322


076 - GR- IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ................................................................... 076 - GR- IDF
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
083-GR- IDF x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 37 of 322


076 - GR- IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 38 of 322


077 - GR- HK Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name .................................................................... 077 - GR- HK
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
084-GR- HK x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 39 of 322


077 - GR- HK Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 40 of 322


078 - GR- SECURITY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ....................................................... 078 - GR- SECURITY
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
085-GR- SECURITY x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 41 of 322


078 - GR- SECURITY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 42 of 322


079 - GR - LUGGAGE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name .................................................... 079 - GR - LUGGAGE
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
086 - GR - LUGGAGE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 43 of 322


079 - GR - LUGGAGE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 44 of 322


081 - GR - STAFF. CORRIDOR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ..................................... 081 - GR - STAFF. CORRIDOR
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
088-GR- STAFF. CORRIDOR x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 45 of 322


081 - GR - STAFF. CORRIDOR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 46 of 322


082 - GR - LIFT LOBBY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ................................................. 082 - GR - LIFT LOBBY
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
089-GR- LIFT LOBBY x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 47 of 322


082 - GR - LIFT LOBBY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 48 of 322


083- GR - APPAR. LOBBY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name .............................................. 083- GR - APPAR. LOBBY
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Dehumidification Data:
Maximum RH Setpoint ............................................................................. 55 %
Heating Source ..................................................................................... Any

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.5 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
090 - GR - APPART. LOBBY x1
091 - GR - AIR LOCK-04 x1
092-GR- APP. CORRIDOR1 x1
092'-GR- APP. CORRIDOR2 x1
093-GR- SHOP / ATM x1
119 - GR - APP. KIDS x1
120 - GR - APP. LOUNGE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All

Hourly Analysis Program v5.00 Page 49 of 322


083- GR - APPAR. LOBBY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Cooling T-stat: Occ. .............................................................................. 23.0 °C


Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 50 of 322


085- GR - CLOAK Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ............................................................ 085- GR - CLOAK
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
094 - GR - CLOAK x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 51 of 322


085- GR - CLOAK Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 52 of 322


086- GR- IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name .................................................................... 086- GR- IDF
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
095-GR- IDF x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 53 of 322


086- GR- IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 54 of 322


087- GR- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ................................................................ 087- GR- ELEC
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
096-GR- ELEC x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 55 of 322


087- GR- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 56 of 322


088- GR- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ................................................................ 088- GR- ELEC
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
097-GR- ELEC x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 57 of 322


088- GR- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 58 of 322


089- GR - AHU RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ........................................................ 089- GR - AHU RM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
098-GR- AHU x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 25.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 59 of 322


089- GR - AHU RM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 60 of 322


090- GR - hot KITCHEN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ................................................... 090- GR - hot KITCHEN
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Dehumidification Data:
Maximum RH Setpoint ............................................................................. 55 %
Heating Source ..................................................................................... Any

Central Cooling Data:


Supply Air Temperature ........................................................................ 14.5 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
105 - GR - KIT. HOT KIT. x1
118 - GR - KIT. CORR x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.30 K
Diversity Factor ...................................................................................... 100 %

Hourly Analysis Program v5.00 Page 61 of 322


090- GR - hot KITCHEN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Direct Exhaust Airflow ............................................................................. 0.0 L/s


Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ........................................................... THERMOSTAT


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 62 of 322


091- GR- F. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ......................................................... 091- GR- F. TOILET
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
121 - GR - F.TOILET x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 63 of 322


091- GR- F. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 64 of 322


092- GR- M. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ........................................................ 092- GR- M. TOILET
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
122 - GR - M.TOILET x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 65 of 322


092- GR- M. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 66 of 322


093- GR- M. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ........................................................ 093- GR- M. TOILET
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
123 - GR - M.TOILET x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 67 of 322


093- GR- M. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 68 of 322


094- GR- F. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ......................................................... 094- GR- F. TOILET
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
124 - GR - F.TOILET x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 69 of 322


094- GR- F. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 70 of 322


095- GR- F. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ......................................................... 095- GR- F. TOILET
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
125 - GR - F.TOILET x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 71 of 322


095- GR- F. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 72 of 322


096- GR- M. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ........................................................ 096- GR- M. TOILET
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
126 - GR - M.TOILET x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 73 of 322


096- GR- M. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 74 of 322


097- GR - KIT. ROOM SER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ............................................ 097- GR - KIT. ROOM SER
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 13.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
114- GR -KIT. ROOM SER x1
117 - GR -KIT. ORDER TAK x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)

Hourly Analysis Program v5.00 Page 75 of 322


097- GR - KIT. ROOM SER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 76 of 322


098 - GR - KIT. CHEF OFFICE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ...................................... 098 - GR - KIT. CHEF OFFICE
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
116 - GR -KIT. CHEF OFF x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 22.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 77 of 322


098 - GR - KIT. CHEF OFFICE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 78 of 322


099 - GR - KIT. COLD KITCHEN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ................................... 099 - GR - KIT. COLD KITCHEN
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 11.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
106 - GR - KIT. COLD KIT x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 20.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 19.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ........................................................... THERMOSTAT


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 79 of 322


099 - GR - KIT. COLD KITCHEN Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 80 of 322


100 - GR - KIT. PREPARATION Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name .................................... 100 - GR - KIT. PREPARATION
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 11.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
111 - GR - KIT. MEAT-POU x1
112 - GR - KIT. SEAFOOD x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 20.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 19.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)

Hourly Analysis Program v5.00 Page 81 of 322


100 - GR - KIT. PREPARATION Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 82 of 322


101-1ST- HK Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name .................................................................... 101-1ST- HK
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
129-1ST- HK x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 83 of 322


101-1ST- HK Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 84 of 322


102-1ST- PANTRY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ........................................................... 102-1ST- PANTRY
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 13.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
130 - 1ST - KIT. PANTRY x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 85 of 322


102-1ST- PANTRY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 86 of 322


103-1ST- BUSINESS LOUNG Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name .......................................... 103-1ST- BUSINESS LOUNG
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
132 - 1ST - BUS. LOUNGE. x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 87 of 322


103-1ST- BUSINESS LOUNG Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 88 of 322


104-1ST- CORRIDOR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ...................................................... 104-1ST- CORRIDOR
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
133 - 1ST - CORRIDOR x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 89 of 322


104-1ST- CORRIDOR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 90 of 322


105 -1ST- MEETING Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ......................................................... 105 -1ST- MEETING
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ..................................................................................... 18

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.5 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
136 - 1ST - MEETING 1 x1
Zone 2: Zone 2
137 - 1ST - MEETING 2 x1
Zone 3: Zone 3
138 - 1ST - PLAYFUL MEET x1
Zone 4: Zone 4

Hourly Analysis Program v5.00 Page 91 of 322


105 -1ST- MEETING Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

140 - 1ST - LOUNG x1


Zone 5: Zone 5
141 - 1ST - RLIFTS LOBBY x1
Zone 6: Zone 6
142 - 1ST -LLIFTS LOBBY x1
Zone 7: Zone 7
139 - 1ST -LOUNGE MEET x1
Zone 8: Zone 8
140'- 1ST - MEET CORR. x1
Zone 9: Zone 9
821 - 2ND - MEETING 1 x1
Zone 10: Zone 10
822 - 2ND - MEETING 2 x1
Zone 11: Zone 11
823 - 2ND - PLAYFUL MEET x1
Zone 12: Zone 12
824 - 2ND -LOUNGE MEET x1
Zone 13: Zone 13
825 - 2ND - LOUNGE x1
Zone 14: Zone 14
826 - 2ND - MEET CORR. x1
Zone 15: Zone 15
827 - 2ND - RLIFTS LOOBY x1
Zone 16: Zone 16
828 - 2ND -LLIFTS LOBBY x1
Zone 17: Zone 17
829 - 2ND -CLIFTS LOBBY x1
Zone 18: Zone 18
143 - 1ST - C LIFTLOBBY x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)
1 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
2 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
3 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
4 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
5 24.0 26.7 21.1 18.3 0.83 100 0.0 0.0
6 24.0 26.7 21.1 18.3 0.83 100 0.0 0.0
7 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
8 24.0 26.7 21.1 18.3 0.83 100 0.0 0.0
9 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
10 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
11 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
12 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
13 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
14 24.0 26.7 21.1 18.3 0.83 100 0.0 0.0
15 24.0 26.7 21.1 18.3 0.83 100 0.0 0.0
16 24.0 26.7 21.1 18.3 0.83 100 0.0 0.0
17 24.0 26.7 21.1 18.3 0.83 100 0.0 0.0
18 24.0 26.7 21.1 18.3 0.83 100 0.0 0.0

Thermostat Schedule ........................................................ THERMOSTATE


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................ VAV box

Hourly Analysis Program v5.00 Page 92 of 322


105 -1ST- MEETING Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 93 of 322


106-1ST- F.PRAYER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ........................................................ 106-1ST- F.PRAYER
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
144 - 1ST - F.PRAYER x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.10 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 94 of 322


106-1ST- F.PRAYER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 95 of 322


107 -1ST- F.ABULATION Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ................................................. 107 -1ST- F.ABULATION
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
145 - 1ST - F.ABULATION x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 96 of 322


107 -1ST- F.ABULATION Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 97 of 322


108-1ST- M.PRAYER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ....................................................... 108-1ST- M.PRAYER
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
146 - 1ST - M.PRAYER x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 98 of 322


108-1ST- M.PRAYER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 99 of 322


109 -1ST- M.ABULATION Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ................................................ 109 -1ST- M.ABULATION
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
147 - 1ST - M.ABULATION x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 100 of 322


109 -1ST- M.ABULATION Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 101 of 322


110 -1ST- STAFF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ............................................................. 110 -1ST- STAFF
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Dehumidification Data:
Maximum RH Setpoint ............................................................................. 55 %
Heating Source ..................................................................................... Any

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.5 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
150 - 1ST - STAFF DINING x1
150* - 1ST - DIN SERV x1
151 - 1ST - STAFF CORR. x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.1 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K

Hourly Analysis Program v5.00 Page 102 of 322


110 -1ST- STAFF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Diversity Factor ...................................................................................... 100 %


Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ........................................................... THERMOSTAT


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 103 of 322


111 -1ST- M.PRAYER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ...................................................... 111 -1ST- M.PRAYER
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
152 - 1ST - M.PRAYER x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 104 of 322


111 -1ST- M.PRAYER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 105 of 322


112 -1ST- M.ABULATION Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ................................................ 112 -1ST- M.ABULATION
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
153 - 1ST - M.ABULAT x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 106 of 322


112 -1ST- M.ABULATION Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 107 of 322


113 -1ST- F.PRAYER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ....................................................... 113 -1ST- F.PRAYER
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
154 - 1ST - F.PRAYER x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 108 of 322


113 -1ST- F.PRAYER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 109 of 322


114 -1ST- F.ABULATION Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ................................................. 114 -1ST- F.ABULATION
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
155 - 1ST - F.ABULATION x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 110 of 322


114 -1ST- F.ABULATION Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 111 of 322


115 -1ST- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ............................................................. 115 -1ST- ELEC
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
156 -1ST- ELEC x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 112 of 322


115 -1ST- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 113 of 322


116 -1ST- IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ................................................................ 116 -1ST- IDF
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
157 -1ST- IDF x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 114 of 322


116 -1ST- IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 115 of 322


117 -1ST- AHU Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ............................................................... 117 -1ST- AHU
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
158 -1ST- AHU x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 25.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 116 of 322


117 -1ST- AHU Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 117 of 322


118 -1ST- M.LOCKER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ................................................... 118 -1ST- M.LOCKER
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
159 -1ST- M. LOCKER x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 118 of 322


118 -1ST- M.LOCKER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 119 of 322


119 -1ST- F.LOCKER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name .................................................... 119 -1ST- F.LOCKER
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
160 -1ST- F. LOCKER x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 120 of 322


119 -1ST- F.LOCKER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 121 of 322


121-1ST- F.TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name .......................................................... 121-1ST- F.TOILET
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
162 - 1ST - F.TOILET x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 122 of 322


121-1ST- F.TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 123 of 322


122 -1ST- AHU Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

1. General Details:
Air System Name ............................................................... 122 -1ST- AHU
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
163 -1ST- AHU x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 25.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 124 of 322


122 -1ST- AHU Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:58AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 125 of 322


123-1ST- M.TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name ......................................................... 123-1ST- M.TOILET
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
131 - 1ST - M.TOILET x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 126 of 322


123-1ST- M.TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 127 of 322


124 - 1ST - M. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name ..................................................... 124 - 1ST - M. TOILET
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
166 - 1ST - M.TOILET x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 128 of 322


124 - 1ST - M. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 129 of 322


125 - 1ST - F. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name ...................................................... 125 - 1ST - F. TOILET
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
167 - 1ST - F.TOILET x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 130 of 322


125 - 1ST - F. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 131 of 322


126 -1ST- IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name ................................................................ 126 -1ST- IDF
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
197 -1ST- IDF x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 132 of 322


126 -1ST- IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 133 of 322


127 -1ST- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name ............................................................. 127 -1ST- ELEC
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
168 -1ST- ELEC x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 134 of 322


127 -1ST- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 135 of 322


128 -1ST- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name ............................................................. 128 -1ST- ELEC
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
169 -1ST- ELEC x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 136 of 322


128 -1ST- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 137 of 322


129 -1ST- IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name ................................................................ 129 -1ST- IDF
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
170 -1ST- IDF x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 138 of 322


129 -1ST- IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 139 of 322


130 -1ST- SERVICE LOBBY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name ............................................ 130 -1ST- SERVICE LOBBY
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
171 -1ST- SERVICE LOBBY x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 140 of 322


130 -1ST- SERVICE LOBBY Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 141 of 322


131 -1ST- OFFICES Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name ......................................................... 131 -1ST- OFFICES
Equipment Type ......................................................................... Undefined
Air System Type ................................................................................... VAV
Number of zones ..................................................................................... 15

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ........................................................................ Proportional
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Minimum Airflow ........................................................................................ 0 %
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ..................................... Constant Temperature - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

% Airflow 100 90 80 70 60 50
% kW 100 83 68 54 41 30

% Airflow 40 30 20 10 0
% kW 21 13 7 3 0

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
172 -1ST- OFF. FD x1
Zone 2: Zone 2
173 -1ST- OFF. OFFICE x1
Zone 3: Zone 3
174 -1ST- OFF. CORR x1

Hourly Analysis Program v5.00 Page 142 of 322


131 -1ST- OFFICES Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Zone 4: Zone 4
175 -1ST- OFF. TRAIN D. x1
Zone 5: Zone 5
176 -1ST- OFF. TRAINING x1
Zone 6: Zone 6
177 -1ST- OFF.HR. D. x1
Zone 7: Zone 7
178 -1ST- OFF.HR.ASS. x1
Zone 8: Zone 8
179 -1ST- OFF. OPEN OFF. x1
Zone 9: Zone 9
180 -1ST- OFF. FINANCE x1
Zone 10: Zone 10
181 -1ST- OFF. ASS. x1
Zone 11: Zone 11
182 -1ST- OFF. DIRECTOR x1
Zone 12: Zone 12
183 -1ST- OFF. CASHER x1
Zone 13: Zone 13
184 -1ST- OFF. D. OPER. x1
Zone 14: Zone 14
185 - 1ST - OFF. PANTRY x1
Zone 15: Zone 15
186 -1ST- OFF. DOS M. x1

Thermostats and Zone Data:

T-Stat Direct
Cooling T-Stat Cooling T-Stat Heating T-Stat Heating T-Stat Throttling Diversity Exhaust Direct
Zone Occ. Unocc. Occ. Unocc. Range Factor Airflow Exhaust Fan
(°C) (°C) (°C) (°C) (°C) (%) (L/s) (kW)

1 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0


2 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
3 24.0 26.7 21.1 18.3 0.83 100 0.0 0.0
4 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
5 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
6 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
7 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
8 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
9 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
10 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
11 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
12 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
13 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0
14 24.0 26.7 21.1 18.3 0.83 100 0.0 0.0
15 23.0 26.7 21.1 18.3 0.83 100 0.0 0.0

Thermostat Schedule ........................................................ THERMOSTATE


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type .................................................................. VAV box with RH
Minimum Airflow ................................................................................... 0.00 L/s/person

Reheat Coil Source ............................................................................... Any


Reheat Coil Schedule ..................................................... JFMAMJJASOND

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

Hourly Analysis Program v5.00 Page 143 of 322


131 -1ST- OFFICES Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Peak zone sensible load
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 144 of 322


132 -1ST- SERVER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name .......................................................... 132 -1ST- SERVER
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
187 -1ST- OFF. SERVER x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 20.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 19.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 145 of 322


132 -1ST- SERVER Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 146 of 322


133 -1ST- AHUROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name .................................................... 133 -1ST- AHUROOM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
188 -1ST- AHU x1
189 -1ST- AHURM CORR. x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 25.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)

Hourly Analysis Program v5.00 Page 147 of 322


133 -1ST- AHUROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 148 of 322


134 -1ST- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name ............................................................. 134 -1ST- ELEC
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
190 -1ST- ELEC x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 149 of 322


134 -1ST- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 150 of 322


135 -1ST- IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name ................................................................ 135 -1ST- IDF
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
191 -1ST- IDF x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 151 of 322


135 -1ST- IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 152 of 322


136 -1ST- PUMP ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name ................................................ 136 -1ST- PUMP ROOM
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
192 -1ST- PUMP ROOM x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 25.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 153 of 322


136 -1ST- PUMP ROOM Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 154 of 322


137 -1ST- IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name ................................................................ 137 -1ST- IDF
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
193 -1ST- IDF x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 155 of 322


137 -1ST- IDF Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 156 of 322


138 -1ST- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name ............................................................. 138 -1ST- ELEC
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
194 -1ST- ELEC x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 23.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 157 of 322


138 -1ST- ELEC Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 158 of 322


139 -1ST- PUMP RM CORR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name .......................................... 139 -1ST- PUMP RM CORR
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ............................................................... Return Air Plenum
Wall Heat Gain to Plenum ........................................................................ 30 %
Roof Heat Gain to Plenum ....................................................................... 70 %
Lighting Heat Gain to Plenum .................................................................. 30 %

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
195 -1ST- PUMPRM CORR. x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Hourly Analysis Program v5.00 Page 159 of 322


139 -1ST- PUMP RM CORR Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser
Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 160 of 322


140 -1ST- STORE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name .......................................................... 140 -1ST- STORE
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
196 -1ST- STORE x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 0.83 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 161 of 322


140 -1ST- STORE Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 162 of 322


141 - 1ST - M. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name ..................................................... 141 - 1ST - M. TOILET
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
198 - 1ST - M.TOILET x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00 Page 163 of 322


141 - 1ST - M. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

Minimum Airflow ................................................................................... 0.00 L/s/person

Zone Heating Units:


Zone ........................................................................................................ All
Zone Heating Unit Type ...................................................................... None

Zone Unit Heat Source ......................................................................... Any


Zone Heating Unit Schedule ........................................... JFMAMJJASOND

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Hydronic Sizing Specifications:
Chilled Water Delta-T ............................................................................. 9.0 K
Hot Water Delta-T ................................................................................. 11.1 K

Safety Factors:
Cooling Sensible ...................................................................................... 10 %
Cooling Latent ........................................................................................... 5 %
Heating ...................................................................................................... 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ............................. Sum of space airflow rates
Space Airflow Sizing Method ......................... Individual peak space loads

5. Equipment Data
No equipment data required for this system.

Hourly Analysis Program v5.00 Page 164 of 322


142 - 1ST - F. TOILET Input Data
Project Name: KFUPM LOAD CALCULATION 100% DD for client 12/18/2019
Prepared by: KA 09:59AM

1. General Details:
Air System Name ...................................................... 142 - 1ST - F. TOILET
Equipment Type ......................................................................... Undefined
Air System Type .............................................................. Single Zone CAV
Number of zones ....................................................................................... 1

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control .............................................. Constant Ventilation Airflow
Ventilation Sizing Method ................................ Sum of Space OA Airflows
Unocc. Damper Position .................................................................. Closed
Damper Leak Rate ..................................................................................... 0 %
Outdoor Air CO2 Level .......................................................................... 400 ppm

Precool Coil Data:


Setpoint ................................................................................................ 26.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Coil position ....................................................... Upstream of Mixing Point

Central Cooling Data:


Supply Air Temperature ........................................................................ 12.0 °C
Coil Bypass Factor .............................................................................. 0.100
Cooling Source ..................................................................................... Any
Schedule ........................................................................ JFMAMJJASOND
Capacity Control ............................... Cycled or Staged Capacity - Fan On

Supply Fan Data:


Fan Type ................................................. ASHRAE 90.1 App G Fan Curve
Configuration ............................................................................... Draw-thru
Fan Performance ....................................... 90.1-2010 Appendix G Fan kW
90.1-2010 Baseline Fan Adjustment Factor Components:
Fully ducted and/or exhaust air systems ................................. Not Used
Return and/or exhaust airflow control devices ......................... Not Used
Exhaust filters, scrubbers, or other exhaust treatment ............ Not Used
Particulate Filtration Credit: MERV 9 through 12 ..................... Not Used
Particulate Filtration Credit: MERV 13 through 15 ................... Not Used
Particulate Filtration Credit: MERV 16 and greater,
and electronically enhanced filters .................................... Not Used
Carbon and other gas-phase air cleaners ............................... Not Used
Energy recovery device, or coil runaround loop ...................... Not Used
Evaporative humidifier/cooler in series with another cooling coil Not Used
Sound attenuation section ...................................................... Not Used
Exhaust system serving Fume hoods ..................................... Not Used

Duct System Data:


Supply Duct Data:
Duct Heat Gain .......................................................................................... 0 %
Duct Leakage ............................................................................................ 0 %

Return Duct or Plenum Data:


Return Air Via ...................................................................... Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
199 - 1ST - F.TOILET x1

Thermostats and Zone Data:


Zone ........................................................................................................ All
Cooling T-stat: Occ. .............................................................................. 24.0 °C
Cooling T-stat: Unocc. .......................................................................... 26.7 °C
Heating T-stat: Occ. .............................................................................. 21.0 °C
Heating T-stat: Unocc. .......................................................................... 18.3 °C
T-stat Throttling Range ......................................................................... 1.00 K
Diversity Factor ...................................................................................... 100 %
Direct Exhaust Airflow ............................................................................. 0.0 L/s
Direct Exhaust Fan kW ........................................................................... 0.0 kW

Thermostat Schedule ...................................................... THERMOSTAT(1)


Unoccupied Cooling is .................................................................. Available

Supply Terminals Data:


Zone ........................................................................................................ All
Terminal Type ................................................................................. Diffuser

Hourly Analysis Program v5.00