SPECIFICATIONS
Method: Colorimetric (DR 900)
Range: 0.7 to 10.0 units TSC
Testing Time: 5 minutes
DESCRIPTION
The Nalco Total System Conformance (TSC)
DR 900 Procedure was developed to accurately
measure the level of treatment in your cooling
water system. Reliable and simple, the test makes
it easy to perform the daily analysis needed to
maintain the proper product dosage. The Nalco-
developed method features state-of-the-art
chemistry and is virtually free from common
interferences that can complicate testing.
Start
1 2 3 4
Start Program Fill two sample cells to the Add four drops of TSC-1 Add 2 mL of TSC Indicator
10 mL mark with sample. Solution (460-S0901) to one Solution (460-S0906) to each
749 TSC If sample is not clear, filter of the sample cells. Swirl to sample cell. Swirl to mix.
before testing. mix. This will be the blank.
5 6 7 8
Start TIMER 1 When the timer beeps, Press: ZERO Place the other sample cell
immediately place the blank (prepared sample) into the
A two-minute reaction period into the cell holder and tightly The cursor will move to the
cell holder and tightly cover
will begin. cover the sample cell with right, then the display will
the sample cell with the
the instrument cap. show:
instrument cap.
0.0 TSC
Product Product
Product Factor Product Factor
N-2807T 20 N-7362 50
Read N-2826 20 N-7364 50
N-2827 23.8 N-7365 20
N-2829 40 N-3010 50
N-2896 50 N-3005 19.6
N-2897 50 N-3008 59.5
Press: READ
N-2899 50 3C64 (Canada) 23.8
The cursor will move to the
N-7361 50 3C65 (Canada) 23.8
right, then the result in units
TSC will be displayed.
Ecolab, NALCO and the logos are trademarks of Ecolab USA Inc.