You are on page 1of 3

Total System Conformanxe (TSC)

DR 900 Analytical Procedure AP-14/900

SPECIFICATIONS
Method: Colorimetric (DR 900)
Range: 0.7 to 10.0 units TSC
Testing Time: 5 minutes

DESCRIPTION
The Nalco Total System Conformance (TSC)
DR 900 Procedure was developed to accurately
measure the level of treatment in your cooling
water system. Reliable and simple, the test makes
it easy to perform the daily analysis needed to
maintain the proper product dosage. The Nalco-
developed method features state-of-the-art
chemistry and is virtually free from common
interferences that can complicate testing.

Nalco DR 900 Colorimeter


ORDERING INFORMATION
Order all replacement parts and reagents by their
part numbers. To be sure this product is compatible
with your treatment program, contact your local
Nalco representative. Items marked with an “*” Description Part No.
are included with the kit or set. To place your Nalco DR 900 Colorimeter 400-P0900.88
order, please contact your local customer service Sample cells, 10-20-25 mL
department. w/caps, 6/pkg 500-P2555.88
Cap/pipet/bulb assembly
REPLACEMENT PARTS AND REAGENTS (for 3.4 oz/100 mL TSC Indicator) 500-P2179.88
Required Parts and Reagents
Optional Parts and Reagents
Description Size Part No.
TSC-1 0.85 oz/25 mL 460-S0901.70 Description Part No.
TSC-1 1.7 oz/50 mL 460-S0901.71 Bottle with dropwise tip,
TSC-1 8.5 oz/250 mL 460-S0901.73 2 oz (60 mL) (For TSC-1) 500-P0359.88
TSC-1 16.9 oz/500 mL 460-S0901.74 Bottle with screw cap pipet,
TSC Indicator 3.4 oz/100 mL 460-S0906.72 4 oz (120 mL) (For TSC Indicator) 500-P0346.88
TSC Indicator 16.9 oz/500 mL 460-S0906.74 Thermometer, lab, –10 to 260°C 500-P2020.88
SAFETY PRECAUTIONS INTERFERENCES
Refer to Material Safety Data Sheet (MSDS) for Iron and/or copper above 2 ppm will interfere and
specific reagent personal safety and disposal cause low results.
information.
Strong reducing agents such as H2S or SO3 may
interfere with results, causing them to appear low.
SUPPORT High residual chlorine levels can cause low
If you have any questions regarding this procedure, readings.
please contact your Nalco representative. In North
America you can also contact the Equipment Help
Desk at 630-305-CHEM.

TOTAL SYSTEM CONFORMANCE (TSC) DR 900 PROCEDURE

Special Note: This test must be run prior to slug chlorination.

Start

1 2 3 4
Start Program Fill two sample cells to the Add four drops of TSC-1 Add 2 mL of TSC Indicator
10 mL mark with sample. Solution (460-S0901) to one Solution (460-S0906) to each
749 TSC If sample is not clear, filter of the sample cells. Swirl to sample cell. Swirl to mix.
before testing. mix. This will be the blank.

Note: Sample temperature


should be 24 ± 1°C prior to
reagent addition.
Note: Turbidity has been
reported in the blank
cell and the sample cell
when running the TSC
test. Turbidity in both the
blank cell and sample cell
indicates an interfering
level of zinc. Dilute the
filtered sample and run
the test. The turbidity will
disappear.
Zero

5 6 7 8
Start TIMER 1 When the timer beeps, Press: ZERO Place the other sample cell
immediately place the blank (prepared sample) into the
A two-minute reaction period into the cell holder and tightly The cursor will move to the
cell holder and tightly cover
will begin. cover the sample cell with right, then the display will
the sample cell with the
the instrument cap. show:
instrument cap.
0.0 TSC

Product Product
Product Factor Product Factor

N-2807T 20 N-7362 50
Read N-2826 20 N-7364 50
N-2827 23.8 N-7365 20
N-2829 40 N-3010 50
N-2896 50 N-3005 19.6
N-2897 50 N-3008 59.5
Press: READ
N-2899 50 3C64 (Canada) 23.8
The cursor will move to the
N-7361 50 3C65 (Canada) 23.8
right, then the result in units
TSC will be displayed.

Note: Determine the


Nalco product concentra-
tion using the table by
multiplying the Step 10
reading by the appropriate
factor.

Nalco, an Ecolab Company


North America: Headquarters – 1601 West Diehl Road • Naperville, Illinois 60563 • USA
Nalco Champion – 7705 Highway 90-A • Sugar Land, Texas 77487 • USA
Europe: Richtistrasse 7 • 8304 Wallisellen • Switzerland
Asia Pacific: 2 International Business Park • #02-20 The Strategy Tower 2 • Singapore 609930
Latin America: Av. das Nações Unidas 17.891 • 6° Andar 04795-100 • São Paulo • SP • Brazil
www.nalco.com

Ecolab, NALCO and the logos are trademarks of Ecolab USA Inc.
©2013 Ecolab USA Inc. All Rights Reserved 8/13