0 1 2 3 4 5 6 7 8 9

Power Supply
R R1
Y Y1
B B1
N N1
1 3 5 12 11
-Q1
11 14
/2.2

/2.7

I> I> I>


2 4 6
1 3 5 1 3 5
C31 C32
2 4 6 2 4 6
-X1 1 2 3
U V W
M
3~
PE
RDOL Scheme
SFC Environmental Technologies Pvt. Ltd.
21st Floor, The Ambience Court, Hi-tech Busines Park, Plot No. 2, Sector 19D,
Vashi, Navi Mumbai-400705. INDIA.
Page 1 /2
0 1 2 3 4 5 6 7 8 9
1 2 Control Supply
230V-L
11
3 4 Q1
230V-N /1.0 14
-F1
31
R2
/2.2 34
41
R5
/2.5 44
11
R1
/2.1 12 14
/2.8
STOP
TB 1
X 1
-X3 1 -X3 1
11 -X2 2
OPEN TRQ
TB 1 TB 1 SW FEDD. TB 1 TB 1
14
11 1 11 11 1 11 1 11 12
LPBS 11 11 11 LPBS 11 PLC 11
PLC 11
1 2
SS1 R5 R2
OPEN
R3
CLOSE
R4
CLOSE TRQ R5 OPEN OPEN CLOSE CLOSE CLOSE OPEN
FEDD. FEED. SW FEDD. /2.5
14 /2.5 2 /2.2 14 14 /2.3 4 14 /2.4 4 14 11 14 14 14 4 14 14
X 2
TB 2 TB 2
12 -X2 3 -X2 3 -X3 2 -X3 2
Q1 TB 2
/1.0 11
12 12

Open Feedback

Close Feedback
C2 C1

Auto Feedback

Trip Feedback
/2.7 11 /2.7 11
11 11
R3 R4
14 14
A1 A1
A1 A1 x1 A1 x1 A1 x1 A1 x1
C1 C2
R1 R2 L1 R3 L2 R4 L3 R5 L4 A2 A2
A2 A2 x2 A2 x2 A2 x2 A2 x2 21 21 21 21
R1 R2 R3 R4
/2.1 24 /2.2 24 /2.3 24 /2.4 24
12 11 /2.7 12 11 /2.7
14 11 14 /2.2 1 4 /2.3 1 4 /2.4 1 2 /2.2
12 11 /2.7 21 24 /2.9 11 14 /2.7 11 14 /2.7 12 11 /2.6
21 24 /2.8 31 34 /2.7 21 24 /2.9 21 24 /2.9 41 44 /2.7
-X4 1 2 3 4 5
Digital Input To PLC Panel

Valve Trip

Indication
Valve Trip
Auto/Manual

Valve Open
Indication

Indication

Indication
Valve Close
Valve Open

Valve Close
Mode

Trip
Torque S/W

Torque S/W Trip

CLOSE Contactor
OPEN Contactor
Note:
1. Selection of MPCB (Qxx) and Contactor (Cxx) shall be as per Type-2 co-ordination.
2. Control supply MCB (Fxx) selection shall be done as per current requirement of contactor coil.
RDOL Scheme
SFC Environmental Technologies Pvt. Ltd.
21st Floor, The Ambience Court, Hi-tech Busines Park, Plot No. 2, Sector 19D,
Vashi, Navi Mumbai-400705. INDIA.
Page 2 /2