Professional Documents
Culture Documents
Technical Battery: For Valve Acid (VRLA)
Technical Battery: For Valve Acid (VRLA)
Section-2
Technical Specifications for valve Regulated Lead Acid (VRLA) battery
2.0Introduction
This section specifies_ the technical requirements of 48 V/50V Valve Regylated Lead
Aoid (VRLA)
batteries, which shall be used for meeting the backup requirementr ir Telecom
eq'ipment i.e.
DWDM Equipment, SDH Equipment, Optical Line Amplifier, Regenerator/Repeater, Network
Management Systern (NMS) and other associated equipment located indoor at substations
Repeater/Amplifier locations etc.
The detailed BoQ is provided in the appen<lices. The Contractor shall furnish technical details along
with all arrangemenl,s and supporting structures, for each type of VRLA lbattery bank during detail
engineering.
2.1 Batteries
VRLA Storage batteries designed for continuous operation shall be provided as iclentif,red in
Appendices. Battery sets shall be maintenance free, sealed type and in thermoplastic containers.
The batteries shall jinclude battery mounting racks, and other equipment requlred t6 provide a
complete operational battery subsystem. The average ambient temperature shall be :lj"C. The
Bidder shall submit temperature vis-d-vis life curve along with the bid. The offered lbattery sets
shall be compact arrd shall require no ri:gular maintenance. All safety equipment required for
installation shall be prrovided by the Contra,ctor.
The batteries to be installed at Communir;ation nodes in PoP, Substation and Repeaterr locations
shall have the minimum capacity as indicarted in Appendices. Battery stacking shall be done with a
view to optimize floor space and loading. The Contractor shall provide the necessary installation
arrangements including grouting, base frames etc.
The Batteries shall be offered from a'|EC/BSNL QA/ RDSO approved manufacturer who has been
manufacturing VRLI\ batteries for the las1. two (2) years and at least tenL (10) numbers of VRLA
batteries of 48V, 300AH or higher capacity manufactured by such manufacturer should have in
satisfactory operation for at least one (1) year as on the originally scheduled date of bid opening.
Depending upon the location, the batteries of different rating may be required as specified in the
Appendices. Battery bank shall be formed as follows:
o Battery bank of 48V shall be formed by connecting 24 nos 2V (nominal) cells of the rated
2-1
Power Grid Corporation of India Ltd.
Technical Specification for Battery package
capacity in series.
o BatterY bank of 50V shall be forned by connecting 25 nos 2V (nominal)
cells of the rated
capacity in sieries
ng the cells/batteries shall be responsible to replace/repair free of charge,
faulty, owing to defective workmanship or material u, pe, the provisiolns
drawing may change for each site based on site constraints. Site wise GA drawing shall
be
submitted for each type of battery bank basred on site survey reports for Ernployer's approval.
2.1.3.1 Containers
The container matet'ial shall have chemical and electro-chemical compatibility and shall be acid
resistant. The material shall meet all the requirements of VRLA batteriei and be consistent with the
life of battery. The container shall be fire retardant and shall have an Oxygen Index of atleast2So/o.
The porosity of the container shall be suoh as not to allow any gases to escape except from the
regulation valve. The tensile strength of the material of the container shall be such as to handle the
internal cell pressurer of the cells in thLe worst working condition. Cell shatl not show any deformity
or bulge on the sides under all working conditions. The container shall be capable of withstanding
the rigours of transport, storage and handling. The containers shall be enclosed in a steel tray.
2.1.3.3 Separators
The separators usecl shall be ofglass mat or synthetic material having high acid absorption
capability, resistant 1o sulphuric acid and good insulating properties. The design of separators shall
ensure that there is no misalignment during normal operation and handling.
1 '')
Power Grid Corporation of India Ltd.
Technical Specification for Battery package
Nuts and bolts for c,onnecting the cells shall be made of copper, brass or stainless steel. Copper or
brass nuts and bolts shall be effectively lead coated to prevent corrosion. Stainless steel bolts and
nuts can be used without lead coating,
When working as a battery, failure of one or two cells shall not cause the failure of battery and
battery should be able to provide uninterrupted rated power to the load.
Depth of Discharge (DOD) is defined as the ratio of quantity of electricity (in Amphere-hour)
removed from a cell or battery on discharge to its rated capacity.
'\) z-J
lG/ I
Power Grid Corporation of India Ltd.
Technical Specification for Battery package
The capacity of the llattery at rate of discharge other than 10 hour disch ar14e rate shall be as given in
the table 2.1 below:
Table- 2.1
Rate of Discharge
Capacity expressed as oh of
Capacity at rate CllD
End cell voltage
ctr 50.0 r.70
c12 f,J.J r.70
ct3 '7t.7 |.74
cl4 '78.2 t.74
ct5 i33.3 r.7s
c/8 9s.0 1 .75
cl20 120.0 r.7 5
The battery shall be capable of being recharged from the fully exhausted condition (1.75Vlcell) at
the specified float voltage. The battery design shall permit the charging of the battery at2.45YlceII
(when two cells shofted). All the cells in aLbattery shall be designed for continuous float operalion
at the specified float voltage throughout the life. Float voltage of each cell in the string shall be
within 0.05V of the average float voltage/cr:ll.
The battery voltage shall not be less than the following values, when a fully charged battery is put to
discharse at Cll0 rat'e:
The bidder shall provide the Tables & Graphs showing relation of the closed circuit voltage,
impedance and the residual capacity of eaLch cell in the battery, when it is discharged to the end
voltage of l.T5Ylcell at C/10 and C/8 rate of discharge. A table and graph showing the relation
' 2-4
.,
^l',
Power Girid Corporation of India Ltd.
attery Package
Throughout its life, in the operating condition of C/10 rate of charge and C/8 rate of discharge in
average ambient ternperature of 35o Celsius, shedding of battery active material shall not lead to
short circuit. The growth of positive plate r;hall be less thanS%o of the total plate area throughout the
specified life.
While operating in the normal operating conditions, the cell or battery shall not lead to dry out,
throughout the life of the battery. Manufacturer shall supply the necess ary data to supporl. the
requirement. The battery shall not exhibit thermal *nu*uy *hile working in tfre urr".ug. ambient
temperature of 35' C, operating range of Cr to 50 'C and at a charge rate of CllO and, discharge rate
of C/8.
f [l \ 2-5
J il.1
Power Cirid Corporation of lndia Ltd.
Technical Specification for Battery package
Section-3
Technical Specifications for
Lithium lon batterv
3.0 Introduction
This section specifies the technical requirerments of 48 V Lithium Ion batteries,
which shall be used
for meeting the backup requirements of Telecom equipment i.e. DWDM Equipment, SDH
Equipment, Optical Line Amplifier, Regenerator/Repeater, Network Meuragement System
O1MS)
and other associated equipment located in<loor at substations, Repeater/Amplifier locations
etc.
The Lithium Ion battery shall meet the requirements specified in the TEC GR/TX/LIB-001/01.
MAR-16 Standard.
3.1 Batteries
Lithium ion Storager batteries designed for continuous operation shall be provided as identified in
Appendices. The system shall employ a modular configuration to provide flexibility, keeping in
view the future bacl<up requirement. Batrleries are required to have all the necessaries electronics
and intelligence built into it to ensure that battery performs in the safest and proper manner with
existing power planrt. These batteries shall be charged normally at 0.5C rate ('C' wherever used in
this document, stand for the capacity of cell/module) in a constant current/constant voltage charge
mode. Maximum Charging rate shall tre specified by the manufacturer. All other required
Charge/discharge management parametersi of battery module shall be provided by Contractor for
parameters matching with switched-mode power supply (SMPS). The battery is normally not
allowed to discharge beyond 80% of C (rated capacity).The discharge rate for these batteries is
between 0.5C to 1 C up to 80% of its rated capacity, depending on application requirements.
The operating Temperature range of battery should be -10o C to 60o C. The Contractor shall furnish
submit temperature vis-d-vis life curve during detailed engineering. The offered battery sets shall be
compact and shall require no regular maintenance. All safety equipment required for installation
shall be provided by the Contractor.
The batteries to be installed at Communication nodes in PoP, Substation and Repeater local.ions
shall have the minirnLum capacity as indical.ed in Appendices.
The Batteries shall be offered from manul'acturer who has been manufacturing Li-ion batteries for
the last two (2) years and at least ten (10) numbers Li-ion batteries of 48V, 50AH or higher capacity
manufactured by such manufacturer shoulclhave in satisfactory operation for at least one (1) year as
on the originally scheduled date of bid opening.
3-1
a
^,\
Power Grid Corporation of India Ltd.
Technical Specification for Battery package
48V Battery module shall be formed by connecting up to 15 nos. cell each having nominal
voltage
as 3V or above of the rated' capacrty in series to form modules subject to
compliance of clause 3.5
& 3.7 ( design practice & cell matching claLuse) . To achieve required capacity as mentioned in IlOe
paralleling of the rnodule is permitted only with an electronic coniroller like parallel
Battery
management system to maintain state of charge (SOC) between parallel connected modules.
The
manufacturer supplying the battery module shall be responsible to replace/repair free of charge,
the
battery/cell becoming faulty, owing to de1'ective workmanship or material u, p.1" the provisio's
of
the bid document.
3.1.3 ConstructionalRequirements
The design of battery shall be as per field proven practices. Lithium Iron Phosphate (LiFepO4) or
equivalent should be used as active material. The paralleling of cells within the module is not
permitted. The paralleling of modules for enhancement of capacity is permitted. The offered battery
module rating should not be less than 50AH. The contractor shall provide minimum two no of
modules for achieving rated capacity. The Battery module shall be so designed as to be suitable for
Horizontal, Vertical and handstand position, can be installed in 19" cabinet along with parallel
battery management. Any installation position & method shall be as per requirement to ensure space
and floor loading requirement. The stacking arrangement shall be such that end terminals of baitery
shall be top two adjacent modules on the same side of stack to minimize voltage drop from power
plant.
3.1.3.1 Containerri
The cell shell made of aluminum metal or equivalent subjected to safety standard are met. It shall be
capable to meet all r'equirements of lithiuna cell and be consistent with the life of battery. The cell
shell shall be in rigid casing of sufficient strength to prevent flexing.
The module containrlr made of painted gallvanized sheet or equivalent shall be capable to meet all
the requirements of I-ithium ion battery and be consistent with the life of battery. Both cell shell and
module container materials shall have chemical and electro-chemical compatibility and shall be acid
resistant. The container shall be symmetrical in shape and stand level on the plane level surface.
The internal area o1' cell shell has sufficient provision for expansion of +ve plate. The module
container shall be fire retardant and shall have an Oxygen Index of at least 28% & should comply
UL-94 V-0 for this purpose. The porosity of the container shall be such as not to allow any gases to
escape except from lhe release valve. The tensile strength of the material of the container shall be
such as to handle the internal cell pressure of the cells in the worst working condition. Module shall
not show any deformity or bulge on the sides under all working conditions. The container shall be
capable of withstanding the rigours of transport, storage and handling. The materials of container
t\ 3-2
,"/]
0
-l
Power Grid Corporation of India Ltd.
Technical Specification for Battery package
3.1.3.4 TerminallPosts
Both the *ve and -ve terminals of the cells/module shall be capable of proper termination and shall
ensure its consistency with the life of the battery. The surface of the.terminal post extending above
the cell/module cover including bolt hole shall be coated with an acid resistant and corrosion
retarding material. Terminal posts or any other metal part which is contact with the electrolyte shall
be made of the sarne alloy as that of ther plates or of a proven material that does not have any
harmful effect on cell/module performirnce. Both +ve and -ve posts shall be clearly and
unambiguously identifiable. The terminal post & its sealing shall be capable to withstand the heat
generated in cell/module during external short circuit condition.
Nuts and bolts for c;onnecting the cells strall be made of copper for -ve and aluminium for *ve
Stainless steel bolts nuts and washers can be used.
The cell/module shall not explode or discharge or burn when an electro-static discharge of 8KV
applied to any of its part exposed to contactt. It shall be tested in accordance with IEC-61000-4-2.
aa
J-J
Power Grid Corporation of India Ltd.
Technical Specification for Battery package
Depth of Discharger (DoD) is defined as the ratio of quantity of electricity (in Ampere-hour)
removed from a cell or battery on discharge to its rated capicity.
3.1.6 Capacityllequirements
When a cell is discharged at Cl5 rate, it shall deliver 100%o of C (rated capacity, corrected at
25'Celcius) before the cell voltage reaches end cell voltage specified bymanufacturer
In case of module, it shall deliver 90o/o ctf C (rated capacity, corrected at 25oCelcrus) before
the
module voltage reaches 45V, when discharged at Cl5 rate. The capacity (cogected at 25"Celcius)
shall also not be less than C and not more than l20o/o of C when dischargl to the voltage of 42y.
The capacity of the cell/module at discharge rates Cl2.to Cl20 shall be as given in the table2;t
below:
Table- 2.1
Cell Module
Capacity End cell Discharge Capacity End cell
expressed voltage current expressed voltage
Rate of Discharge as "/" of as o/" of
Discharge current Capacify Capacity
at rate at rate
ct5 c/10
cl2 0.5c 97.6 2.5 42V
ct3 0.33C 99.r 2.5 0.333C 99.r 42V
ct4 0.25C 99.2 2.5 0.2sc 99.2 42Y
cts a.2c 100 2.5 0.2c 100 42V
c/8 0.125C 100 2.5 0.125c 100 42V
clr0 0.1c 100 2.5 0.1c 100 42V
cl20 0.05c 100 2.5 0.0sc 100 42V
The module shall be capable of being rechirged from the fully exhausted condition (42Ylmodule) at
the specif,red charge voltage. The modute design shall permit the charging of the module at
54Vlmodule, in cons;tant current and constant voltage charging mode. Charging and discharging of
the module at slow rate of Cl72 and ClI20 shall not affect life and performance of module and shall
not lead to capacity loss forever.
The cell/module voh.age shall not be less tlhan the following values, when a fully charged battery is
put to discharge at Cl5 rute:
3-4
is,
Power Grid Corporation of India Ltd.
Technical Specification for Battery package
The bidder shall provide the Tables & Graphs showing relation of the closed circuit voltage,
impedance and the residual capacity of ear;h module/celt in the battery string, when it is discharg-ed
to the end voltage o1 42Y lmodule at Cl20,tCll0,Cl8,Cl6,Cl5,Cl3 and, Cl2 rate of discharg e,2.5y l6ell
or 42Ylmodule at C'4 & C3 rate A table arLd graph showing the relation between the impedance and
residual capacity of each cell or module shall also be provided by the bidder.
When the battery is put to load at Cl3, inrmediately after taking it off from the float, the voltage of
any of the cell in the battery shall not fall below 3V, throughout the battery life. In case of modirle it
shall not fall below zITY rnthe above condiitions.
Loss in capacity during storage at an averclge ambient temperature of 35oC for a period of 6 months
shall not be more tlnn 20o/o and the cell/module shall achieve 95o/o of its rated capacity wittrin 2
charge/discharge cyr:les and full rated caparcity within 3 cycles, after the storage period of 6 months.
Voltage of each cell in the battery set shall be within 0.05V of the average voltage throughout the
storage period. Amp,sls hour efficiency shall be better than95%o and watt hour efhciency shall not
be less than9}Yo.
3.1.9 Conductanr:ematching
Conductance matching of each cell/ cell nnodule in the battery, when connected in series, shall be
within +l- 15yo of the average cell conductance. Also when the cell are connected in parallel to lbrm
a cell module, the conductance of all the cell in the cell module shall be within +l-I5% oi the
average conductance of the cells of the module. The conductance matching test certificate shall be
obtained from any recognized or accreditecl lab.
3-5
Power Grid Corporation of India Ltd.
Technical Specification for Battery Package
3.1.10 Standard discharge & charge current (A): 0.5C at a temp. 25 degree C and humidity
55+i-5% RII.
3.1.16 ChemicallRequirements
While operating in the normal operating conditions, the cell/module or battery shall not lead to
dry
out, throughouithe life of the battery. Manufacturer shall supply the necessary data to
support the
requiremeit. The cell/modul elbattery shall not exhibit thermal runaway while working in the
uu.rug. ambient temperature of 35o i, operating range of -10 to 60 "C and at a charge
rate of Ol2 '
i) Electrical SafetY
ii) Mechanical SafetY
iii)Operational Safety (Environmental testing)
iv) Projectile
reports'
Contractor shall carry out the above safety tests or submit the previous test
3-6
\ ^\'
Power Grid Corporation of India Ltd.
Technical Specification for Battery package
It should have all the necessary electronics and intelligence built into it so as to ensure that the
battery performs in the safest and proper rnanner without any communications with existine
SMpS
based power plant.
A BMS may also feature a pre-charged system allowin6; a safe way to connect the battery loads and
eliminating the excerssive inrush currents to load capacitors. The connection to load shall normaly
controlled through Solid state or Electronic switches.
3-7
Power Grid Corporation of India Ltd
Technical Specification for Battery package
3-8
Power Cirid Corporation of India Ltd.
Technical Specification for Batterv
3.1.18.10 LED/LCID to be provided for power, activity and fault status in BMS
i. Shuffling energy from the most charged cells to the least charged cells (balancers)
ii. Reducing the charging current to a sufficiently low level that will not damage fully charged
cells, while less charged cells may r;ontinue to charge.
iii. Modular charging
3-9