FIRE RESISTANT CABLE 600V

Low-Smoke Halogen-Free Jacket Fire Barrier


Tape

Applications
This cable is designed for areas where
the integrity of the electrical circuit is
Low-Smoke Halogen-Free critical in maintaining power supply.
Insulation Applications can be found in emergency
Specifications lightings, control and power circuits,
BS 6387 Copper power stations, fire alarm systems,
Conductor
IEC 60331 underground tunnels, communication
Phelps Dodge Specification systems, sewage treatment plants, lifts,
escalators, and high-rise buildings.
Voltage Rating
0.6/1 kV
Construction
Plain-annealed copper conductor
Insulation Color Fire barrier tape
Natural
Low-smoke halogen-free insulation
Low-smoke halogen-free jacket
Jacket Color
Orange

Conductor Wall thickness


Approximate
Construction (nominal)
Cable
Size Fire Barrier Cable Cable Ampacity
No. of Diameter Insulation Jacket
Tape diameter weight
strand
mm² mm mm mm mm mm kg / km A
2.0 7 1.8 0.145 0.7 1.4 7.1 73 25
3.5 7 2.3 0.145 0.7 1.4 7.7 95 30
5.5 7 2.9 0.145 0.7 1.4 8.3 120 40
8.0 7 3.5 0.145 0.7 1.4 8.9 149 55
14 7 4.7 0.145 0.7 1.4 10.1 220 70
22 7 5.9 0.145 0.9 1.4 11.6 317 90
30 7 6.7 0.145 0.9 1.4 12.5 393 115
38 7 7.8 0.145 0.9 1.4 13.6 490 130
50 19 8.8 0.145 1.0 1.4 14.8 602 150
60 19 9.8 0.145 1.0 1.5 15.9 726 170
80 19 11.2 0.145 1.1 1.5 17.6 930 205
100 19 12.7 0.145 1.2 1.6 19.3 1,160 225
125 37 14.4 0.145 1.2 1.6 21.3 1,443 265
150 37 15.7 0.145 1.4 1.7 23.1 1,728 295
200 37 17.8 0.145 1.6 1.8 25.8 2,186 355
250 37 19.8 0.145 1.7 1.9 28.6 2,775 400
325 61 22.9 0.145 1.8 2.0 31.6 3,496 470
400 61 25.5 0.145 2.0 2.1 34.9 4,315 515
500 61 28.2 0.145 2.2 2.2 38.1 5,221 580

+Diagrams of cables are illustrative only and not necessarily to scale. PDP reserves the right to change or vary the construction of any of their products
without notice. While every care has been taken in the preparation of this data sheet, PDP accept no liability of any kind and are not responsible for the
results on any actions taken on the basis of this information or resulting from errors or omissions. This technical data sheet is intended as a guide only;
any person using it must make reference to the appropriate local standards or authorities.