Professional Documents
Culture Documents
CHAPTER 16
Hot Weather Concreting
315
Chap. 16 (2010).qxd:EB001 (2010) 1/27/11 3:45 PM Page 316
establish the relationship for the property of interest as a • organize a preconstruction conference to discuss the
function of time at various concrete temperatures. This precautions required for the project
process will establish the maximum allowable time to • use materials and mix proportions that have proven
discharge concrete after batching for various concrete performance in hot-weather conditions (lower
temperatures. cement contents, and set retarding admixtures)
Setting a maximum concrete temperature is not a guar- • cool the concrete or one or more of its ingredients
antee of strength or durability. For most work it is too (Figure 16-1)
complex to simply limit only the maximum temperature • use a concrete consistency (slump) that allows rapid
of concrete as placed; circumstances and concrete require- placement and consolidation
ments vary too widely. For example, a temperature limit • reduce the time of transport, placing, and finishing as
that would serve successfully at one jobsite (such as in a much as possible so as to reduce and minimize
cooler climate) could be highly restrictive at another (such waiting time
as in a warmer climate). The inverse could occur if con- • schedule concrete placements to limit exposure to
crete mixtures that were designed for hot-weather condi- harsh atmospheric conditions. Consider night or
tions were placed in cooler ambient conditions. more favorable weather conditions
Atmospheric conditions, including air temperature, rela- • consider methods to limit moisture loss during
tive humidity and wind speed, in conjunction with site placing and finishing, such as sunshades, wind-
conditions influence the precautions needed. For example, screens, fogging, or spraying
flatwork done under a roof that blocks solar radiation • apply temporary moisture-retaining films to control
with exterior walls in place that screen the wind could be evaporation after strike-off and prior to finishing
successfully completed using a concrete with a high tem- concrete
perature. However, this concrete would cause difficulty if
placed outdoors on the same day where it would be ex- The above precautions are discussed in further detail
posed to direct sun and wind. Additionally, placement of throughout this chapter.
concretes with a vulnerable surface to volume ratio such
as thin overlays with relatively high cementitious contents Effects of High Concrete Temperatures
require special care.
As concrete temperature increases there is a loss in slump
that is often compensated for by adding water to the con-
crete at the jobsite. At higher temperatures a greater amount
of water is required to hold slump constant than is needed
at lower temperatures. The addition of water results in a
higher water-cement ratio, thereby lowering the strength at
all ages and adversely affecting other desirable properties
of the hardened concrete. This is in addition to the adverse
effect on strength at later ages due to the higher tempera-
ture, even without the addition of water.
316
Chap. 16 (2010).qxd:EB001 (2010) 1/27/11 3:45 PM Page 317
Concrete temperature, °F 15
Mix proportions held constant.
40 60 80 100
310 Initial set
Cement A
12 Final set
180 Initial set
300 Cement B
Final set
Time, hours
9
Water content, kg/m3
280 3
32°
Figure 16-3. This shows that the setting time can be re- C(
05°F
80 )
duced by 2 or more hours with a 10°C (18°F) increase in
°C (1
°F)
41
concrete temperature. Concrete should remain plastic long
49°C
(120
enough so that each layer can be placed without devel- 60
opment of cold joints in the concrete. Set retarding ad-
mixtures, ASTM C494, Standard Specification for Chemical 40
Curing: specimens cast
Admixtures for Concrete (AASHTO M 194) Type B, and and moist-cured at
temperature indicated
hydration control admixtures can be beneficial in offset- for first 28 days. All
20
ting the accelerating effects of high temperature. moist-cured at 23°C
(73°F) thereafter.
In hot weather, there is an increased tendency for cracks 0
to form in both the fresh and hardened concrete. Rapid 1 3 7 28 90 365
evaporation of water from freshly placed concrete can Age of test, days
cause plastic-shrinkage cracks before the surface has hard- Figure 16-4. Effect of high concrete temperatures on compressive
ened (see Plastic Shrinkage Cracking). Cracks may also strength at various ages (Klieger 1958).
develop in the hardened concrete because of increased
drying shrinkage due to higher water contents or thermal strengths are lower. If the water content had been increased
volume changes as the concrete cools (see Chapter 10). to maintain the same slump (without increasing cement
content), the reduction in strength may have been even
Air entrainment is also affected in hot weather. At elevated
greater than shown.
temperatures, an increase in the amount of air-entraining
admixture dosage is generally required to produce a given The proper fabrication, curing, and testing of compression
entrained air content. test specimens during hot weather is critical. Steps should
be taken to assure ASTM C31, Standard Practice for Making
Figure 16-4 shows the effect of high initial concrete tem-
and Curing Concrete Test Specimens in the Field (AASHTO
peratures on compressive strength. The concrete tempera-
T 23) procedures are followed regarding initial curing
tures at the time of mixing, casting, and curing were 23°C
of strength specimens for acceptance or quality control
(73°F), 32°C (90°F), 41°C (105°F), and 49°C (120°F). After
testing at 16ºC to 27ºC (60ºF to 80ºF). If the initial 24 hour
28 days, the specimens were all moist-cured at 23°C (73°F)
curing is at 38ºC (100ºF), the 28-day compressive strength
until the 90-day and one-year test ages. The tests, using
of the test specimens may be 10% to 15% lower than if
identical concretes of the same water-cement ratio, show
cured at the required ASTM C31 (AASHTO T 23) curing
that while higher concrete temperatures give higher early
temperatures (Gaynor, Meininger, and Khan 1985).
strength than concrete at 23°C (73°F), at later ages concrete
317
Chap. 16 (2010).qxd:EB001 (2010) 1/27/11 3:45 PM Page 318
Specimens cured in the field in the same manner as the 0.22 (TaMa + Tc Mc) + Tw Mw + TwaMwa
structure more closely represent the actual strength of T=
0.22(Ma + Mc) + Mw + Mwa
concrete in the structure at the time of testing. However,
test specimens give little indication of whether a deficiency Where:
is due to the quality of the concrete as delivered or to T = temperature of the freshly mixed concrete, °C (°F)
improper handling and curing. On some projects, field-
cured specimens are made in addition to those destined Ta, Tc, Tw, and Twa = temperature in °C (°F) of aggregates,
for controlled laboratory curing. These are especially cement, added mixing water, and free water on aggregates
useful when the weather is unfavorable, to determine Ma, Mc, Mw, and Mwa = mass, kg (lb), of aggregates,
when forms can be removed, or when the structure can cementing materials, added mixing water, and free water
be put into use. For more information see Chapter 18. on aggregates
Example calculations for initial concrete temperature are
Cooling Concrete Materials shown in Table 16-1.
79,917
Initial concrete temperature = 2515 = 31.8°C
To achieve 1°C reduction in initial concrete temperature:
2515
Cement temperature must be lowered = = 8.2°C
308
2515
Or water temperature dropped = 515 = 4.9°C
2515
Or aggregate temperature cooled = 1692 = 1.5°C
* Total kilojoules are relative to a baseline of 0°C.
318
Chap. 16 (2010).qxd:EB001 (2010) 1/27/11 3:46 PM Page 319
Mixing-water temperature, °F
90°
Ice
2 9°
70
F)
20
85°
F)
10 50
F)
319
Chap. 16 (2010).qxd:EB001 (2010) 1/27/11 3:46 PM Page 320
Table 16-2B. (Inch-Pound Units). Effect of Ice (75 lb) on Temperature of Concrete
Specific heat Btu to vary Initial temperature Total Btu
Material Mass, M, kg Btu / lb • R temperature, 1°F of material, T, °F in material**
(1) (2) (3) (4) (5)
Col. 1 x Col. 2 Col. 3 x Col. 4
Cement 564 (M c) 0.22 124 150 (Tc) 18,600
Water 207 (Mw) 1.00 207 80 (Tw) 16,560
Total aggregate 3100 (Ma) 0.22 682 80 (Ta) 54,560
Ice* 75 (M i ) 1.00 75 32 (T i ) 2,400
1088
minus 75 (M i ) x heat of fusion, (144 Btu/lb) = –10,800
81,320
81,320
Concrete temperature = = 74.7°F
1088
*32 M i – 144 M i = – 112 M i
**Total Btu are relative to a baseline of 0°F.
Figure 16-6 shows crushed ice being charged into a truck Liquid Nitrogen
mixer prior to the addition of other materials. Mixing time If a greater temperature reduction is required, the injection
should be long enough to completely melt the ice. The of liquid nitrogen into the mixer may be the best alterna-
volume of ice generally should not replace more than tive method. Liquid nitrogen can be added directly into a
approximately 75% of the total batch water. The maxi- central mixer drum or the drum of a truck mixer to lower
mum temperature reduction from the use of ice is limited concrete temperature. Figure 16-1 shows liquid nitrogen
to about 11°C (20°F). added directly into a truck mixer near a ready mix plant.
This may also be added at the jobsite.
320
Chap. 16 (2010).qxd:EB001 (2010) 1/27/11 3:46 PM Page 321
during injection can be determined through the use of an times while measuring slump loss over time have been
infrared thermometer aimed at the bottom of the drum. helpful in verifying that certain dosages of admixtures will
perform properly in the field.
Cement
Cement temperature has only a minor effect on the tem- Preparation Before Concreting
perature of the freshly mixed concrete because of cement’s
low specific heat and the relatively small amount of
cement in a concrete mixture (ACI Committee 305). A Before concrete is placed, certain precautions should be
cement temperature change of 4°C (8°F) generally will taken during hot weather to maintain or reduce concrete
change the concrete temperature by only 0.5°C (1°F). temperature. Mixers, chutes, conveyor belts, hoppers,
Because cement loses heat slowly during storage, it may pump lines, and other equipment for handling concrete
still be warm when delivered (this heat is produced in should be shaded, painted white, or covered with wet
grinding the cement clinker during manufacture). Cement burlap to reduce the effect of solar heating.
temperatures in storage silos at ready-mix plants are often Forms, reinforcing steel, and subgrade should be wetted
greater than 50°C (120°F) even in cold weather conditions. with cool water just before the concrete is placed. During
Since the temperature of cement affects the temperature placing and finishing operations, fogging can be directed
of the fresh concrete to some extent, some specifications over the concrete surface. This not only cools the contact
place a limit on its temperature at the time of use. This surfaces and surrounding air but also increases its relative
limit varies from 66°C to 82°C (150°F to 180°F). However, humidity. The increase in relative humidity minimizes the
it is more practical to specify a maximum temperature for rate of evaporation of water from the concrete after place-
freshly mixed concrete rather than place a temperature ment. For slabs on ground, it is a good practice to moisten
limit on individual ingredients (Lerch 1955). the subgrade the evening before concreting. There should
be no standing water or puddles in the forms or on the
subgrade when concrete is placed.
Supplementary Cementitious Materials
During extremely hot periods, improvements may be ob-
Many concrete producers consider the use of supplemen- tained by restricting concrete placements to early morning,
tary cementitious materials (SCMs) to be essential in hot late evening, or nighttime hours, especially in arid climates.
weather conditions. The materials of choice are fly ash and This practice has resulted in substantially less thermal
other pozzolans (ASTM C618, Standard Specification for shrinkage and cracking of thick slabs and pavements.
Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use in
Concrete or AASHTO M 295) and slag cement (ASTM C989, Transporting, Placing, and Finishing
Standard Specification for Slag Cement for Use in Concrete
and Mortars or AASHTO M 302). Chapter 4 discusses the Transporting and placing concrete should be completed
impact of each SCM on the water demand and heat of as quickly as practical during hot weather. Delays con-
hydration. These materials generally slow both the rate of tribute to slump loss and an increase in concrete temper-
setting and the rate of slump loss. However, some caution atures. Sufficient labor and equipment must be available
regarding finishing is needed. The rate of bleeding can be at the jobsite to handle and place concrete immediately
slower than the rate of evaporation and plastic shrinkage upon delivery.
cracking or crazing may result. This is discussed in greater
detail under Plastic Shrinkage Cracking. Prolonged mixing, even at agitating speed, should be
avoided. If delays occur, stopping the mixer and then
Chemical Admixtures agitating intermittently can minimize the heat generated
by mixing. ASTM C94 (AASHTO M 157) requires that
discharge of concrete be completed within 90 minutes or
A set retarding admixture may be beneficial in delaying before the drum has completed 300 revolutions, which-
the setting time in hot weather concreting, despite the ever occurs first. However, these restrictions may be ex-
potential for increased rate of slump loss resulting from tended under certain conditions (ACI 301-10). During
their use. A hydration control admixture or set stabilizer hot weather the time limit may be reduced to 60 minutes
can be used to stop cement hydration and setting. Hydra- or even 45 minutes. If specific time limitations on the
tion is resumed, when desired, with the addition of a completion of discharge of the concrete are desired, they
special accelerator (reactivator). should be included in the project specifications. It is also
Set retarding admixtures should conform to the require- reasonable to obtain test data from a trial batch simulating
ments of ASTM C494 (AASHTO M 194) Type B. Admixtures the batch to placement time, mixing conditions, and anti-
should be tested under job conditions before construction cipated concrete temperatures to document, if necessary,
begins; this will determine their compatibility with the a reduction in the time limit.
other concrete ingredients. Trial mixtures that simulate the Since the setting of concrete is more rapid in hot weather,
anticipated temperatures as well as haul and placement extra care must be taken with placement techniques to
321
Chap. 16 (2010).qxd:EB001 (2010) 1/27/11 3:46 PM Page 322
avoid cold joints. For placement of walls, shallower layers Plastic shrinkage cracking is usually associated with
can be specified to assure enough time for consolidation hot-weather concreting; however, it can occur any time
with the previous lift. Temporary sunshades and wind- ambient conditions produce rapid evaporation of mois-
breaks help to minimize cold joints. ture from the concrete surface. These cracks occur when
water evaporates from the surface faster than it can travel
While proper consolidation is critical to concrete place- to the surface during the bleeding process. This condition
ment, overvibration with internal vibrators should be
creates rapid drying shrinkage and tensile stresses in the
avoided. Internal vibrators produce significant amounts of
surface that often result in short, irregular cracks. The
heat and can raise the temperature of the concrete locally
following conditions, individually or collectively, increase
by 10°C (18°F) or more during a 10 second insertion
(Figure 16-7) (Burlingame 2004). evaporation of surface moisture and also increase the
possibility of plastic shrinkage cracking:
1. High cementitious materials content
26.9°C (80.4°F)
2. Low w/cm
3. High concrete temperature
4. High air temperature
20 (68)
5. Low humidity
6. Wind
322
Chap. 16 (2010).qxd:EB001 (2010) 1/27/11 3:46 PM Page 323
40
Relative humidity, percent Concrete temperature, °C
100
To use these charts:
90
35
1. Enter with air temperature,
80
move up to relative humidity.
70
2. Move right to concrete tem- 30
perature. 60
rate of evaporation. 30
20
15
20
10
10
5
5 10 15 20 25 30 35
Air temperature, °C Wind velocity, km/h
Metric
4
40
25
2 20
80
90
15
60 10
1
80 5
40 0
70 0
60
20
50
40
40 60 80 100
Air temperature, °F Wind velocity, mph
Inch-Pound Units
0.8
Rate of evaporation, lb (ft2/hr)
0.6 25
20
0.4 15
10
0.2
5
2
0
0
Figure 16-9. Effect of concrete and air temperatures, relative humidity, and wind velocity on rate of evaporation of surface moisture from concrete.
Wind speed is the average horizontal air or wind speed in km/h (mph) measured at 500 mm (20 in.) above the evaporating surface. Air temperature
and relative humidity should be measured at a level approximately 1.2 to 1.8 m (4 to 6 ft) above the evaporating surface and on the windward side
shielded from the sun’s rays (Kohler 1952, Menzel 1954, and NRMCA 1960).
323
Chap. 16 (2010).qxd:EB001 (2010) 1/27/11 3:46 PM Page 324
Uno (1998) built-in regression equations for saturation 3. Moisten concrete aggregates that are dry and
vapor pressure and combined them with the Kohler/ absorptive.
Menzel equation to produce a unified equation that takes 4. Dampen the subgrade (Figure 16-10) and fog forms
vapor pressure into account: prior to placing concrete.
E = 5([Tc + 18]2.5 – r • [Ta + 18]2.5)(V + 4) x 10–6 (SI units) 5. Erect temporary windbreaks to reduce wind velocity
over the concrete surface.
E = (Tc 2.5 – r • Ta 2.5)(1 + 0.4V) x 10–6 (in.-lb units)
6. Erect temporary sunshades to reduce concrete
Where: surface temperatures.
7. Fog the slab immediately after placing and before
W = mass of water evaporated in kg (lb) per m2 (ft2) of finishing, taking care to prevent the accumulation of
water-covered surface per hour water that may increase the w/cm at the surface and
eo = saturation water vapor pressure in mm Hg (psi) in reduce the quality of the cement paste in the slab
the air immediately over the concrete surface, at the surface. Tooling a wet surface will supply the mixing
concrete temperature. Obtain eo from Weast (1986) energy to increase the water-cement ratio.
or ACI 305 (2010). 8. Protect the concrete with temporary coverings, such
as reflective (white) polyethylene sheeting, during
ea = water vapor pressure in mmhg (psi) in the air sur- any appreciable delay between placing and finishing.
rounding the concrete obtained by multiplying the
saturation vapor pressure at the temperature of the air
surrounding the concrete by the relative humidity of
the air. Air temperature and relative humidity are
measured approximately 1.2 m to 1.8 m (4 ft to 6 ft)
above the concrete surface on the windward side and
shielded from the sun’s rays.
Ta = air temperature, °F (°C) Figure 16-10. Dampening the subgrade, yet keeping it free of
standing water will lessen drying of the concrete and reduce problems
When the rate of evaporation of bleed water exceeds from hot weather conditions.
1 kg/m2 (0.2 lb/ft2) per hour, precautionary measures such
as windscreens or fogging are desired. With some concrete
Fogging the concrete surface before and after final finish-
mixtures, such as those containing certain pozzolans,
ing is the most effective way to minimize evaporation and
cracking is possible if the rate of evaporation exceeds 0.5
reduce plastic shrinkage cracking (Figure 16-11). Use of
kg/m2 (0.1 lb/ft2) per hour. Concrete containing silica fume
a fog spray directed at a level approximately 1.5 m (5 ft)
is particularly prone to plastic shrinkage because bleeding
above the concrete surface will raise the relative humidity
rates are commonly as low as 0.25 kg/m2 (0.05 lb/ft2) per
of the ambient air over the slab, thus reducing evaporation
hour. Therefore, protection from premature drying is essen-
from the concrete. Fog nozzles atomize water using air
tial even at lower evaporation rates.
pressure (Figure 16-12) to create a fog blanket. They should
One or more of the precautions listed below can minimize not be confused with garden-hose nozzles, which leave an
the occurrence of plastic shrinkage cracking. They should excess amount of water on the slab. Fogging should be
be considered while planning for hot-weather concrete continued until a suitable curing material such as a curing
construction or while dealing with the problem after compound, wet burlap, or curing paper can be applied.
construction has started.
Other methods to prevent the rapid loss of moisture from
1. Keep the concrete temperature low by cooling aggre- the concrete surface include a temporary application of
gates and mixing water. plastic sheeting to the surface, spray applications, and
2. Add fibers to the concrete mixture reducing placement time. The plastic sheeting, when used,
is typically installed after strike-off and removed immedi-
ately before finishing operations commence. Temporary
324
Chap. 16 (2010).qxd:EB001 (2010) 1/27/11 3:46 PM Page 325
moisture-retaining films (usually polymers) can be applied Curing and protection are more critical in hot weather
immediately after screeding to reduce water evaporation than in temperate periods. On hardened concrete and on
before final finishing operations and curing commence. flat concrete surfaces in particular, curing water should
These materials are floated and troweled into the surface not be more than about 11°C (20°F) cooler than the con-
during finishing and should have no adverse effect on the crete. This will minimize cracking caused by thermal
concrete or inhibit the adhesion of membrane-curing com- stresses due to temperature differentials between the
pounds. Repeated applications of moisture-retaining films concrete and curing water.
followed by finishing are not recommended since these
materials typically contain water contents of 90%. Reduce To prevent the drying of exposed concrete surfaces, moist
curing should commence as soon as the surfaces are
time between placing and the start of curing by elimi-
finished and continue for at least 24 hours. In hot weather,
nating delays during construction.
continuous moist curing for the entire curing period is
preferred. Avoid wetting and drying of a surface.
325
Chap. 16 (2010).qxd:EB001 (2010) 1/27/11 3:46 PM Page 326
326