You are on page 1of 75

Faculty of Degree Engineering - 083

Department of Electrical Engineering -09

Multiple Choice Questions


Subject: Testing and Commissioning of Electrical Equipment’s Branch: Electrical Engineering

Subject code: 2180901 Semester: 8th

1. The main function of a fuse is to

(A) protect the line

(B) open the circuit

(C) protect the appliance

(D) prevent excessive currents

(e) none of the above

2. On which of the following routine tests are conducted ?

(A) Oil circuit breakers

(B) Air blast circuit breakers

(C) Minimum oil circuit breakers

(D) All of the above

3. SF6 gas

(A) is yellow in colour

(B) is lighter than air

(C) is nontoxic

(D) has pungent small

(e) none of the above

4. The arcing contacts in a circuit breaker are made of

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(A) copper tungsten alloy

(B) porcelain

(C) electrolytic copper

(D) aluminium alloy

5. Which of the following medium is employed for extinction of arc in air circuit
breaker ?

(A) Water

(B) Oil

(C) Air

(D) SF6

6. With which of the following, a circuit breaker must be equipped for remote operation
?

(A) Inverse time trip

(B) Time-delay trip

(C) Shunt trip

(D) None of the above

(e) All of the above

7. Fault diverters are basically

(A) fuses

(B) relays

(C) fast switches

(D) circuit breakers

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

8. A thermal protection switch can protect against

(A) short-circuit

(B) temperature

(C) overload

(D) over voltage

9. Arc in a circuit behaves as

(A) a capackive reactance

(B) an inductive reactance

(C) a resistance increasing with voltage rise across the arc

(D) a resistance decreasing with voltage rise across the arc

10. Thermal circuit breaker has

(A) delayed trip action

(B) instantaneous trip action

(C) both of the above

(D) none of the above

11. Relays can be designed to respond to changes in

(A) resistance, reactance or impedance

(B) voltage and current

(C) light intensity

(D) temperature

(e) all above

12. Overload relays are of…… type.

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(A) induction

(B) solid state

(C) thermal

(D) electromagnetic

(e) all above

13. Thermal overload relays are used to protect the motor against over current due to

(A) short-circuits

(B) heavy loads

(C) grounds

(D) all of the above

14. Magnetic circuit breaker has ______ trip action.

(A) delayed

(B) instantaneous

(C) both of the above

(D) none of the above

15. D.C. shunt relays are made of

(A) few turns of thin wire

(B) few turns of thick wire

(C) many turns of thin wire

(D) many turns of thick wire

16. The relay operating speed depends upon

(A) the spring tension

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) the rate of flux built up

(C) armature core air gap

(D) all of the above

17. In order that current should flow without causing excessive heating or voltage drop,
the relay contacts should

(A) have low contact resistance

(B) be clean and smooth

(C) be of sufficient size and proper shape

(D) have all above properties

18. Circuit breakers usually operate under

(A) transient state of short-circuit current

(B) sub-transient state of short-circuit current

(C) steady state of short-circuit current

(D) after D.C. component has ceased

19. Circuit breakers are essentially

(A) current carrying contacts called electrodes

(B) arc extinguishers

(C) circuits to break the system

(D) transformers to isolate the two systems

(e) any of the above

20. The current zero interruption, in oil and air blast circuit

breakers, is achieved by

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(A) lengthening of the gap

(B) cooling and blast effect

(C) both (A) and (B)

(D) deionizing the oil with forced air

(e) none of the above

21. Air blast circuit breaker is used for

(A) over currents

(B) short duty

(C) intermittant duty

(D) repeated duty

22. An efficient and a well designed protective relaying should have

(A) good selectivity and reliability

(B) economy and simplicity

(C) high speed and selectivity

(D) all of the above

23. Burden of a protective relay is the power

(A) required to operate the circuit breaker

(B) absorbed by the circuit of relay

(C) developed by the relay circuit

(D) none of the above

24. Directional relays are based on flow of

(A) power

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) current

(C) voltage wave

(D) all of the above

25. A differential relay measures the vector difference

between

(A) two currents

(B) two voltages

(C) two or more similar electrical quantities

(D) none of the above

26. A transmission line is protected by

(A) inrush protection

(B) distance protection

(C) time graded and current graded over current protection

(D) both (B) and (C)

(e) none of the above

27. Large internal faults are protected by

(A) merz price percentage differential protection

(B) mho and ohm relays

(C) horn gaps and temperature relays

(D) earth fault and positive sequence relays

28. When a transmission line is energized, the wave that propagates on it is

(A) current wave only

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) voltage wave only

(C) both (A) and (B)

(D) power factor wave only

29. Protective relays are devices that detect abnormal conditions in electrical circuits by
measuring

(A) current during abnormal condition

(B) voltage during abnormal condition

(C) constantly the electrical quantities which differ during normal and

abnormal conditions

(D) none of the above

30. The voltage appearing across the contacts after opening of the circuit breaker is
called______voltage.

(A) recovery

(B) surge

(C) operating

(D) arc

(e) none of the above

31. Ionization in circuit breaker is facilitated by

(A) high temperature

(B) increase of mean free path

(C) increasing field strength

(D) all of the above

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

32. In a circuit breaker the basic problem is to

(A) maintain the arc

(B) extinguish the arc

(C) transmit large power

(D) emit the ionizing electrons

33. Overheating of relay contacts or contact born out is due to

(A) slow making and breaking of load circuit contacts

(B) foreign matter on the contact surface

(C) too low contact pressure

(D) all of the above

34. Interruption of large currents by relay requires

(A) arc suppressing blow out coils

(B) wide separation of the opened contacts

(C) high speed opening of contacts

(D) all of the above

35. Shunt capacitance is neglected while considering

(A) short transmission line

(B) medium transmission line

(C) long transmission line

(D) medium and long transmission lines

36. The arc voltage produced in A.C. circuit breaker is always

(A) in phase with the arc current

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) lagging the arc current by 90″

(C) leading the arc current by 90°

(D) none of the above

37. The time of closing the cycle, in modern circuit breakers is

(A) 0.003 sec

(B) 0.001 sec

(C) 0.01 sec

(D) 0.10 sec

(e) none of the above

38. Insulation resistance of high voltage circuit breakers is more than

(A) 1 mega ohms

(B) 10 mega ohms

(C) 100 mega ohms

(D) 500 mega ohms

39. H.R.C. fuses provide best protection against

(A) overload

(B) reverse current

(C) open-circuits

(D) short-circuits

40. The ground wire should not be smaller than No ______ copper.

(A) 2

(B) 4

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(C) 6

(D) 10

41. The delay fuses are used for the protection of ________.

(A) motors

(B) power outlet circuits

(C) fluorescent lamps

(D) light circuits

42. Which of the following is the least expensive protection for overcurrent is low
voltage system ?

(A) Rewireable fuse

(B) Isolator

(C) Oil circuit breaker

(D) Air break circuit breaker

(e) None of the above

43. Resistance grounding is used for voltage between

(A) 33kVto66kV

(B) HkVto33kV

(C) 3.3kVandllkV

(D) none of the above

44. The contacts of high voltage switches used in power system are submerged in oil.
The main purpose of the oil is to

(A) lubricate the contacts

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) insulate the contacts from switch body

(C) extinguish the arc

(D) all of the above

(e) none of the above

45. In Railway applications ______ circuit breaker is used.

(A) SFe

(B) bulk oil

(C) minimum oil

(D) air break

46. To protect most of the electrical equipment handling low power, the types of relays
used are

(A) thermocouple

(B) electronic and bimetallic

(C) both (A) and (B)

(D) none of the above

47. Wave trap is used to trap waves of

(A) power frequencies

(B) higher frequencies entering generator or transformer units

(C) either of the above

(D) none of the above

48. Ungrounded neutral transmission system is not recommended because of system

(A) insulation being overstressed due to over voltages

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) insulation overstress may lead to failure and subsequent phase to phase faults

(C) being inadequately protected against ground fault

(D) all of the above

49. The reflection co-efficient at the open circuited end of a transmission line.

(A) zero

(B) infinity

(C) unity

(D) none of the above

50. For the protection of power station buildings against direct strokes the requirements
are

(A) interception

(B) interception and conduction

(C) interception, conduction and dissipation

(D) interception, conduction, dissipation and reflection

(e) none of the above

51. The line insulation is the insulation level of the station

equipment.

(A) less than

(B) same as

(C) more than

(D) proportional to

(e) not directly related with

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

52. The interaction between a transmission line and communication line is minimized by

(A) transposing transmission as well as communication lines

(B) increasing the height of the trans-mission line tower

(C) increasing the distance between the two lines

(D) all of the above

53. When a wave propagates on a transmission line, it suffers reflection several times at

(A) tapping

(B) load end

(C) sending end

(D) sending and other end

(e) all of the above

54. Which of the following statements is incorrect?

(A) Station batteries are used to operate relay only

(B) The lightning arresters are basically surge diverters

(C) An impedance relay has maximum fault current when fault occurs near the relay

(D) A high speed relay has an operation of 1 to 2 cycles

55. Discrimination between main and back up protection is provided by the use of
relays which are

(A) fact

(B) sensitive

(C) slow

(D) none of the above

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

56. Induction cup relay is operated due to changes in

(A) current

(B) voltage

(C) impedance

(D) all of the above

57. A.C. network analyser is used to solve problems of

(A) load flow

(B) load flow and short-circuit

(C) load flow and stability

(D) load flow, short-circuit and stability

(e) none of the above

58. Which of the following statements is incorrect ?

(A) Lightning arrestors are used before the switchgear

(B) Shunt reactors are used as compensation reactors

(C) The peak short current is (1.8 xV2) times the A.C. component

(D) The MVA at fault is equal to base MVA divided by per unit equivalent fault
reactance

59. Short-circuit currents are due to

(A) single phase to ground faults

(B) phase to phase faults

(C) two phase to ground faults

(D) three phase faults

(e) any of these

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

60. To reduce short circuit fault currents are used.

(A) reactors

(B) resistors

(C) capacitors

(D) none of the above

61. Bus coupler is very essential in arrangement

(A) single bus

(B) double bus, double breaker

(C) main and transfer bus

(D) all of the above

62. For cost and safety, the outdoor substations are installed for voltages above

(A) 11 kV

(B) 33 kV

(C) 60kV

(D) 110kV

63. The short circuit in any winding of the transformer is the result of

(A) mechanical vibration

(B) insulation failure

(C) loose connection

(D) impulse voltage

64. relays are used for phase faults on long line.

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(A) Impedance

(B) Reactance

(C) Either of the above

(D) None of the above

65. For which of the following protection from negative sequence currents is provided ?

(A) Generators

(B) Motors

(C) Transmission line

(D) Transformers

66. relay is preferred for phase fault on short transmission line.

(A) Induction type

(B) Reactance

(C) Impedance

(D) None of the above

67. Distance relays are generally

(A) split-phase relays

(B) reactance relays

(C) impedance relays

(D) none of the above

68. For which of the following ratings of the transformer differential protection is
recommended ?

(A) above 30 kVA.

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) equal to and above 5 MVA

(C) equal to and above 25 MVA

(D) none of the above

69. A _______ is used to measure the stator % winding temperature of the generator.

(A) thermocouple

(B) pyrometer

(C) resistance thermometer

(D) thermometer

70. The under voltage relay can be used for

(A) generators

(B) busbars

(C) transformers

(D) motors

(e) all of the above

71. The relay with inverse time characteristic will operate within

(A) 1.5 sec

(B) 5 to 10 sec

(C) 5 to 20 sec

(D) 20 to 30 sec

(e) none of the above

72. The single phasing relays are used for the protection of

(A) single phase motors only

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) two phase motors only

(C) two single phase motors running in parallel

(D) three phase motors

73. Which of the following devices will receive voltage surge first travelling on the
transmission line ?

(A) Lightning arresters

(B) Relays

(C) Step-down transformer

(D) Switchgear

74. Which of the following parameter can be neglected for a short line ?

(A) Inductance

(B) Capacitance

(C) Resistance

(D) Reactance

75. Series reactors should have

(A) low resistance

(B) high resistance

(C) low impedance

(D) high impedance

76. Which of the following circuit breakers has high reliability and minimum
maintenance ?

(A) Air blast circuit breakers

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) Circuit breaker with SF6 gas

(C) Vacuum circuit breakers

(D) Oil circuit breakers

77. Arc in a circuit breaker is interrupted at

(A) zero current

(B) maximum current

(C) minimum voltage

(D) maximum voltage

78. transmission line has reflection coefficient as one.

(A) Open circuit

(B) Short-circuit

(e) Long

(D) None of the above

79. What will be the reflection co-efficient of the wave of load connected to transmission
line if surge impedance of

the line is equal to load ?

(A) Zero

(B) Unity

(C) Infinity

(D) None of the above

80. The inverse definite mean time relays are used for over current and earth fault
protection of transformer against

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(A) heavy loads

(B) internal short-circuits

(C) external short-circuits

(D) all of the above

81. Over voltage protection is recommended for

(A) hydro-electric generators

(B) steam turbine generators

(C) gas turbine generators

(D) all of the above

(e) none of the above

82. Air blast circuit breakers for 400 kV power system are designed to operate in

(A) 100 microsecond

(B) 50 millisecond

(C) 0.5 sec

(D) 0.1 sec

83. Overfluxing protection is recommended for

(A) distribution transformer

(B) generator transformer of the power plant

(C) auto-transformer of the power plant

(D) station transformer of the power plant

84. Series capacitors are used to

(A) compensate for line inductive reactance

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) compensate for line capacitive reactance

(C) improve line voltage

(D) none of the above

85. Admittance relay is _______ relay.

(A) impedance

(B) directional

(C) non-directional

(D) none of the above

86. The material used for fuse must have

(A) low melting point and high specific resistance

(B) low melting point and -low specific resistance

(C) high melting point and low specific resistance

(D) low melting point and any specific resistance

87. If the fault occurs near the impedance relay, the VII ratio will be

(A) constant for all distances

(B) lower than that of if fault occurs away from the relay

(C) higher than that of if fault occurs away from the relay

(D) none of the above

88. The torque produced in induction type relay (shaded pole structure) is

(A) inversely proportional to the current

(B) inversely proportional to the square of the current

(C) proportional to the current

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(D) proportional to square of the current

89. The steady state stability of the power system can be increased by

(A) connecting lines in parallel

(B) connecting lines in series

(e) using machines of high impedance

(D) reducing the excitation of machines

(e) none of the above

90. The inductive interference between power and communication line can be
minimized by

(A) transposition of the power line

(B) transposition of the communication line

(C) both (A) and (B)

(D) increasing the distance between the conductors

91. The power loss is an important factor for the design of

(A) transmission line

(B) motor

(C) generator

(D) feeder

92. A fuse is connected

(A) in series with circuit

(B) in parallel with circuit

(C) either in series or in parallel with circuit

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(D) none of the above

93. H.R.C. fuse, as compared to a rewirable fuse, has

(A) no ageing effect

(B) high speed of operation

(C) high rupturing capacity

(D) all of the above

94. The fuse rating is expressed in terms of

(A) current

(B) voltage

(C) VAR

(D) kVA

95. The fuse blows off by

(A) burning

(B) arcing

(C) melting

(D) none of the above

96. On which of the following effects of electric current a fuse operates ?

(A) Photoelectric effect

(B) Electrostatic effect

(C) Heating effect

(D) Magnetic effect

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

97. An isolator is installed

(A) to operate the relay of circuit breaker

(B) as a substitute for circuit breaker

(C) always independent of the position of circuit breaker

(D) generally on both sides of a circuit breaker

98. A fuse in a motor circuit provides protection against

(A) overload

(B) short-circuit and overload

(C) open circuit, short-circuit and overload

(D) none of the above

99. Protection by fuses is generally not used beyond

(A) 20 A

(B) 50 A

(C) 100 A

(D) 200 A

100. A fuse is never inserted in

(A) neutral wire

(B) negative of D.C. circuit

(C) positive of D.C. circuit

(D) phase dine

101) Which of the following circuit breakers is used for the railway electrification?

(A) Air blast circuit breaker

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) SF6 circuit breaker

(C) Bulk oil circuit breaker

(D) Minimum oil circuit breaker

102) The stability of arc in vacuum depends on _________.

(A) The contact material only.

(B) The circuit parameters only.

(C) The contact materials and its vapour pressure.

(D) Both (b) and (c)

e. None of these

103) SF6 is which type of gas?

(A) Electro positive

(B) Electro negative

(C) Both (a) and (b)

(D) None of these

104) What is the average rate of rise of restriking voltage upto the first peak?

(A) 525 * 103kV / sec

(B) 453 * 103kV / sec

(C) 582 * 103 kV / sec

(D) 467 * 103 kV / sec

105) Circuit breakers usually operate under

(A) Steady short circuit current

(B) Sub transient state of short circuit current

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(C) Transient state of short circuit current

(D) None of these

106) What is the actuating quantity for the relays?

(A) Magnitude

(B) Frequency

(C) Phase angle

(D) All of these

107) Which among these are the main characteristics of a fuse element?

(A) Low melting point

(B) High conductivity

(C) Least deterioration due to oxidation

(D) All of the above

108) What is the making capacity of the circuit breaker?

(A) Less than the asymmetrical breaking capacity of the breaker

(B) Greater than the asymmetrical breaking capacity of the breaker

(C) Equal to the asymmetrical breaking capacity of the breaker

(D) Equal to the symmetrical breaking capacity of the breaker

109) In a circuit breaker the contact space is ionised by what?

(A) Field emission from the contact surface.

(B) Thermal emission from the contact surface.

(C) Thermal ionisation of gas.

(D) All of above.

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

110) A three phase, 33 kV oil circuit breaker is rated 1200 A, 2000 MVA, 3s. What is
its symmetrical breaking current?

(A) 1200 A

(B) 3600 A

(C) 35 kA

(D) 104.8 kA

111) What should be the value of fusing factor?

(A) Equal to zero

(B) Equal to one

(C) Less than one

(D) More than one

112) What is the relation between the fusing current and the diameter of the wire?

(A) I = k d3

(B) I = k d3/2

(C) I = k d2

(D) I = k d2/3

113) The making and breaking currents of a 3 phase ac circuit breakers in power
systems are respectively in ________form.

(A) rms value, rms value

(B) instantaneous value, rms value

(C) rms value, instantaneous value

(D) instantaneous value, instantaneous value

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

114) Why is an isolator installed?

(A) To isolate one portion of the circuit from another

(B) As an substitute for the circuit breaker

(C) It used on either sides of the circuit breaker

(D) Both (a) and (c)

e. None of these

115) Assertion (A): In comparison to making capacity of a circuit breaker its breaking
capacity is normally higher.

Reason (R): The breaking capacity of a CB is expressed as √3 * VI * 10-6 MVA

(A) Both A and R are true and R is the correct explanation of A

(B) Both A and R are true and R is not the explanation of A

(C) A is true but R is false

(D) A is false but R is true.

116) What is the cut off current in the fuse?

(A) Maximum value actually reache(D)

(B) Rms value actually reache(D)

(C) Average value actually reache(D)

(D) None of the above

117) Which circuit breaker is preferred to be installed in extra high voltage AC


system?

(A) Bulk oil type circuit breaker

(B) Air blast circuit breaker

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(C) SF6 circuit breaker

(D) Vacuum circuit breaker

118) A three phase circuit breaker is rated 2000 MVA, 33 kV. What will be its making
current?

(A) 35 kA

(B) 49 kA

(C) 70 kA

(D) 89 kA

119) A fuse wire of circular cross section has a radius of 0.8mm. The wire blows off at
a current of 9(A) What will be the radius of the wire that will blow off at a current of
1A?

(A) 0.2 mm

(B) 0.18 mm

(C) 0.28 mm

(D) 0.3 mm

120) Which among these tests are performed to check the nation or international
standards?

(A) Type test.

(B) Production tests.

(C) Site checks.

(D) All of the above.

121) Refer to the following facts to answer the question

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

A 50 Hz, 11 kV, 3 phase alternator with earthed neutral having a reactance of 3 ohms
per phase and is connected to a bus bar through a circuit breaker, if the distributed
capacitance upto CB between the phase and neutral is 0.01 μ F.

What is the frequency of oscillations?

(A) 10000 Hz

(B) 12500 Hz

(C) 12628 Hz

(D) 13265 Hz

122) What is switchgear?

(A) An apparatus used for switching, controlling and protecting the electrical circuits
and equipments.

(B) It detects the faults only.

(C) It corrects the faults only.

(D) All of the above.

123) What is / are the main disadvantage / s of using oil as the quenching medium in
the circuit breakers?

(A) Need periodical replacement.

(B) Risk of formation of explosive mixture with air.

(C) Possibility of causing fire hazards.

(D) All of the above.

124) Which of the following circuit breakers has the lowest operating voltage?

(A) SF6 circuit breaker

(B) Air break

(C) Air blast

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(D) Minimum oil circuit breaker

125) The most efficient torque producing actuating structure for the induction type
relays is

(A) Shaded pole structure

(B) Watt hour meter structure

(C) Induction cup structure

(D) Single induction loop structure

126) Plug setting of a electromagnetic relay can be altered by varying

(A) Number of ampere turns

(B) Air gap of magnetic path

(C) Adjustable back stop

(D) None of these

127) Which material is used for the manufacture of bus bars?

(A) Aluminium rods.

(B) Copper rods.

(C) Any conducting material.

(D) Made of silver.

128) Which device sends the information to the circuit breaker to interrupt the circuit
in case of fault?

(A) Switch

(B) Relay

(C) Circuit breaker itself does this function.

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(D) Fuse.

129) When does the circuit breaker operate in the line?

(A) When power is to be supplie(D)

(B) When the line is to be teste(D)

(C) Whenever the fault occurs in the line.

(D) Whenever the switch and the relay has to be operate(D)

130) What is the primary principle of a fuse?

(A) Open the circuit.

(B) Protect the appliance.

(C) Protect the line.

(D) Prevent excess current from flowing into the line.

131) On what factor does the operating speed of the relay depend?

(A) Rate of flux built up

(B) Armature core air gap

(C) Spring tension

(D) All of these

132) Protective relays can be designed to respond to ___________.

(A) Light intensity, impedance

(B) Temperature, resistance, reactance

(C) Voltage and current

(D) All of these

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

133) What is the purpose of back up protection?

(A) To increase the speed

(B) To increase the reach

(C) To leave no blind spot

(D) To guard against failure of primary

134) What is the major cause of the failure of the circuit breaker?

(A) Trip circuit open

(B) Trip latch defective

(C) Spring defective

(D) All of these

135) Why are the isolators used?

(A) Break abnormal current

(B) Making under fault conditions

(C) Breaking the circuit under no load condition

(D) None of the above

136) The isolators used in the transmission lines are capable of breaking

(A) Fault current

(B) No current

(C) Charging current

(D) Load current

137) For which among the following the current ratings are not required?

(A) Circuit breakers

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) Relays

(C) Isolators

(D) Load break switch

138) What is the making to breaking current ratio for an extra high voltage circuit
breaker?

(A) More than 1

(B) Equal to 1

(C) Less than 1

(D) A negative value

139) The breaking capacity of a three phase circuit breaker is given by

(A) Service line voltage * rated symmetrical current in amperes * 10-6 MVA

(B) √3 * Service line voltage * rated symmetrical current in amperes * 10-6 MVA

(C) 1.1* Service line voltage * rated symmetrical current in amperes * 10-6 MVA

(D) √2 * Service line voltage * rated symmetrical current in amperes * 10-6 MVA

140) Which of the following circuit breaker is highly reliable and has a least
maintenance?

(A) Oil circuit breakers

(B) Air blast

(C) Vacuum circuit breakers

(D) SF6 circuit breakers

141) The rating of the circuit breaker is usually determined on the basis of
____________ fault.

(A) Symmetrical

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) Line to line

(C) Single line to ground

(D) Double line to ground

142) Which among these circuit breakers produce the least arc energy?

(A) Plain oil

(B) Minimum oil

(C) Air blast

(D) Air break

143) A thermal protection switch provides protection against what?

(A) Overload

(B) Temperature

(C) Short circuit

(D) Over voltage

144) What does protective relay provide?

(A) Provide additional safety to the circuit breaker in its operation.

(B) Close the contacts when the actuating quantity attains a certain predetermined
value.

(C) Limit the arcing current during the circuit breaker operation.

(D) Earth or ground any stray voltage.

145) What is the main purpose of oil in oil circuit breakers?

(A) Provide insulation

(B) Quenching ar(C)

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(C) Provide cooling of contacts.

(D) None of the above

146) What is the advantage of using oil as the arc quenching medium?

(A) Good cooling properties.

(B) High dielectric strength.

(C) Acts as an insulator.

(D) All of these.

147) When does the arc interruption in oil circuit breaker take place?

(A) Contacts apart.

(B) Voltages becomes zero

(C) Current goes through zero

(D) All of the above

148) For rural electrification in India, which circuit breaker is generally used?

(A) Oil

(B) SF6

(C) Vacuum

(D) Air blast

149) Keeping in view the cost and the overall effectiveness, which of the following
circuit breaker is best suited for capacitor bank switching?

(A) Vacuum circuit breaker

(B) Air blast CB

(C) SF6

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(D) Oil CB

150) To limit current chopping in vacuum circuit breakers, the contact material
employed should have the properties of

(A) Low conductivity and high vapour pressure.

(B) Low conductivity and low vapour pressure.

(C) High conductivity and high vapour pressure.

(D) High conductivity and low vapour pressure.

151) SF6 gas is imported in _____________.

(A) Air cylinders

(B) Gas cylinders

(C) Liquid form in cylinders

(D) Solid form.

152) During arc extinction SF6 gas gets converted to which among these?

(A) Gets decomposed to SF4 and SF2

(B) Gets decomposed to S and F

(C) Gets reduced to SF6

(D) Gets oxidized

153) What is the most important property which makes the SF6 very efficient medium
for circuit breaking?

(A) Is non toxic and non inflammable.

(B) Has a high dielectric constant.

(C) Has a high breakdown strength

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(D) Is highly electronegative gas

154) What is the normal pressure at which the SF6 gas is maintained in the closed
position of the breaker?

(A) 2 kg / cm2

(B) 2.5 kg /cm2

(C) 2.8 kg / cm2

(D) 3 kg / cm2

155) What is the major drawback of using SF6 circuit breakers?

(A) Sealing problems of the gas.

(B) Ingress of moisture in the gas system – dangerous.

(C) Deterioration of SF6 gas with time.

(D) Both (a) and (b)

e. None of these

156) Why do the SF6 gases have an excellent heat transfer property?

(A) Low gaseous viscosity.

(B) High dielectric strength.

(C) Higher molecular weight.

(D) Both (a) and (c)

e. None of these

157) What is the breaking capacity of the air blast circuit breaker?

(A) 5000 MVA

(B) 6000 MVA

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(C) 7000 MVA

(D) 10000 MVA

158) In axial blast type of CB, expansion of air takes place from ______________.

(A) High pressure to low pressure.

(B) Low pressure to high pressure.

(C) Always in high pressure.

(D) Always in low pressure.

159) The air blast circuit breakers for 400 kV systems are designed to operate in how
much time?

(A) 0.1 s

(B) 0.5 s

(C) 50 ms

(D) 100µs

160) What is the type of air blast in cross blast type CB?

(A) The blast of air is along the ar(C)

(B) The blast of air cuts across the ar(C)

(C) Both (a) and (b)

(D) None of the above.

161) Why is the resistance switching used in a air blast circuit breaker?

(A) Reduce the magnitude of fault current.

(B) Control the CB operating time.

(C) Damp out the fast transient.

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(D) Change the fault current power factor.

162) When using air blast circuit breaker, current chopping is a phenomenon observed
when

(A) A long overhead line is switched off.

(B) A bank of capacitors is switched off.

(C) A transformer on no load is switched off.

(D) A heavy load is switched off.

163) Which type of air is used in air blast circuit breaker?

(A) Ionised air

(B) Air free from moisture

(C) Air should have least CO2

(D) Air must have oil mist.

264) What is the maximum current upto which fuses can be used?

(A) 25 A

(B) 50 A

(C) 75 A

(D) 100 A

165) What is fusing factor?

(A) The ratio of current rating of the fuse to the minimum fusing current

(B) The ratio of minimum fusing current to the current rating of the fuse

(C) The ratio of maximum fusing current to the current rating of the fuse

(D) The ratio of minimum fusing current to the voltage rating of the fuse

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

166) For a current upto 10A which material is used as the fusing element?

(A) Copper

(B) Silver

(C) Alloy of lead and tin

(D) Zinc

167) Which among these is the least expensive protection for over current in low
voltage system?

(A) Rewirable fuse.

(B) Isolator.

(C) Circuit breaker.

(D) Air breaker switch.

168) Which among the following statement is true related to fuse?

(A) Greater the current smaller is the time taken by the fuse to blow out.

(B) Greater the current greater is the time taken by the fuse to blow out.

(C) The current is directly proportion to the blow out time of fuse.

(D) Is dependent on the temperature and atmospheric conditions.

169) How is the restriking voltage measured?

(A) RMS value

(B) Peak value

(C) Instantaneous value

(D) Average value

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

170) What is the interrupting medium in the contactor?

(A) Air at atmospheric pressure.

(B) SF6 gas

(C) Oil

(D) All of the above.

171) Recovery voltage is the value of rms voltage that reappears across the poles of a
circuit breaker before_______________

(A) Restriking voltage

(B) Final arc extinction

(C) Rise of voltage

(D) All of the above

172) Why is it difficult to interrupt a capacitive circuit?

(A) The current has a leading power factor.

(B) The restriking voltage can be high.

(C) Current magnitude is very small.

(D) Stored energy in the capacitor is very high.

173) Rate of rise of restriking voltage depend on_____________?

(A) Type of circuit breaker.

(B) Capacitance of the system.

(C) Inductance of the system.

(D) Both (b) and (c)

e. None of these

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

174) On what factor does the rate of rise of restriking voltage (RRRV) depend?

(A) System voltage.

(B) Circuit power factor only

(C) Switching conditions

(D) Both (b) and (c).

175) In a circuit breaker, the active recovery voltage depends upon which among
these?

(A) Circuit conditions.

(B) Power factor.

(C) Both (a) and (b)

(D) None of the above

176) What is restriking voltage?

(A) The transient voltage that appears across the circuit breaker contacts at the instant
of arc extinction.

(B) The transient voltage that appears across the circuit breaker contacts at the end of
arc extinction.

(C) Both (a) and (b)

(D) None of the above

177) For a high speed circuit breaker what will the total clearing time?

(A) Few minutes.

(B) Few seconds.

(C) 1 to 2 cycles.

(D) 5 to 20 cycles.

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

178) The interrupting time of a circuit breaker is the period between the instant of
_________.

(A) Initiation of short circuit and the arc extinction on an opening operation.

(B) Energizing the trip circuit and the arc extension on an opening operation.

(C) Initiation of short circuit and the parting of primary arc contacts.

(D) Energizing of the trip circuit and the parting of primary arc contacts.

179) In a circuit breaker, ionisation is facilitated by_________________.

(A) Increase in field strength.

(B) Increase in mean free length.

(C) High temperature of the surrounding medium.

(D) All of the above.

180) Which of the following should have low value for the contacts and their material?

(A) Thermal capacity.

(B) Contact resistance.

(C) Thermal conductivity.

(D) None of above.

181) The heat produced at the contact point owing to flow of electric current is least
affected by_____________________.

(A) Temperature of the surrounding medium.

(B) Contact resistance.

(C) Magnitude of electric current flowing.

(D) Duration of flow of current.

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

182) The resistance of an electric arc can be increased by

(A) Increasing the concentration of ionised particles.

(B) Reducing the arc length.

(C) Splitting the ar(C)

(D) Increasing the arc cross section.

183) By using low resistance method for arc extension what is the value of arc
resistance?

(A) Arc resistance is zero.

(B) Arc resistance is high

(C) Arc resistance is low

(D) Arc resistance is very high

184) What happens in the arc extinction using high resistance method?

(A) Arc resistance is decreased with time.

(B) Arc resistance is increased with time.

(C) No change it remains same.

(D) Arc resistance is kept zero.

185) What is the arc voltage in a circuit breaker?

(A) In phase with the arc current.

(B) Lagging the arc current by 90°

(C) Leading the arc current by 90°

(D) Lagging the arcing current by 180°

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

186) Arcing voltage will be the least in case of

(A) Carbon

(B) Copper

(C) Silver

(D) Tungsten

187) How is the initiation of electric arc at the instant of contact separation caused?

(A) Thermionic emission of electrons.

(B) Field emission of electrons.

(C) Both (a) and (b)

(D) None of these.

188) The arc resistance depends on which among the following factors?

(A) Cross section of the ar(C)

(B) Length of the ar(C)

(C) Degree of ionization

(D) All of the above.

189) Which type of tripping is generally preferred for the circuit breaker?

(A) Manual

(B) Automatically

(C) Depending on the voltage level

(D) None of the above

190) Which part of the circuit breaker is helpful in breaking the current?

(A) Trip coil.

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) Contacts.

(C) Medium

(D) Handle.

191) When a fault occurs in a high voltage transmission line, what happens first?

(A) Circuit breaker operates then the relay.

(B) Relay operates and then the circuit breaker.

(C) Relay operates, then successively the isolator and the circuit breaker.

(D) Isolator operates, then successively the relay and the circuit breaker.

192) Upto what voltage can the liquid type HRC fuses be used?

(A) 33 kV

(B) 132 kV

(C) 66 kV

(D) 220 kV

193) What is the main advantage of using a fuse?

(A) Cheapest type of protection.

(B) Inverse time current characteristics.

(C) Current limiting effect under short circuit conditions.

(D) All of above.

194) On what basis is the selection of fuse done?

(A) Steady loa(D)

(B) Fluctuating loa(D)

(C) Both (a) and (b)

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(D) None of these.

195) Upto what voltage a cartridge type of fuse can be used?

(A) 400 V

(B) 11 kV

(C) 20 kV

(D) 33 kV

196) In a HRC fuse what is the time between the cut off and the final current zero
called?

(A) Pre - arcing time.

(B) Arcing time.

(C) Total operating time.

(D) None of these.

197) Which material is used in the liquid type of fuse?

(A) SF6

(B) Distilled water

(C) Carbon tetra chloride.

(D) Mineral oil / transformer oil

198) What is the advantage of HRC fuses over Rewirable fuses?

(A) High speed operation

(B) High rupturing capacity

(C) No ageing effect.

(D) All of the above.

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

199) If the strands of the fusing wire are twisted, what happens to the fusing current?

(A) Increases

(B) Reduces.

(C) No change/ remains same

(D) Depends on the value of current, increases or decreases.

200) What is the typical value of the pre arcing time?

(A) 0.1

(B) 0.01

(C) 0.001

(D) 0.0001

201. Outdoor switchgear is generally used for voltage beyond

(A) 11 KV

(B) 33 KV

(C) 66 KV

(D) 132 KV

202. The least expensive protection for over current in low-voltage system is

(A) Rewirable fuse

(B) Isolator

(C) Circuit breaker

(D) Air-break switch

203. Purpose of backup protection is

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(A) To increase the speed

(B) To increase a reach

(C) To leave no blind spot

(D) To guard against failure of primary

204. We do not require any protection against prime mover failure in case of

(A) Turbo generator sets

(B) Hydro generator sets

(C) Diesel engine driven alternators

(D) Back pressure turbo generators

205. For the protection of stator winding of an alternate against internal fault involving
ground the relay used is a

(A) Biased differential relay

(B) Directional over-current relay

(C) Plain impedance relay

(D) Buchholz relay

206. For the protection of a large squirrel cage induction motor against single phase
normally

(A) An over-current relay is used

(B) Differential relay is used

(C) Directional relay is used

(D) Negative sequence current sensitive relay is used

207. The most commonly used method for the protection of three phase feeder is

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(A) Time graded protection

(B) Differential protection

(C) Reverse power protection

(D) None of the above

208. Which is the pilotless protection method for feeder line ?

(A) Differential protection

(B) Carrier current protection

(C) Time credit protection

(D) None of the above

209. Time graded protection of a radial feeder can be achieved by using

(A) Definite time relay

(B) Inverse time relay

(C) Both definite and inverse time relays

(D) None of the above

210. Pilot-wire protection scheme is the most economical and provides high speed
relaying for

(A) Short length of lines upto 15 km

(B) Medium length of lives up to 60 km

(C) Long length of lines up to 200 km

(D) All of the above

211. Problems associated with differential protection is/are

(A) Magnetising inrush current

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) Mismatching characteristics of CTs

(C) Charge of ratio as a result of tapping

(D) All of the above

212. For the protection of transformers, harmonic restraint is used to guard against

(A) Magnetising inrush current

(B) Unbalanced operation

(C) Lightning

(D) Switching over-voltage

213. The types of faults that occur in electric motors are

(A) Stator

(B) Rotor

(C) Overload

(D) All of the above

214. The main function of under voltage protective device generally employed with a
motor starter is to

(A) Open the supply circuit on failure of power supply

(B) Control the motor voltage

(C) Prevent the opening of supply circuit

(D) None of the above

215. The bias factor S in unit protection synchronous generators

(A) Lies between .05 and .1 pu

(B) Is less than .05 pu

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(C) Lies between .1 to .25 pu

(D) Is greater than .025 pu

216. In a balanced voltage pilot wire protection scheme if the pilot circuit gets opened,
the relay will

(A) Fail to trip on internal faults

(B) Trip on full load

(C) Trip instantaneously on external faults

(D) None of the above

217. In a balanced voltage pilot-wire protection scheme, if the pilot circuit gets short-
circuited, the relay will

(A) Fail to trip on internal faults

(B) Fail to trip on external faults

(C) Trip on full load

(D) Trip instantaneously

218. The frequency of carrier in the carrier current pilot scheme is in the range of

(A) 1 kHz to 10 kHz

(B) 10 kHz to 25 kHz

(C) 25 kHz to 50 kHz

(D) 50 kHz to 500 kHz

219. The frequency of carrier transmitted by microwave pilot is in the range of

(A) 1000 kHz to 1500 kHz

(B) 2000 kHz to 5000 kHz

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(C) 900 kHz to 6000 kHz

(D) 10000 kHz to 15000 kHz

220. In carrier current protection the purpose of the wave trap is for

(A) Trapping power frequency waves

(B) Trapping high frequency waves entering into generators/ transformer unit

(C) Both a and b

(D) None of the above

221. As soon as a fault develops in a generator stator, it is essential to suppress field


excitation, otherwise

(A) Terminal voltage will drop

(B) It may lead to loss of synchronism

(C) It will continue to supply power to the stator winding fault

(D) All of the above

222. Distance protection scheme is preferred over graded lime-lag over-current


protection in HV and EHV lines because

(A) It is faster in operation

(B) It is simple

(C) It is cheaper in cost

(D) All of the above

223. Requirements of protection power station buildings against direct strokes are

(A) Interception

(B) Conduction

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(C). Dissipation

(D) All of the above

224. The protection against direct lighting strokes and a high-voltage steep waves is
provided by

(A) Ground wires

(B) Lightning arresters

(C) Lightning arresters and ground wires

(D) Earthing of neutral

225. For protection of rotating machines against lightning surge .............is used

(A) Lightning arrester

(B) Capacitor

(C) Combination of lightning arrester and a capacitor

(D) Lightning conductor and arrester

226. In between the generating station and consumers a number of transformation and
switching stations exist, these are called the

(A) Switchgears

(B) Substations

(C) Intermediate substations

(D) Transformation stations

227. With large reactance interconnector between two power stations

(A) The power stations may fall out of step due to large angular displacement between
the power stations

(B) Power will be transferred with minimum power losses

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(C) Power will be transferred with voltage fluctuations and noise

(D) None of the above

228. In a isolated neutral system, when a single line to ground fault occurs

(A) Persistent arcing grounds will be developed

(B) Voltage in the healthy phases rise to full line value causing isolation breakdown

(C) The capacitive current in the faulty phase rises to 3 times its normal value

(D) All of the above

229. Tap changing transformers are employed for

(A) Stepping down the voltage

(B) Stepping up the voltage

(C) Supplying low-voltage current to instruments

(D) Both stepping up and stepping down the voltage

230. Field failure in an alternator occurs due to

(A) Failure of exciter

(B) Faulty field circuit breaker

(C) In rush of large currents

(D) Both A and B

231. Large internal faults are protected by

(A) Merz price percentage differential protection

(B) Mho and ohm relays

(C) Horan gaps and temperature relays

(D) Earth fault and positive sequence relays

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

232. Which of the following is the least expensive protection for over current in low-
voltage system ?

(A) Rewireable fuse

(B) Isolator

(C) Oil circuit breaker

(D) Air break circuit breaker

233. For the protection of power station buildings against direct strokes the
requirements are

(A) Interception

(B) Interception and conduction

(C) Interception, conduction and dissipation

(D) Interception,conduction,dissipation and reflection

234. The line insulation is............. the insulation level at the station equipment

(A) Less than

(B) Same as

(C) More than

(D) Not directly related with

235. Discrimination between main and back up protection is provided by the use of
relays which are

(A) Fact

(B) Sensitive

(C) Slow

(D) None of the above

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

236. Short-circuit currents are due to

(A) Single phase to ground faults

(B) Phase to phase faults

(C) Three phase faults

(D) Any of these

237. For which of the following protection from negative sequence current is provided?

(A) Generators

(B) Motors

(C) Transmission line

(D) Transformers

238. For which of the following ratings of the transformer differential protection is
recommended?

(A) Above 30 KVA

(B) Equal to and above 5 MVA

(C) Equal two and above 25 MVA

(D) None of the above

239. Over voltage protection is recommended for

(A) Hydro electric generators

(B) Steam turbine generators

(C) Gasturbine generators

(D) All of the above

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

240. Overfluxing protection is recommended for

(A) Distribution transformer

(B) Generator transformer of the power plant

(C) Auto transformer of the power plant

(D) Station transformer of the power plant

241. Hey switchgear is device used for

(A) Interrupting an electrical circuit

(B) Switching an electrical circuit

(C) Reaching and controlling an electrical circuit

(D) Switching, controlling and protecting the electrical circuit and equipment

242. Switching over voltage arc are more hazardous than lighting surges in case of

(A) Unbalanced systems

(B) Low-voltages

(C) 11 KV systems

(D) EHV and UHV systems

243. Least number of faults are generally reported for

(A) Transmission lines

(B) Cables

(C) Switchgears

(D) Transformers

244. Minimum working voltage will be least in case of

(A) Silver

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) Graphite

(C) Carbon

(D) Tungsten

245. In a contactor, interrupting medium may be

(A) Air

(B) Oil

(C) Sf6 gas

(D) Any of the above

246. The transient voltages that appears across the contacts at the instant of arc
extinction is called ..............voltage

(A) Supply

(B) Recovery

(C) Restriking

(D) Peak

247. The power loss is an important factor for the design of

(A) Transmission line

(B) Motor

(C) Generator

(D) Feeder

248. SF6 gas

(A) Is yellow in colour

(B) Is lighter than air

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(C) Is non-toxic

(D) Has pungent small

249. SF6 gas is transported in

(A) Air cylinders

(B) Gas cylinders

(C) Liquid from in cylinders

(D) Solid form in boxes

250. The short-circuit in any winding of the transformer is the result of

(A) Mechanical vibration

(B) Insulation failure

(C) Loose connection

(D) Impulse voltage

251. The actuating quantity for the relays may be

(A) Magnitude

(B) Frequency

(C) Phase angle

(D) Any of the above

252. The operating speed of a relay depends upon the

(A) Rate of flux built up

(B) Armature core air gap

(C) Spring tension

(D) All of these

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

253. Inverse time current relays are used for the protection of

(A) Feeders

(B) Transformers

(C) Alternators

(D) Both A and B

254. IDMT relays are used to protect the power transformers against

(A) External short-circuit

(B) Over loads

(C) Internal short-circuits

(D) Both A and B

255. In distance protection, the relay measures

(A) Negative sequence impedance of the light from relay up to the fault point

(B) Positive sequence impedance of the line from relay up to the fault point

(C) Self impedance of the line from relay up to the fault point

(D) Zero sequence impedance of the line from relay up to the fault point

256. The relay used for phase fault protection of short transmission lines is

(A) Reactance relay

(B) Impedance relay

(C) Mho relay

(D) IDMT relay

257. Where severe synchronising swing occur, the relay employed is

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(A) Impedance relay

(B) Mho relay

(C) Reactance relay

(D) Induction relay

258. For the protection of lines against faults involving variable fault resistance, the
preferred relaying scheme is a

(A) Plain impedance relay

(B) Directional over-current relay

(C) Mho relay

(D) Reactance relay

259. For ground fault we prefer

(A) Plain impedance relay

(B) Directional over current relay

(C) Mho relay

(D) Reactance relay

260. Admittance relay

(A) Nondirectional relay

(B) Directional relay

(C) Differential relay

(D) None of the above

261. The relay used for feeder protection is

(A) Under voltage relay

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) Translay relay

(C) Thermal relay

(D) Buchholz relay

262. Which relay is used to detect and protect internal fault in a transformer ?

(A) Buchholz relay

(B) Directional relay

(C) Thermal relay

(D) Distance relay

263. Which one of the following relay has the capability of anticipating the possible
major fault in a transformer ?

(A) Over-current relay

(B) Differential relay

(C) Buchholz relay

(D) Over fluxing relay

264. Zero sequence current is used for relaying purpose only in the case of

(A) Phase over current really

(B)Phase impedance relay

(C) Ground over current relay

(D) Ground impedance relay

265. To prevent mal operation of differentially connected relay while energising a


transformer, the relay restraining coil is biased with

(A) Second harmonic current

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) Third harmonic current

(C) Fifth harmonic current

(D) Seventh harmonic current

266. How many relays are used to detect interphase fault of a three line system?

(A) One

(B) Two

(C) Three

(D) Six

267. Which is the main relay for protecting up to 90% of the transmission line-length in
the forward direction?

(A) Directional over current relay

(B) Mho relay

(C) Carrier current protective relay

(D) Impedance relay

268. For protection of parallel feeders fed from one end, the relays required are

(A) Nondirectional relays at the source end and directional relay at the load end

(B) Nondirectional relay at both ends

(C) Directional relay at source end and nondirectional relay at load end

(D) Directional relay at both ends

269. Relays can be designed to respond to changes in

(A) Resistance, reactance or impedance

(B) Voltage and current

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(C) Light intensity

(D) All of the above

270. DC shunt relays are made of

(A) Few turns of thin wire

(B) Few turns of thick wire

(C) Many turns of thin wire

(D) Many turns of thick wire

271. The relay operating speed depends upon

(A) The spring tension

(B) The rate of flux built up

(C) Armature core air gap

(D) All of the above

272. In order that current should flow without causing excessive heating or voltage
drop, the relay contacts should

(A) Have low contact resistance

(B) Be clean and smooth

(C) Be of sufficient size and proper shape

(D) Have all above properties

273. Interruption of large currents by relay requires

(A) Arc suppressing blow out coils

(B) Wide separation of the open contacts

(C) High speed opening of contacts

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(D) All of the above

274. To protect most of the electrical equipment handling low power, the types of relays
used are

(A) Thermocouple

(B) Electronic and bimetallic

(C) Both A and B

(D) None of the above

275. ............. Relays are used for phase faults on long line

(A) Impedance

(B) Reactance

(C) Either of the above

(D) None of the above

276. ........ Relays is preferred for phase fault on short transmission line

(A) Induction type

(B) Reactance

(C) Impedance

(D) None of the above

277. The under voltage relay can be used for

(A) Generators

(B) Bus bars

(C) Transformers

(D) All of the above

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

278. The relay with inverse time characteristic will operate within

(A) 1.5 sec

(B) 5 to 10 sec

(C) 5 to 20 sec

(D) 20 to 30 sec

279. The single phasing relays are used for the protection of

(A) Single phase motors only

(B) Two phase motors only

(C) Two single phase motor running in parallel

(D) Three phase motors

280. The inverse definite mean time relays are used for over current and earth fault
protection of transformer against

(A) Heavy loads

(B) Internal short circuits

(C) External short circuits

(D) All of the above

281. In a static over current relay, inverse time characteristics are obtained by

(A) A transistor amplifier

(B) An integrating circuit

(C) A transistor switch

(D) A differentiating circuit

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

282. In the case of transmission line protection, over current relay is used

(A) Only up to 110 KV

(B) Only up to 220 KV

(C) Only up to 50 KV

(D) Only up to 1100 KV

283. Directional over current relays have two exciting coils connected across

(A) CT secondaries of two different phases

(B) VT secondaries of two different phases

(C) CT and VT secondaries of same phases

(D) CT and VT secondaries of two different phases

284. The domains of power system where directional over current relay is indispensable
are

(A) In case of parallel feeder protection

(B) In case of ring main feeder protection

(C) Both A and B

(D) None of the above

285. In an inverse definite minimum time, electromagnetic type over current relay, the
minimum time feature is achieved because of

(A) Saturation of the magnetic circuit

(B) Proper mechanical design

(C) Appropriate time delay element

(D) Electromagnetic damping

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

286. Impedance relay can be used for

(A) Phase faults only

(B) Earth faults only

(C) Both earth and phase faults

(D) None of the above

287. Impedance relay may use

(A) Balance beam structure

(B) Induction cup structure

(C) Shaded pole structure

(D) Either A or B

288. An impedance is relay is a

(A) Voltage restrained over current relay

(B) Voltage restrained directional relay

(C) Directional restrained over current relay

(D) Directional restrained over voltage relay

289. On transient fault OC and impedance relay

(A) Under reaches

(B) Over reaches

(C) Reach unaffected

(D) None of the above

290. Threshold characteristics of a plain impedance relay in a complex Z plane is a

(A) Circle passing through origin

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(B) Circle with the centre at the origin

(C) Straight line passing through origin

(D) Straight line offset from the origin

291. The structure used in reactance relay is

(A) Induction cup

(B) Double induction loop

(C) Single induction loop

(D) Either A or B

292. Reactance relay is normally used for protection against

(A) Earth fault only

(B) Phase fault only

(C) Both earth and phase faults

(D) None of the above

293. The operating characteristics of the reactance relay in the complex impedance
plane is a

(A) Circle with its origin at the centre of the R-X plane

(B) Circle passing through the origin

(C) Straight line passing through the origin

(D) Straight line parallel to the X axis

294. A reactance relay is

(A) Voltage restrained overcurrent relay

(B) Voltage restrained directional relay

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

(C) Directional restrained overcurrent relay

(D) Directional restrained over voltage relay

295. Reactance relays are used for phase fault in.......line

(A) Short

(B) Medium

(C) Long

(D) All of the above

296. A differential relay response to

(A) Algebraic difference of two or more similar electrical quantities

(B) Phasor difference of two or more similar electrical quantities

(C) Algebraic difference between two currents

(D) Algebraic difference between two voltages

297. Differential relays are used for protection of

(A) Feeders

(B) Alternators

(C) Transformers

(D) All of the above

298. Differential relays are used for protection of equipments against

(A) Internal faults

(B) Over current

(C) Reverse current

(D) Reverse power

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

299. In a biased differential relay the bias is defined as a ratio of

(A) Number of turns of restraining and operating coil

(B) Operating coil current and restraining coil current

(C) Fault current and operating coil current

(D) Fault current and restraining coil current

300. Both voltage and current signals are required for

(A) A plain over current relay

(B) A differential relay

(C) A directional relay

(D) A biased directional relay

 Dr. Subhash Technical Campus- The Jewel of Junagadh 


Faculty of Degree Engineering - 083
Department of Electrical Engineering -09

Q Ans. Q Ans. Q Ans. Q Ans. Q Ans. Q Ans.


1 D 51 E 101 A 151 C 201 C 251 D
2 D 52 D 102 D 152 A 202 A 252 D
3 C 53 D 103 C 153 D 203 D 253 D
4 A 54 A 104 B 154 C 204 A 254 D
5 C 55 C 105 B 155 D 205 A 255 B
6 C 56 D 106 D 156 D 206 D 256 A
7 C 57 D 107 D 157 C 207 B 257 B
8 C 58 A 108 B 158 A 208 B 258 D
9 D 59 E 109 C 159 C 209 C 259 D
10 A 60 A 110 C 160 B 210 A 260 B
11 E 61 C 111 C 161 C 211 D 261 B
12 E 62 B 112 B 162 C 212 A 262 A
13 B 63 D 113 D 163 B 213 D 263 C
14 B 64 A 114 A 164 D 214 A 264 C
15 C 65 A 115 D 165 A 215 A 265 A
16 D 66 B 116 A 166 C 216 A 266 C
17 D 67 B 117 C 167 A 217 C 267 B
18 A 68 D 118 D 168 A 218 D 268 A
19 A 69 C 119 B 169 B 219 C 269 D
20 C 70 E 120 A 170 D 220 B 270 C
21 D 71 B 121 C 171 B 221 C 271 D
22 D 72 D 122 D 172 B 222 A 272 D
23 B 73 A 123 D 173 D 223 D 273 D
24 A 74 B 124 B 174 D 224 C 274 C
25 C 75 A 125 C 175 C 225 C 275 A
26 D 76 B 126 A 176 A 226 B 276 B
27 A 77 A 127 B 177 C 227 A 277 D
28 C 78 A 128 B 178 B 228 D 278 B
29 C 79 A 129 C 179 D 229 D 279 D
30 A 80 B 130 D 180 B 230 D 280 B
31 D 81 D 131 D 181 A 231 A 281 B
32 C 82 B 132 D 182 C 232 A 282 C
33 D 83 B 133 D 183 C 233 C 283 C
34 D 84 A 134 D 184 B 234 D 284 C
35 A 85 B 135 C 185 A 235 C 285 A
36 A 86 A 136 C 186 C 236 D 286 A
37 A 87 B 137 C 187 C 237 A 287 D
38 C 88 B 138 A 188 D 238 B 288 A
39 D 89 A 139 B 189 B 239 D 289 A
40 D 90 C 140 D 190 B 240 B 290 B
41 A 91 A 141 A 191 B 241 D 291 D
42 A 92 A 142 C 192 B 242 D 292 A
43 C 93 D 143 A 193 D 243 B 293 D
44 C 94 A 144 B 194 C 244 A 294 C
45 A 95 C 145 B 195 D 245 D 295 A
46 C 96 C 146 D 196 B 246 C 296 B
47 B 97 D 147 C 197 C 247 B 297 D
48 D 98 B 148 C 198 D 248 C 298 A
49 C 99 C 149 A 199 B 249 C 299 B
50 C 100 A 150 A 200 C 250 D 300 C

 Dr. Subhash Technical Campus- The Jewel of Junagadh 

You might also like