General features for MPE Series (Deep-cycle) battery

* recombination of up to 99% and freedom from electrolyte * Maintenance-free operation.


Absorbent Glass Mat (AGM) technology for efficient gas Long service life, float or cyclic applications.
* Low self discharge. Maxton Power Tech Co.,Ltd
w w w.maxtonpower.com
Computer designed lead, calcium tin alloy grid for high * Case and cover are available in both standard and flame
maintenance or water adding.
* power density. * retardant ABS (Standard :UL94V0). info@maxtonpower.com

* UL-recognized component. MPE12-225D(12V200Ah)


MPE12-200

Specifications Battery picture and construction Outer dimension and terminal


Outer dimensions (±2mm)
Unit:mm
Nominal Voltage 12V Terminal :T19 522 240

φ16

221
216
Rated capacity (20 hour rate) 225 Ah

6
T19 221 mm (8.69 inches)
Total Height
T12 237 mm (9.29 inches) M8×16

Dimensions
(±2mm) Height 216 mm (8.50 inches)
522 240

Length 522 mm (20.6 inches) Terminal :T12


3

238
216
Width 240 mm (9.45 inches)
Battery Construction φ9

Weight Approx (+3%) 60.5 Kg (133.4lbs) Component Positive plate Negative plate Container Cover

21
Raw material Lead dioxide Lead ABS ABS
Component Electrolyte Separator Safety valve Terminal
25
Raw material Dilute sulfuric acid Fiberglass Rubber Copper

Characteristics Constant current discharge (25oC , 77 oF) Constant power discharge (25oC , 77 oF)
10 hour rate(20 A,10.8V) 200Ah Unit:A Unit:watts
Capacity
5 hour rate(32A,10.5V) 160Ah o
25℃(77℉)
1 hour rate(120 A,9.6V) 120Ah Constant Current(Amp) and Constant Power(Watt) Discharge Table at 25℃(77 F )
Internal Resistance Full charged battery at 25℃(77℉) Approx 4.3 mΩ Time 5min 10min 15min 30min 1h 2h 3h 4h 5h 8h 10h 20h
Capacity 40℃ (104℉) 102%
25℃ (77℉) A 641 422 340 228.0 120.0 70.0 51.4 40.0 33.0 23.40 21.00 11.34
affected 100%
9.60V W
by Temperature 0℃ (32℉) 85% 6611 4507 3648 2451 1296 769 572 450 375 268 243 131.9
(10hour rate) -15℃ (5℉) 65% A 620 381 320 218.0 112.8 66.8 50.0 39.0 32.4 22.80 20.60 11.00
Remaining capaicty Capacity after 3 month storage 91% 10.20V
W 6626 4252 3585 2447 1276 770 579 453 378 267 242 129.0
Self-Discharge Capacity after 6 month storage 82%
A 600 341 280 204.0 109.2 65.2 48.8 38.4 32.0 22.60 20.20 11.00
At 25℃(77℉) Capacity after 12 month storage 64% 10.50V
Terminal type T19 (Option T12) W 6554 3875 3198 2348 1265 756 569 449 375 266 239 130.0
Max. Discharge current 25℃/(77℉) 1600A (5Seconds) A 578 321 260 188.0 105.6 63.6 47.6 37.8 31.2 22.00 20.00 10.80
10.80V
Nominal operating temperature 25℃±5℃(77℉±9℉) W 6490 3702 3000 2178 1229 745 561 446 369 261 238 128.6
Operating Discharge -15℃~50℃ (5℉~122℉) A 559 301 240 168.0 102.0 62.0 46.0 36.8 30.4 21.40 19.00 10.20
Temperature Charge -10℃~50℃ (14℉~122℉) 11.10V
W 6339 3483 2798 1966 1200 733 546 438 363 256 229.4 123.6
Range Storage -20℃~50℃ (-4℉~122℉)
Initial Charging Current less than 50A (Above characteristics data are average values obtained within three charge/discharge cycles,not the minimum values.)
Charge methods Cycle use Voltage 14.5-15.0V
(constant Voltage) Temperature compensation:-30mV/℃
At 25℃(77℉) Standby use Voltage 13.5-13.8V
Temperature compensation:-18mV/℃
Ratings presented herein are subject to revision without notice. Please refer to www.maxtonpower.com to confirm the latest edition. Edition II:2011 Page :1/2
info@maxtonpower.com
w w w.maxtonpower.com
Deep Cycle Battery (VRLA Battery,AGM technology) Maxton Power Tech Co.,Ltd
Maintenance-free Sealed Lead Acid Rechageable Battery MPE12-225D(12V200Ah)
MPE12-200
Discharge characteristics (25℃,77 F) o
Charge characteristics (25℃,77 F) o
Life characteristics of Cyclic Use (25℃,77 F) o

120 120
13.0 0.25C Charged Volume
Voltage(V)

100 0.20C 14.4 100


12.0 Charging Voltage

Charged Volume (%)

Capacity(%)
80

Charging Current (A)


80 0.14C 13.8

Charging Voltage (V)


11.0
40A 20A 10A 0.12C
10.0 60A 60 0.10C 13.2 Charging Voltage 60
400A 200A 120A 100% DOD 50% DOD 30% DOD
0.08C
9.0 40
40 0.06C 12.6
8.0 After 100% Discharge
0.04C After 50% Discharge 20
7.0 20 0.02C 12.0
01 2 3 5 10 20 30 60 2 3 5 10 20 30
Charging Current
0
Minutes Hours 0 200 400 600 800 1000 1200 1400 1600
0 0 8 16 20 28 32 36
Discharge time 4 12 24 Number of cycle (times)
Charge time (hour)/ (25℃/77℉) (DOD means depth of discharge)

Effect of Temperature on capacity Self-discharge characteristics Life Characteristics of standby use (25℃,77 F) o

120 110 120


100 100

Capacity(%)
Residual Capacity (%)
C(A) 100
0.05 C(A)
capacity(%)

80 0 .1 90
A) 80
0 .2 C (
60 80
)
1 .0 C ( A 60
A) 70 Testing conditions: floating voltage: 2.27 to 2.30V/Cell
40 2 .0 C ( ambient temperature: 25 C(77 F)
40
60
20
C:Nominal Capacity
50
40℃(104℉) 30℃(86℉) 20℃(68℉) 20
0
-20 -10 0 10 20 30 40(℃) 40 0
-4 14 32 50 68 86 104 (℉) 0 2 4 6 8 10 12 14 16 18 20 4 6 8
Ambient temperature(-20℃/-4℉—40℃/104℉) Storage time (months) Years

Relationships for open voltage and remained capacity (for reference) Relationship for charging voltage and temperature Temperature effects on floating life

14.0 12V 15
Open Voltage (V)

13.5 15.6
10
Voltage (V)

13.0
15.0 Cycl 2.3V/Cell (charging voltage)
e us

Iife (years)
12.5 e
12.0 14.4
F lo a ti n 5
11.5 13.8 g use
11.0
13.2
10.5
10.0 0 10 20 30 40(℃) 0
-10 10 20 30 40 50 60
0 20 40 60 80 100 32 50 68 86 104 (℉)
14 Temperature (℃)
Residual capacity (%) at 25℃ Ambient temperature(-20℃/-4℉—40℃/104℉)

Ratings presented herein are subject to revision without notice. Please refer to www.maxtonpower.com to confirm the latest edition. Edition II:2011 Page :2/2