You are on page 1of 36

Portfolio Overview; June 2020

- Grouping of products

Performance
Manual valves: Automatic controls: improving
SVL, Safety ICS, EVRA automation:
ICM, ICF, AKS 4100

Manual systems Automated systems High-end/enhanced systems

1 | Danfoss Cooling – IRF Classified as Business


Basic operation & maintenance

Flexline Valve (PS52)

• SVA,REG,CHV,SCA-X,FIA
• SVA DH-DL size 250 / 300
• STC (PS 25 bar)

2 | Danfoss Cooling – IRF Classified as Business


Stop valve
– type SVA 80-150

Cap O-ring
Spring loaded
Packing gland
Teflon ring
Grease
Identification ring
Spindle
O-ring
Bolts Packing washer
- Aluninium
Valve bonnet Gasket

Balls
Soft back seat

Cone, Cone seal Disc spring

4 | Danfoss Cooling – IRF Classified as Business


SVL-Flexline Platform ( Part program; up to DN125 )

Overhual kit
Spare part
Inspection kit Repair kit

5 | Danfoss Cooling – IRF Classified as Business


Regulating valve
– type REG-SA and
REG-SB 15-40

Packing gland Seal cap

Identification
ring Spindle
Bonnet,Flange

Gasket O-ring
- non asbestos
Spring loaded
Housing Teflon ring
Disk spring O-ring

Cone Packing washer


- Aluminium
O-ring Bonnet,Insert

6 | Danfoss Cooling – IRF Classified as Business


Stop check valve type
-SCA-X 50-125

Spindle seal cap and gasket O-ring

Packing gland
Valve bonnet
Marking label
Bolts
Spring loaded
Teflon ring
Gasket
Packing washer Fiber, non asbestos
- Aluminium
Housing
Spring
Spring ring
Guide sleeve
Valve plate
Cylinder with seat
Teflon ring

O-ring

7 | Danfoss Cooling – IRF Classified as Business


Filter
– type FIA 50-200

Gasket

Filter element

Housing
Marking label
- Aluminium
Packing washer
- Aluminium
Pressure relief (screw)

Cover
Bolts
- Stainless steel

8 | Danfoss Cooling – IRF Classified as Business


Filter – type FIA
Note

9 | Danfoss Cooling – IRF Classified as Business


Solenoid valve

ICF/EVRAT

All can function


as solenoid valve !!
10 | Danfoss Cooling – IRF Classified as Business
Solenoid valve,
EVRA(T) 10 -20

11 | Danfoss Cooling – IRF Classified as Business


Solenoid valve
EVRA 25

12 | Danfoss Cooling – IRF Classified as Business


Solenoid valve,
EVRA 32

13 | Danfoss Cooling – IRF Classified as Business


Solenoid valve,
ICS-1

14 | Danfoss Cooling – IRF Classified as Business


Control valve,
ICS-3

SI

P
S II

15 | Danfoss Cooling – IRF Classified as Business


ICS Valve; Pilot valve

16 | Danfoss Cooling – IRF Classified as Business


ICV group ; ICS Valve

17 | Danfoss Cooling – IRF Classified as Business


ICS Valve; Pilot valve
OLD

NEW

18 | Danfoss Cooling – IRF Classified as Business


ICLX Valve

19 | Danfoss Cooling – IRF Classified as Business


EVM NO EVM NC

ICLX Valve

Hot gas inlet

Closed Bleed Open


NC: Closed NO: Open NC: Open NO: Closed NC: Open NO: Closed

External External External


pressure inlet pressure inlet pressure inlet

ICEDRAW.DK ICEDRAW.DK ICEDRAW.DK

20 | Danfoss Cooling – IRF Classified as Business


ICLX Valve

21 | Danfoss Cooling – IRF Classified as Business


Unbox ICS/ICLX valves
Size DN25-80 (ICSH max at size DN80 ) Size 100-150

Top part is square shape; 4 bolts Top part is circle shape; 8 bolts

Keep plastic cap closed, the internal surface of valve is sensitive!!....remove when prior to weld only

22 | Danfoss Cooling – IRF Classified as Business


Unbox ICS/ICLX valves
Don’t lost small item or you’ll had problem later when start up

For ICS ; don’t for get blank plug and their insert

Blanking plug A + B
This picture shown both
A and B had put together

Don’t forget aluminum


gasket and O-ring

23 | Danfoss Cooling – IRF Classified as Business


Unbox ICS/ICLX valves
Don’t lost small item or you’ll had problem later when start up

For ICLX ; in box along with gasket set, had included 1 EVM NO, EVM NC, 2
screws for change over 2 to 1 step, External for Pilot and damping orifice

Noted

Dampening orifice is mandatory to be


installed when hot gas (or external) pilot
pressure is 2 bar greater than valve’s inlet
pressure….or else ICLX may damage!!

• Orifce size 1 mm. dia for ICLX < DN100


• Orifce size 1.8 mm. dia for ICLX
DN100 and above

Keep this two Allen bolts for


Operation step conversion

24 | Danfoss Cooling – IRF Classified as Business


ICM Valve

ICM 20 / ICMTS 20
ICAD 600A ICM 25
ICAD 600A-TS ICM 32
Encoder: Yes

ICM 40
ICM 50
ICM 65
ICAD 1200A
Encoder: Yes
ICM 100
ICM 125
ICM 150

25 | Danfoss Cooling – IRF Classified as Business


ICM Valve

26 | Danfoss Cooling – IRF Classified as Business


27 | Danfoss Cooling – IRF Classified as Business
ICV group ; ICM Valve

28 | Danfoss Cooling – IRF Classified as Business


Liquid level control application, solution from Danfoss

Electronic level switch LLS4000,


As optional

29 | Danfoss Cooling – IRF Classified as Business


Liquid level control application, solution from Danfoss

30 | Danfoss Cooling – IRF Classified as Business


Liquid level sensor - type AKS 4100

Current version
After Sep 2017 Old version
Before Sep 2017

Improved of seal
(Metaglass)

31 | Danfoss Cooling – IRF Classified as Business


Installation
Stand pipe for cable version

32 | Danfoss Cooling – IRF Classified as Business


Installation
Mechanical Connected

Get all welding done


Before assembly sensor
• Work on right bolt
Don’t leave probe end • Not the top one with
Without plastic cover
seal

33 | Danfoss Cooling – IRF Classified as Business


Installation
Software checked!!

PWD
Level
2

34 | Danfoss Cooling – IRF Classified as Business


Configuration
Cut the right cable length

Probe length = Cable length


+ (33-12 ) mm

35 | Danfoss Cooling – IRF Classified as Business


Configuration
Find 4 & 20 mA

36 | Danfoss Cooling – IRF Classified as Business


AKS 4100 Level measurement placed in
standpipe
EKE 347

Wet return line from evaporator Dry suction line


AKS 4100 to compressor
(Cable)

ICM
(open)
Liquid line from
Receiver/Intermediate cooler

Pump line to evaporator

Liquid pump

37 | Danfoss Cooling – IRF Classified as Business