Current And Voltage Unbalance-


Causes And Counter Measures
February 25, 2015

What is unbalance?
Any deviation in voltage and current waveform from perfect sinusoidal, in terms of
magnitude or phase shift is termed as unbalance. In ideal conditions i.e. with only linear
loads connected to the system, the phases of power supply are 120 degree apart in
terms of phase angle and magnitude of their peaks should be same. On distribution
level, the load imperfections cause current unbalance which travel to transformer and
cause unbalance in the three phase voltage. Even minor unbalance in the voltage at
transformer level disturbs the current waveform signi cantly on all the loads
connected to it. Not only in the distribution side but through the transformer, voltage
unbalances disturbs the high voltage power system as well.

Products Applications Knowledge Media Case Studies About


Causes of unbalance
Practical
LOGIN imperfections which can result in unbalances are:-

https://zenatix.com/current-and-voltage-unbalance-causes-and-counter-measures/ 1/8
4/8/2019 Current and Voltage Unbalance- causes and counter measures | Zenatix

1. A three phase equipment such as induction motor with unbalance in its windings. If
the reactance of three phases is not same, it will result in varying current owing in
three phases and give out system unbalance.

– With continuous operation, motor’s physical environment cause degradation of rotor


and stator windings. This degradation is usually different in different phases, affecting
both, the magnitude and phase angel of current waveform.

– A current leakage from any phase through bearings or motor body provides oating
earth at times, causing uctuating current.

2. Any large single phase load, or a number of small loads connected to only one phase
cause more current to ow from that particular phase causing voltage drop on line.

3. Switching of three phase heavy loads results in current and voltage surges which
cause unbalance in the system.

4. Unequal impedances in the power transmission or distribution system cause


differentiating current in three phases.

How to calculate unbalance –


Unbalance is calculated in terms of maximum deviation of current in a phase from the
mean of three phases. To calculate the percentage deviation- [1]

Where- Im is mean of currents in three phases (i.e. Im= (Ir+Iy+Ib)/3

Products Applications Knowledge Media


Ir, Iy, Ib are phase currents. Case Studies About

LOGIN

https://zenatix.com/current-and-voltage-unbalance-causes-and-counter-measures/ 2/8
4/8/2019 Current and Voltage Unbalance- causes and counter measures | Zenatix

Besides, an unbalance can also be quanti ed by comparing the intensity of negative


sequence currents in comparison to the positive sequence currents. The permissible
limit in terms of percentage of negative phase sequence current over positive sequence
current is 1.3% ideally but acceptable upto 2%.[2]

Effects of unbalance:
1. The unbalance decreases the motor ef ciency by causing extra heating in the motor.
Heat generated also effect the equipment life by increasing the operating temperature,
which decompose the grease or oil in the bearing and de-rate the motor windings.

2. In induction motors connected to unbalanced supply, the negative sequence currents


ow along with positive sequence current resulting in decreased percentage of
productive current and poor motor ef ciency. Any unbalance above 3% hampers the
motor ef ciency.

3. Torque (and thus the speed) produced by the motor becomes uctuating. These
sudden changes in torque cause more vibration in the gear box or the equipment
connected to it. The vibration and noise produced damages the equipment and also
reduces the ef ciency of equipment.

4. The variable frequency or speed drives connected to an unbalanced system can trip
off. VFD treats high level unbalances as phase fault and can trip on earth fault or
missing phase fault.

5. Unbalances cause de-rating of power cables and thus increase I2R losses in the
cable. For distribution cables de-rating factor represents the part of total current
giving fruitful outcomes.

6. UPS or inverter supplies also perform with poor ef ciency and inject more harmonic
currents in case of unbalances in the system.
Products Applications Knowledge Media Case Studies About

LOGIN

https://zenatix.com/current-and-voltage-unbalance-causes-and-counter-measures/ 3/8
4/8/2019 Current and Voltage Unbalance- causes and counter measures | Zenatix

7. Negative phase sequence current owing due to unbalance can cause faults in the
motor, resulting in, tripping or permanent damage of the electrical equipment.

Quantifying the losses-


An unbalance of 1% is acceptable as it doesn’t affect the cable. But above 1% it
increases linearly and at 4% the de-rating is 20%. [3]
This implies that- 20% of the
current owing in the cable will be unproductive and thus the copper losses in the
cable will increase by 25% at 4% unbalance.

1. For motors, an unbalance of 5% will result in capacity reduction by 25%. [4]


That
means, the motor current will increase to match the equipment’s torque needs which
will result in proportional copper losses in motor. The voltage unbalance of 3% increase
the heating by 20% for an induction motor.[4]

2. The resistance for negative sequence current is 1/6th of the positive sequence
current which means a small unbalance in voltage waveform will give more current and
thus losses.[4]

Effects on the distribution Transformer-


Transformer offers high reactance to negative phase sequence currents and thus
reduces the level of unbalance on the other side of the system.

– Ideally any distribution transformer gives best performance at 50% loading and every
electrical distribution system is designed for it. But in case of unbalance the loading
goes over 50% as the equipments draw more current.

– Following data represents the ef ciency of transformer under different loading


conditions-[5]

1. Full Load- 98.1%


Products Applications Knowledge Media Case Studies About

2. Half Load- 98.64%


LOGIN

https://zenatix.com/current-and-voltage-unbalance-causes-and-counter-measures/ 4/8
4/8/2019 Current and Voltage Unbalance- causes and counter measures | Zenatix

3. Unbalanced loads- 96.5%

For a distribution transformer of 200KVA rating, the eddy currents accounts for 200W
but in case of 5% voltage unbalance they can rise upto 720W.[5]

Control Measures-
1. All the single phase loads should be distributed on the three phase system such that
they put equal load on three phases.

2. Replacing the disturbing equipments i.e. with unbalanced three phase reactance.

3. Reducing the harmonics also reduces the unbalance, which can be done by installing
reactive or active lters. These lters reduce the negative phase sequence currents by
injecting a compensating current wave.

4. In case the disturbing loads cannot be replaced or repaired, connect them with high
voltage side this reduces the effects in terms of percentage and even controlled
disturbance in low voltage side.

5. Motors with unbalanced phase reactance should be replaced and re-winded.

To identify the exact reasons for unbalance, Zenatix recommends metering at different
loads in the distribution. Zenatix can collect high resolution data from these metering
locations and analyze it to identify the exact causes and control measures that can
result in improvement in the unbalance. Further, such detailed metering will provide
data that can be used to identify other wastages that happen in the day to day
operations of a facility thus providing further bene ts of the installed solution.

Case Study-
For further clari
Products cation on theKnowledge
Applications voltage and current
Media unbalance, three phase
Case Studies currents of
About
two of the zenatix’s customers were analyzed. For the purpose of case study, we can
name the two clients as client1 & client2.
LOGIN

https://zenatix.com/current-and-voltage-unbalance-causes-and-counter-measures/ 5/8
4/8/2019 Current and Voltage Unbalance- causes and counter measures | Zenatix

First, the readings of three phase currents were taken at the frequency of 15 minutes
for a month. Then we need to remove the readings during non-working hours too, as
during such times load current will be quite low and thus a current unbalance of only 2-
3 amps can shown very high percentage unbalance. After re ning the data, percentage
of unbalance was calculated by running simulation on R-software. As all the readings
mentioned are taken at the duration of 15 minutes, we got percentage unbalance
readings for the whole month with the frequency of 15 minutes. These continuous
readings were then plotted.

Products Applications Knowledge Media Case Studies About

LOGIN

https://zenatix.com/current-and-voltage-unbalance-causes-and-counter-measures/ 6/8
4/8/2019 Current and Voltage Unbalance- causes and counter measures | Zenatix

It is clear by only looking at the plot that for client1’s system is more balanced as
compared to client2’s. Further analysis was done for getting consolidated data on what
is maximum unbalance, what is the average unbalance and which phase is causing it.

Following data was tabulated based on the results obtained after analysis.

Fig.1 – Shows the plot of percentage unbalance with time for zenatix’s client with
balanced system.

Fig.2 – Shows the plot of percentage unbalance with time for zenatix’s client with
balanced system.

Fig.3 -Shows the comparison between the system of two clients.

References-
[1] – De-rating of Induction Motors Operating with a Combination of Unbalanced
Voltages and Over- or Under-voltages- P.Pillay, Jean Newell Distinguished Professor in
Engineering, Clarkson University AND P.Hofmann, Manager of Power Quality ,
Manhattan, NY. [2]- Limits for Voltage Unbalance in the Electricity Supply System,
Version 1.0, 30th November 2005, Prepared by- Abu Dhabi Distribution Company, Al
Ain Distribution Company and RASCO. [3]- CHK GridSense PTY Ltd. Suite 102, 25
Angas Street, Meadowbank, NSW 2114, Australia- GridSense.com [4]-
http://www.larsentoubro.com/lntcorporate/ebg/html/negative_sequence.html [5]-
http://www.iaeng.org/publication/IMECS2011/IMECS2011_pp948-952.pdf

Products Applications Knowledge Media Case Studies About

LOGIN

https://zenatix.com/current-and-voltage-unbalance-causes-and-counter-measures/ 7/8
4/8/2019 Current and Voltage Unbalance- causes and counter measures | Zenatix

Next Post

Zenatix @ Startup Innovation Showcase (Smart Cities)

ALL RIGHTS RESERVED | P R I VAC Y P O L I C Y

https://zenatix.com/current-and-voltage-unbalance-causes-and-counter-measures/ 8/8

You might also like