Professional Documents
Culture Documents
REPORT
Penetration distance:
The distance between the two air terminals should be chosen in such a way that, the protection is
provided for all the objects placed on the surface to be protected. The protection of the objects
placed on the surface can be ensured by calculating the penetration distance of the rolling sphere.
The distance between the level of air terminals and the least point of sphere in the space between
the air terminals is called penetration distance.
Let us consider an object of height ‘h’ placed on the surface to be protected. Let ‘ht’ be the height of
the air terminal, ‘p’ be the penetration distance and ‘d’ be the distance between the two terminals.
𝑝 < (ℎ𝑡 − ℎ)
Distance between air terminals:
The penetration distance of the rolling sphere below the level of conductors in the space between
the conductors can be calculated by using the below formula (IS 62305-3).
2
𝑝 = 𝑟 − √[𝑟 2 − (𝑑⁄2) ]
Where,
p – penetration distance
r – radius of rolling sphere
d – distance between the air terminals
For attaining a particular penetration distance, we can derive the required distance between the air
terminals from the above equation.
𝑑 = 2 ∗ √[2 ∗ 𝑝 ∗ 𝑟 − (𝑝)2 ]
If there are no objects protruding from the structure to be protected, then the penetration distance
can be increased up to the height of the air terminal to provide maximum protection. At this
condition, the distance can be calculated by substituting the value of height of air terminal (ht) in
place of penetration distance (p).
𝑑 = 2 ∗ √[2 ∗ ℎ𝑡 ∗ 𝑟 − (ℎ𝑡 )2 ]
A down conductor should be installed at each exposed corner of the structure and as far as
practicable, they form a direct continuation of the air-termination conductors. Down conductors
are installed in such a way that they provide the shortest and most direct path to earth.
Down conductors, even if covered in insulating material, shall not be installed in gutters or water
spouts. The effects of moisture in the gutters lead to intensive corrosion of the down conductor.
Designing:
Site Details:
Design Considerations:
Ventilators and Solar panels are mounted on the metal roof sheets. To provide protection for them,
a penetration distance of 0.5m is considered for the designing. The penetration distance should be
less than the difference between the height of air terminal and height of the object to be protected.
𝒑 < (𝒉𝒕 − 𝒉)
𝒅 = 𝟐 ∗ √[𝟐 ∗ 𝒑 ∗ 𝒓 − (𝒑)𝟐 ] 𝒎
Here,
r = 60 m for LPL IV and
p = 0.5 m
Air terminals:
The entire air terminal assembly shall be divided into two parts for designing purpose.
i) Along the width of shed
ii) Along the length of shed
Along the width of Shed:
Hence, twelve numbers of air terminals at an equal interval of 15 m can be placed along the width
of the shed to provide protection for the entire 165m of the shed.
Total number of air terminals = no. of air terminals along length * no. of air terminals along width
= 12*5
Down Conductor:
The total down conductor used for the LPS can be calculated by dividing the system into two parts.
Hence, for LPS of class IV, the distance between the down conductors (DC) shall be 20m.
= 18+2
Total no. of DC = 20
Total length of DC connecting to earth = (No. of DC along length*18) + (No. of DC along width*20)
= (18*18) + (2*20)
= 324 + 40
Earthing System:
Horizontal or vertical earth electrodes installed outside the structure to be protected should be
connected to each down-conductor. Hence, one of earth electrode can be installed for each down
conductor and all the earth electrodes shall be interconnected to form a grid. The earth electrodes
should be installed at a distance of 1m from the wall.
No. of down conductors = 20
No of earth pits = 20
Conductors needed for interconnection = (2*170) + (2*65)
= 470 m