Switchyard PMCC Load Analysis

Bus Section – I
S. No. Description Rating Duty C/I LF Mode Max. Demand
KW R S KW KVA
1 Feeder for Lighting Transformer 64 C 0.9 1 57.6 67.76
2 Package Chiller – 1 power 45 C 0.9 1 40.5 47.65
supply
3 Package Chiller – 3 power 45 C 0.9 1 0.0 0.0
supply
4 Feeder for vent fans swyd 15 C 0.9 1 13.5 15.88
control room cable vault
5 Feeder for vent sys battery and 7.5 C 0.9 1 6.75 7.94
charger room swyd
6 AHU Fan 1 7.5 C 0.9 1 6.75 7.94
7 AHU Fan 4 7.5 C 0.9 1 0.0 0.0
8 Cooling tower fan 1 7.5 C 0.9 1 6.75 7.94
9 Condenser water pump 1 3.7 C 0.9 1 3.33 3.92
10 Condenser water pump 3 3.7 C 0.9 1 0.0 0.0
11 BMK 1 2.2 C 0.9 1 1.98 2.33
12 BMK 2 2.2 C 0.9 1 1.98 2.33
13 BMK 3 2.2 C 0.9 1 0.0 0.0
14 BMK 4 2.2 C 0.9 1 1.98 2.33
15 Feeder for AHP control room 15 C 0.9 1 13.5 15.88
AC
16 220 V DC Battery charger 15 C 0.9 1 0.0 0.0
17 48 V DC Battery Charger 5 C 0.9 1 4.5 5.29
18 Feeder for transformer oil filter 15 I 0.4 1 0.0 0.0
19 Single phase 230 V outlets (5 5 I 0.4 1 2 2.35
Nos.)
20 Feeder 1 for ICT CCC 2 C 0.9 1 1.8 2.12
21 Spare feeders I 0.4 1 0.0 0.0
Connected load in KW 272.2 162.92 191.67
Bus Section – II
S. No. Description Rating Duty C/I LF Mode Max. Demand
KW R S KW KVA
1 Feeder for Lighting Transformer 64 C 0.9 1 0.0 0.0
2 Package Chiller – 2 power 45 C 0.9 1 40.5 47.65
supply
3 220 V DC Battery Charger 15 C 0.9 1 13.5 15.88
4 Welding Db supply 30 C 0.9 1 27 31.76
6 AHU Fan 2 7.5 C 0.9 1 6.75 7.94
7 AHU Fan 3 7.5 C 0.9 1 6.75 7.94
8 Cooling tower fan 2 7.5 C 0.9 1 6.75 7.94
8 Cooling tower fan 3 7.5 C 0.9 1 0.0 0.0
Feeder for vent in AC plant 5 C 0.9 1 4.5 5.29
room – swyd control room
Feeder for vent fans switchgear 5 C 0.9 1 4.5 5.29
room – swyd control bldg
48 V DC Battery charger 5 C 0.9 1 0.0 0.0
9 Condenser water pump 2 3.7 C 0.9 1 3.33 3.92
11 BMK 5 2.2 C 0.9 1 0.0 0.0
12 BMK 6 2.2 C 0.9 1 1.98 2.33
13 BMK 7 2.2 C 0.9 1 1.98 2.33
14 BMK 8 2.2 C 0.9 1 0.0 0.0
15 STP sump pump 2 2.2 C 0.9 1 0.0 0.0
16 Feeder for heater in AHU room 2 I 0.4 1 0.8 0.94
17 Feeder for humidifier in AHU 2 I 0.4 1 0.8 0.94
room
18 Fresh air fan for AHU room 1.5 C 0.9 1 1.35 1.59
19 Feeder for CHP Control room 15 C 0.9 1 13.5 15.88
AC
20 Feeder for control panel of AC 2.2 C 0.9 1 1.98 2.33
system ESP room
21 Feeder for control panel of AC 2.2 C 0.9 1 1.98 2.33
system Swyd control room
22 Single phase 230 V outlet (5 5 I 0.4 1 2 2.35
Nos)
23 Feeder – 2 for ICT CCC 0.0 0.0
24 Spare 0.0 0.0
25 Connected load in KW 245.6 141.93 166.98
Total connected load in KW 517.8 304.85 358.65

Maximum Demand - 359 KVA


Maximum demand with 10% margin - 395 KVA
Transformer rating selected – 630 KVA
Full load current of transformer selected – 876 Amps.
Switchgear incomer rating – 1250 Amps.