Professional Documents
Culture Documents
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
1
Coefficient of Utilization (CU) Coefficients of Utilization (CU)
Factors influencing coefficient of utilization: Coefficient of utilization is based on room cavity ratio
(RCR)
The efficiency of the luminaire RCR is five (5) times the ratio of total vertical surface
The luminaire distribution area to total horizontal surface area within the room
cavity, and therefore indicates the relative space
The geometry of the space proportions.
The reflectances of the room surface
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Floor cavity ratio – is the space between the workplane and the
floor computed using the equation below in relation to room
cavity ratio:
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
It is necessary to convert the actual ceiling reflectance into an Room cavity height (hRC) = Luminaire height – Workplane height
effective ceiling cavity reflectance (pCC) and the actual floor Assuming a workplane height of 0.76m (typical desk height)
reflectance must be converted to an effective floor cavity reflectance
(pFC). hRC = 2. 59 m – 0.76m
= 1.83m
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
2
CU Determination CU Determination
In this example, the luminaires are recessed in the ceiling so the Step 2. Since the Lumen Method considers what occurs only within
luminaire height is the as the ceiling height. Computing the room the room cavity, the ceiling and floor cavities are replaced with their
cavity ratio, we have: effective reflectances.
To find the effective reflectance of a floor or ceiling cavity, find the
RCR = 5 x Room cavity height (Length + Width) floor cavity ratio and ceiling cavity ratio using the equations below
Length x Width
RCR = 5 x 1.83m (3.05m + 4.57m)
3.05m x 4.57m
RCR = 5
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
CU Determination CU Determination
Step 3. Find the effective cavity reflectances using cavity surface
reflectances. The surface that is opposite the opening to the cavity is
called the base cavity. The base reflectance, the wall reflectances, and
the cavity ratio determine the effective cavity reflectance. Using the
IESNA Lighting Handbook, look for the cavity reflectances and cavity
ratios.
For the ceiling cavity, the base reflectance is the actual ceiling surface
reflectance while the floor cavity, the base reflectance is the actual floor
surface reflectance.
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
CU Determination CU Determination
Step 4. Once all room cavity reflectances and the room CU = 0.50, which means that 50% of the lumens given off by the
cavity ratio are known, the CU value can be determined lamps reach the workplane and the other 50% are absorbed by the
by selecting the appropriate value from the luminaire’s luminaire or the room surfaces and never reach the workplane.
CU table.
Continuing with Example 1, the following assumptions
are made after consulting the IES Lighting Handbook
Table on Effective Reflectances:
Effective Ceiling Cavity Reflectance, ρCC = 0.70
Wall Reflectance, ρW = 0.50
Effective Floor Cavity Reflectance, ρFC = 0.20
RCR = 5 (calculated in Step 1)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
3
Coefficients of Utilization for Some Luminaire Light Loss Factor
Two types of Light Loss Factor (LLF)
Recoverable
Non-recoverable
Total Light Loss Factor (LLF) is the product of
the individual light loss factors, recoverable and
non
- recoverable
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
4
Room Surface Dirt Depreciation Luminaire Dirt Depreciation
Luminaire Dirt Depreciation Factor (LDD)
depends on three (3) aspects of the situation:
The amount and type of dirt in the environment (a
clean office environment compared to a dirty
manufacturing facility)
The type of luminaire used
The expected cleaning cycle for the equipment
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
5
Heat Extraction Thermal Factor Voltage to Luminaire Factor
Heat extraction factor is the fractional lumen loss High or low voltage at the luminaire will affect
or gain due to airflow the lumen output of lamps
Airflow has an effect on lamp temperature and High voltage condition will increase the lumen
lamp lumens especially those air handling output of lamps over their rated output
fluorescent luminaires which are integrated with Low voltage condition will reduce the lumen
the HVAC system as a means of introducing or output
removing air from the room The rate of change of lumen output with a
voltage change varies with each light source, but
has the greatest effect on incandescent lamps
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
6
Luminaire Surface Depreciation Loss Factor Determination
Example 2. LLF Determination
Luminaire surface depreciation results from
Detailed description of the determination of the light loss factors can be
adverse changes in metal, paint and plastic found in the IESNA Lighting Handbook. The product of the recoverable
components that result in permanently reduced factors and the non-recoverable factors will give us the total light loss
factor.
light output
Luminaire surface depreciation factor adjusts
Recoverable Factors
light output to original reflectance
Lamp Lumen Depreciation (LDD) 0.90
Lamp Burnout Factor (LBO) 1.00
Luminaire Dirt Depreciation Factor (LDD) 0.94
Room Surface Dirt Depreciation Factor (RSDD) 0.96
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
7
Calculated Illuminance Calculated Illuminance
Example 2. Find the number of luminaires needed in a room given the
By rearranging the Lumen Method equation, it is following:
possible to find the number of luminaires required to
meet a specific average illuminance level: Room dimensions: 9.15m by 9.15m by 3.5m
Target Illuminance: 300 lux average maintained
(lumens/lamp) x (lamps/luminaire) x (no. of luminaires)
x CU x LLFTOTAL Working Plane Height: 0.76m
EWP = Luminaire: Recessed round
AWP
Lamp: 70 watt metal halide, 5600 lumen initial output
AWP x EWP Reflectances (ρ): Ceiling cavity 0.70
No. of =
luminaires (lumens/lamp) x (lamps/luminaires) Walls 0.30
x CU x LLFTOTAL Floor Cavity 0.20
Assume LLFTOTAL = 0.75
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Step 4. Obtain Effective Floor Cavity Reflectance (ρFC) using Tables in 5600 lumen x 1 x 0.55 x 0.75
CU determination for metal halide lamps
Number of luminaires = 10.9
Step 5. Obtain Coefficient of Utilization (CU) from Manufacturer’s Data In this example, 12 fixtures can be spaced uniformly in a 3 by 4 pattern.
Although 12 is more than the calculated value of 10.9 fixtures, results within a
The CU based on calculated value of RCR and the given reflectances, we 10% margin is generally acceptable for meeting this target criterion
get 0.55 as the answer.
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
8
Spacing Criteria Spacing Criteria
For fluorescent luminaires, it is necessary to first establish the
The exact spacing between rows is calculated by dividing the room
maximum number that can be installed in one row. the maximum number
width by the number of rows
is calculated by subtracting at least 0.3 meter from the room length and
then dividing by the length of the luminaire. Spacing between luminaires in each row is calculated by dividing
the room length by the number of luminaires per row.
spacing between the outer luminaires and the adjacent wall is one-
half of the luminaire spacing
If desks or other work areas are to be located alongside the walls,
then the wall-to-luminaires spacing should be reduced to one-third of
the luminaire spacing
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Examples:
What is the illuminance on a wall display from a
spotlight aimed at the display?
How much light is striking a point on the façade of a
building or in a parking lot from a floodlight?
Factors to consider
Luminous intensity
Distance
Orientation of the surface
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
9
Luminous Intensity Luminous Intensity
Planar symmetrical
Luminaire distribution is Asymmetrical
confined to two vertical
planes separately Asymmetry present in one of
the Planes of measurement.
Typical distribution for
Fluorescent Lamp
luminaires and Road
Lighting
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Distance Distance
Distance between a surface and the source affects the illuminance Light Source
(luminous flux per unit of area) striking that surface
Surface of a given area that is closer to the source captures a larger
D
portion of the flux in the cone than a surface of the same given area
i
that is further away E = I/ d2 s
Considering the luminous intensity as the luminous flux (lumens) t
Solid Angle w
leaving a source in a cone traveling in a specific direction, as the a
area increases the iluminance decreases while the luminous flux n
remains the same c
I e
Inverse Square Law states that the cross-sectional area of the cone
increases with the square of the distance from the source.
Therefore, the illuminance on this surface varies inversely with the
square of the distance from the source
Plane A P d
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
E = I/ d2 cos θ
Where:
E = Illuminance on the surface
θ is the angle between the light ray coming from the
I = Luminous intensity of the source in the direction
source to the point, and a line that is perpendicular
of the surface (normal) to the plane or surface on which the illuminance
is being measured or calculated
d = Distance from the source to the surface
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
10
Orientation of the Surface Illuminance at a Point-
Point-Direct Component
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Illuminance at a Point-
Point-Direct Component Illuminance at a Point-
Point-Direct Component
Using the equation; Example 2. This example will consider the illuminance at a single point
on a horizontal surface from two luminaires aimed straight down. An
assumed LLF of 0.85 will be used and Luminaire #1 is the same in
E = I/ d2 x cos θ x LLFTOTAL Example 1.
E = 2200 cd x cos 15° x 0.85 D1 = 2.13m θ1 = 15°
2.13 m2 D2 = 2.29m θ2 = 25°
E = 398 lux (maintained) β1 = 15° I1 = 2200 cd
β2 = 25° I2 = 2000 cd
This tells us that 398 lux will strike the point in question directly from
the luminaire and no reflected light is calculated. The answer is a E1 = 398 lux (from previous calculation)
maintained illuminance level since a light loss factor of 0.85 was
E2 = 291 lux (from calculations)
included to account for the loss of light over time due to reduced lumen
output of the lamp and dirt on the luminaire surfaces. ETOTAL = E1 + E2 = 689 lux
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Illuminance at a Point-
Point-Direct Component Illuminance at a Point-Direct Component
Example 3. This example will consider the illuminance at multiple points In Table 1, illuminance at point 2 is greater than at point
on a vertical surface from a luminaire aimed at the surface. An assumed 1 and illuminance at point 3 is the least. This is because
LLF of 0.85 will be used. the distance at point 2 is less than point 1 and the angle
Table 1. Components of Example 3 theta (θ ) at point 2 is less than at point 1, despite the fact
Point Distance, m θ°C β°C I LLF Emaintained
that the intensity in that direction is less.
1 1.74 45 0 2300 0.85 463 lux
2 1.37 27 18 2225 0.85 893 lux
Similar reasoning can be used with regard to point 3.
3 2.29 56 11 2100 0.85 194 lux
These two factors cause the illuminance at point 2 to be
The luminaire is now aimed at the vertical surface so β is no longer greater than the illuminance at point 3.
measured from straight down, and β and θ are no longer equal.
Illuminance is calculated using the same equation as the prior
examples.
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
11
Sample Calculations Sample Calculations
Sample Calculation 1:
The room to be lighted is as follows:
The calculations presented using various tables and figures
are only meant to give the user of this module a general Type of building : Commercial
overview of the design of lighting system, showing individual Area/activity : Drafting/tracing paper, low contrast
steps from the selection of the recommended luminance Average age of worker : 35 years
level, to the design of lighting layout.
Demand for speed and/or accuracy : Important
Task background reflectance : 75%
Size of room : 10.0 by 13.25 meters; 2.91 m ceiling
Height of work plane : 0.91 m
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
12
Sample Calculations Sample Calculations
Step 4: Determine the effective floor cavity reflectance (pFC) from IES
Step 3: Calculate the cavity ratios using Equations and indicate
Lighting Handbook Table. Note that the effective ceiling cavity
dimensions.
reflectance is the same as the actual ceiling reflectance.
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
13
Sample Calculations Sample Calculations
Step 7: Calculate the total initial lamp lumens (TILL) using the Step 8: Calculate the required number of luminaires using equation
equation below: below. From IES Lighting Handbook Table, the initial lumens
are 3175 and there are two lamps per luminaire.
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
14
Sample Calculations Sample Calculations
Step 11: Check the maximum spacing allowed between rows: Step 12: Draw plan of the room and indicate the locations of
- From the IES Lighting Handbook Table, for luminaire 2, SC luminaires
is 1.4 for crosswise spacing.
- Maximum spacing = 1.4 x hRC = 1.4 x 2.0 = 2.8 m
- 2.0 m is within the limits
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
In this example, the designer should start over with F32T8 or Room dimensions:
F36T8 lamps operated with electronic ballasts and go through the
calculations again to reduce the UPD. L = 15.00 m (length)
W = 8.00 m (width)
H = 3.40 m (ceiling-to-floor height)
h = 2.55 m (luminaire-to-work plane height)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
15
Sample Calculations Sample Calculations
Required quality of light: Lighting design data is available in EULUMDAT format
Conference room: Light color ww or nw, Ra group 2A for most OSRAM luminaires. EULUMDAT data can be
Illuminance read by a wide range of programs for lighting design,
E = 300 lux
including DIALUX (Version 2.0 and higher), RELUX,
SPECTRAL ƒn LUMAGIC and RADEMACHER BELWIN.
Selected lamp:
The table below shows the room utilization factor for
2 DULUX L 24 W, numerous combinations of room factors and reflectances
Light color LUMILUX Warm (always assuming ideal dispersion).
(LF 31/830), Ra group 1B, The illuminance E required in a room of area L x W is
Luminous flux per lamp achieved with n luminaires that have an efficiency çLB
and with lamps with a luminous flux φ.
ƒn= 1800 lumen
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Result:
24 luminaires (ç is rounded up)
Recommended arrangement:
3 rows of 8 luminaries
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
16
Sample Calculations Sample Calculations
Sample Calculation 3. Given are the following :
General Information:
Project Identification: Shopping Mall
Width = 15 m
Average maintained Illuminance: 400 lux or 400 lux /1lux x 10.76fc
Length = 100 m
= 37.17 fc
Ceiling height = 3.5 m
Lamp data: 26W TC-D (compact fluorescent lamp)
Desired Illumination = 400 lux
Lamp flux: 1800 lumen (as per manufacturer’s data)
Type of Luminaire = 200mf Downlight w/ 26W TC-D Lamp
Luminaire data:
Manufacturer: Zumtobel Staff (Fumaco)
Model No: Panos HG 2/26W TC-D VVG 200
ñw = 50%
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Step 1: Fill in all information in sketch If from manufacturer’s data, CU table are given based on
Room Cavity Ratio
L (Length) = 100 m
W (width) = 15 m
h (height) = 3.5 m
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Ceiling : cc = 70%
where:
Wall : w = 50%
Floor : fc = 20%
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
17
Sample Calculations Sample Calculations
Step 4: Obtain Coefficient of Utilization from manufacturer's data:
by interpolation CU @ 1.34:
Based on Fig. 9-28 of IESNA Handbook @ RCR 1.34 @
70/50/20 reflectance
RCR = 0.64
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
18
Sample Calculations Sample Calculations
Step 8: Select a practical lay out for the luminaire. Step 9: Calculate Luminaire Spacing
Spacing Criterion, SC = spacing distance/mounting height
As per Figure 9-28 of IESNA Handbook, for 8" open reflector Number of luminaires per row = (15m-5.25m)/5.25 = ~ 2
using 2-26 CFL, SC = 1.5
Number of luminaires per column = 343/2 = 172 luminaires x 5.25
Spacing distance = 1.5 x 3.5 m = 5.25 m m (spacing) = 903 m which exceeded 150 m.
Spacing criterion with this case is not applicable
For this distance, 343 luminaires required to achieve 400 lux Assuming spacing at end rows = 1 m
illumination cannot be placed for the given area.
Number of luminaires/row = 15-2(1)/2 = 6.5 ~ 7 luminaires/row
Transverse spacing = 15-2(l)/6= 2.17 m
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
19
Sample Calculations Sample Calculations
Sample Calculation 4. Given the following data:
Width = 15 m
Length = 100 m
Ceiling height = 3.5 m
Desired Illumination = 400 lux
Type of Luminaire = 200mf Downlight w/ 26W TC-D Lamp
Luminaire : 8" Downlight with 70W Metal Halide Lamp
Lamp Flux : 6600 lumens (from manufacturer’s data) from Table
(Figure 9-28) of IESNA handbook CU of metal halide downlight #10
@ 70/50/20 reflectance & RCR of 1.34
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
20
Sample Calculations Sample Calculations
Transverse spacing = 15m - 2(1.175m)/5 Draw plan of the room and indicate the locations of luminaries.
= 2.53 m
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
Module 4 –Lighting Calculations Philippine Efficient Lighting Market Module 4 –Lighting Calculations Philippine Efficient Lighting Market
Transformation Project (PELMATP) Transformation Project (PELMATP)
21