An error code will appear on the display automatically when a fault causes the
inverter to trip. The following table lists the cause associated with the error.
Causets)
ay
‘Over-current event while at
constant speed
The inverter output was short-circuited, or the
motor shaft is locked or has a heavy load.
E02
‘Over-current event during
deceleration
These conditions cause excessive current for
the inverter, so the inverter output is turned
03
‘Over-current event during
acceleration
OFF.
The dual-voltage motor is wired incorrectly.
Eo
‘Over-current event during
other conditions
E05
‘Motor overload protection
/When a motor overload is detected by the
electronic thermal function, the inverter trips
Jand turns OFF its output.
Check that the thermal model is property set in
Parameter b0 (2, b0 13, 69 10, b9 I! and b9 12.
Check if the application can accept softer accel-
ration rates to minimize peak currents FOO2/
/Feoz/A0s2/R2S2).
Check if motor parameters are not correctly set
(H020 to HO34 or HO0S), depending in motor
[control method (ROY4/RE4),
06
Braking resistor overload
protection
When the BRD operation rate excoods the set
ting of "8090", this protective function shuts off
the inverter output and displays the error code.
en
‘Over-voltage protection
[When the DC bus voltage exceeds a threshold,
[due to regenerative energy from the motor.
E08
EEPROM error
[When the builtin EEPROM memory has prob-
lems due to noise or excessive temperature,
{the inverter trips and turns OFF its output to the
motor.
Ero.
Code
Cause(s)
E03
Under-vorlage error
‘A decrease of internal DC bus voltage below &
threshold results in a control circuit fault. This
condition can also generate excessive motor
heat of cause low torque. The inverter trips and
turns OFF its output.
Eo
‘Current detection error
Tan error occurs in the internal current deteo-
tion system, the inverter will shut off its output
and display’the error code.
‘GPU error
‘A malfunction in the builtin CPU has occurred,
so the inverter trips and turns OFF its output to
the motor.
External tip
‘Asignal on an intelligent input terminal
configured as EXT has occurred. The inverter
trips and turns OFF the output to the motor.
usr
When the Unaltended Start Protection (USP)
js enabled, an error occurred when power is
applied while a Run signal is present. The
inverter trips and does not go into Fun Mode
until the error is cleared.
En
Ground fault
The inverter is protected by the detection of
ground faults between the inverter output and
the motor upon during powerup tests. This
feature protects the inverter, and does not pro-
tect humans.
Es
Input over-voltage
The inverter tests for input over-voltage after
the inverter has been in Stop Mode for 100 sec-
fonds. If an over-voltage condition exists, the
inverter enters a fault state. After the fault is
cleared, the inverter can enter Run Mode again.
Ea7
Tnverter thermal tip
When the inverter internal temperature is above
the threshold, the thermal sensor in the inverter
modiila datacts tha excessive tamnaratire ofthe power devices and trips, turing the inverter
output OFF.
Eee
‘CPU communication error
‘When communication between two CPU fails,
Inverter trips and displays the error code.
E25
Main circuit error (3)
The inverter will tip if the power supply estab-
lishment is not recognized because of a mal-
function due to noise or damage to the main
circuit element.
E30
Driver error
instantaneous overcurrent occurs the Inverter
will shut off IGBT's output to protect the main
circuit element. After ripping due this protective
function the inverter cannot retry the operation.
E35
Thermistor
When a thermistor is connected to terminals [5]
and [L] and the inverter has sensed the temper-|
ature is too high, the inverter trips and turns
OFF the output,
E36
Braking error
When “0 f has been specified for the Brake
Control Selection (b120), the inverter will tr
itcannot receive the braking confirmation signal,
within the Brake Wait Time for Confirmation
(b 124) after the output of the brake release sig-
fal. Or when the output current doesn't reach.
the brake release current (b 126) during the
brake wait time for release (b 12 1)
En
Safe Stop
Safe stop signal is given.”
E38
Low-speed
‘overload protection
overload occurs during the motor operation at
a very low speed, the inverter will detect the
overload and shut off the inverter output.
Eso
‘Operator connection
When the connection between inverter
and operator keypad failed, inverter trips and
displays the error code.
Name Tause(s)
EY Modbus communication | When “trip” is selected (C016=00) as a
error behavior in case of communication error,
inverter trips when timeout happens.
[E13 | Drive Programming invalid | The program stored in inverter memory has
instruction been destroyed, or the PRG terminal was.
turned on without a program downloaded to the
inverter.
E41 [Drive Programming ‘Subroutines, i-statement, or fornext loop are
nesting count error nested in more than eight layers
ES | Drive Programming nvertet found the command which cannot be
instruction error executed.
[ES to | Drive Programming user | When user -defined tip happens, inverter trips
Go trip (0 to 9) and displays the error code.
[EGO to | Option errors (ervar in con- | These errors are reserved for the option board
[E69 nected option board, the | Each option board can show the errors for adi
meanings change upon | ferent meaning .. To check the specific mean-
the connected option)._|ing, please refer to the corresponding option
board user manual and documentation.
[é80 | Encoder disconnection |i the encoder wiring is disconnected, an
encoder connection error is detected, the
fencoder fails, oran encoder that does not
support line driver output is used, the inverter
will shut off its output and display the error
‘ode shown on the right.
EB1 [Excessive speed Tithe motor speed rises to “maximum frequency
(8004) x overspeed error detection level (PO26)"
oF more, the inverter will shutoff its output and
isplay the error code shown on the right.
[£83 | Positioning range error If current position exceeds the position range
specification (PO12-P0723), the inverter will shut
ff its output and display the error code.