You are on page 1of 3

JOB NO. DOCUMENT NO. REV.

ENGINEERING CENTER 26070 - 203 MTD - 420 - JT001 1


REFINING DIRECTORATE SHEET 2 OF 3
No
DATA SHEET CRUDE STORAGE TANK
1 ITEM NO : 420-T-01 A/B PROJECT : RDMP RU V LAWE LAWE
2 SERVICE : CRUDE OIL STORAGE TANK CUSTOMER : PERTAMINA
3 GENERAL INFORMATION
4 Tank Type External Double Deck Floating Roof Design Code API 650
5 Product Stored Crude Oil Shell Design Variable Design Point Method
6 No of Required Tank 2 ( two ) Project Specification 26070-203-3PS-MTF5-J0001
7 DESIGN INFORMATION
8 Operating Pressure, kg/cm
3
ATM Maximum Design Level, mm 17982
9 Operating Temperature, C
o
45 Minimum Design Level, mm 1142
10 Maximum Capacity, m3 (Note 12) 170800 Internal Diameter ( ID ), mm 110000
11 Net Working Capacity, m3 160000 Tank Height ( H ), mm 19510
12 Liquid Name Crude Oil Corr.Allowance Shell plate, mm 3
13 Design Specific Gravity 0.86 Bottom plate, mm 3
14 Test Water Specific Gravity (Sea Water) 1.03 Roof plate, mm 3
15 Design Internal Pressure, mmH20 ATM Roof Structural, mm 3
16 Design External Pressure, mmH20 ATM Joint Efficiency 1
17 Temperature ( Max.), C
o
85 Radiography As per spec
18 o
Temperature ( Min.), C 20 Roof Load ( Uniform Live ), kg/m2 122
19 Rain Fall @ 1 hour, mm/hr 100 Bottom Slope / Type 1:120 / Apex Up
20 Wind Velocity, m/sec 35 Flash Point, oC 25
21 Check buckling in corroded condition Yes Boiling Point, oC -
22 Seismic Use Group 1 Initial Filling rate until level 1.9 m, m3/hr 1500
23 Site Class D Pump Rate from level > 1.9m ( Inlet ), m3/hr 8000
24 Mapped Seismic Parameter, S0 / S1 / Ss 0.07/0.111/0.186 Pump Rate ( Outlet ), m3/hr 1431
25 Maintenance Floating Roof Level, mm 1800 (TBD)
26 Operating Floating Roof Level, mm 1500 (TBD)
27
28 OTHER REQUIREMENT
29 Spiral Stairway Yes Stress Relief As per API-650
30 Rolling Ladder Yes External Surface Painting Yes
31 Roof Walkway Yes Interior Surface Painting No (TBD)
32 Draw off Sump Yes Structural Painting Yes
33 Gauge Hatch Yes Bottom Underside Painting Yes (TBD)
34 Mixing Yes Insulation No
35 Heating Coil Yes Lightning Protection Yes (TBD)
36 Shell Earth Lug Yes Immerse Cathodic Protection Yes
37 Retractable Roof Earth Lug Yes Cleanout flush door Yes
38 Name Plate Yes Primary Seal w/Weather Shield Yes
39 Automatic Level Gauge Yes
40 Air Foam System Yes
41 Articulate Roof Drain Yes
42
43 NOTES :
44 1 Crude Processing shall be ESPO 60 % : AZERI 40 % at phase -1 and Arab Light Crude ( ALC ) 100 % at phase -2
45 2 Roof Drain shall be designed and sized in accordance the rainfall intensity of Lawe Lawe, 100 year event
46 3 Contractor/Vendor shall be recalculated all nozzle size/rating and quantity
47 4 Tank dimension and roof level are indicate as design requirement, it shall be reviewed during detail engineering.
48 5 Vendor shall propose mixer sized for approval Pertamina marked with " VTA "
49 6 Tank shall be completed with tank heater to maintain service temperature
50 7 Thickness mentioned above is preliminary for bid only. Recalculation by Vendor shall be confirmed for mechanical strength guarantee
51 8 Nozzle location ( elevation and orientation) will be provide further during detail engineering
52 9 Tank Design, Construction , Inspection and Testing shall comply with Engineering Specification Atmospheric Storage Tank
53 and API-650.
54 10 Plate width & length are for estimation only. Vendor shall finalize actual dimensions.
55 11 TBD = To be decide during detail engineering
56 12 Maximum capacity is measured from bottom plate to maximum design liquid level.
57 13 Instrument nozzle shall be reviewed during detail.
58
59
60

Electronic documents, once printed, are uncontrolled and may became outdated.

Pertamina Confidential © 2018 PT. Pertamina (Persero). All rights reserved


JOB NO. DOCUMENT NO. REV.
ENGINEERING CENTER 26070 - 203 MTD - 420- JT001 1
REFINING DIRECTORATE SHEET 3 OF 3

DATA SHEET CRUDE STORAGE TANK


ITEM NO : 420-T-01 A/B PROJECT : RDMP RU V LAWE LAWE
SERVICE : CRUDE OIL STORAGE TANK CUSTOMER : PERTAMINA

SKETCH
SHELL CONNECTION
Mark Size /Rating Qty Application
N1 40"/150# WNRF 1 LIQUID INLET w/Internal Pipe
N12
N2 30"/150# WNRF 1 LIQUID OUTLET w/internal pipe
N3-5 10"(TBD)/150# SORF 3 (TBD) ROOF DRAIN ( SHELL CONN.)
N6A-D 6"(TBD)/300# WNRF 4 (TBD) STEAM INLET c/w VALVE
CONDENSATE OUTLET c/w reducer 2"
N11 3"(TBD)/300# WNRF
N7A-D 4 (TBD) & valve
N8-10 4"(TBD)/150# SORF 3 (TBD) WATER DRAIN w/internal pipe & Sump
N11A-D 2"(TBD)/150# SORF 4 (TBD) TEMPERATURE INDICATOR
CO 36" X 48" 1 FLUSH CLEANOUT DOOR
M1A-D 24" API-650 4 SHELL MANHOLE
M3A-D 30"(VTA)/150# WNRF 4 (VTA) MIXER CONNECTION

ROOF CONNECTION
N12A-E 12" (VTA) 5 (VTA) AUTO BLEEDER VENT
GH1 12" (VTA) 2 (VTA) GAUGE POLE W/GAUGE HATCH
GH2 12" (VTA) VTA GUIDE POLE
T1 4"/150# SORF 1 TEMPERATURE TRANSMITTER
T2 2"/150# SORF 1 TEMP. INDICATOR
L1 8"/150# SORF 1 LEVEL TRANSMITTER
L2 3"/150# SORF 1 LEVEL SWITCH
M2A-D 24"API650 4 (VTA) ROOF MANHOLE
RV 6"(VTA) VTA RIM VENT
MC 20"(VTA) API 650 VTA COMPARTMENT MANHOLE
SD VTA VTA ROOF DRAIN SUMP

CONSTRUCTION DETAIL (VTA)


Thickness Width Length Joint
Material
( mm ) ( mm ) ( mm )
Bottom Plate A283 Gr.C 10 Lap
Annular Plate A537 Cl.2 23 Butt
Bottom / Top Deck A283 Gr.C 8/5 Lap
Wind Girder A283 Gr.C
Structural A36
Shell Plate : Flush Stacked Inside
Shell Course 1 A537 Cl.2 39 2438 15025 Butt
Shell Course 2 A537 Cl.2 38 2438 15025 Butt
Shell Course 3 A537 Cl.2 28 2438 15025 Butt
Shell Course 4 A537 Cl.2 24 2438 15025 Butt
Shell Course 5 A537 Cl.2 19 2438 15025 Butt
Shell Course 6 A537 Cl.2 14 2438 15025 Butt
Shell Course 7 A537 Cl.2 10 2438 15025 Butt
Shell Course 8 A283 Gr.C 10 2444 15025 Butt
Roof Manhole Neck A283 Gr.C
Shell Manhole Neck A537 Cl.2 Tank Weight Empty Weight 3000 ton
Manhole Flg & Cover A283 Gr.C Operating Weight 150000 ton
Nozzle Neck < 12" A106 Gr.B Hydrostatic Test Weight 180000 ton
Nozzle Neck > 12" A537 Cl.2
Flange for Nozzle A105
Bolt & Nut A193-B7/ A194-2H
Gasket Compressed Fiber
Heating Coil A106 Gr.B
Cleanout Door A537 Cl.2
TBD = To be decide during detail engineering VTA: Vendor To Advice

Electronic documents, once printed, are uncontrolled and may became outdated.

Pertamina Confidential © 2018 PT. Pertamina (Persero). All rights reserved

You might also like