Occupancy Category
The structure is classified as
Standard Occupancy Category V – Miscellaneous structures
Reference: Table 103-1
Reference: Fig.207A.5-1
• Exposure Category
The sign is located at Lomboy Sto. Tomas La Union which is a suburban Area, where the ground surface
roughness, as defined by Surface Roughness B, therefore exposure category shall be taken as, Exposure B
Reference: Table 207.6-1
• Topographic Factor, K zt
1+1.7 I z √ g 2Q Q 2+ g 2R R2
Gf =0.925 ( 1+1.7 g v I z )
Where:
0.577
g R=√ 2 ln (3600 n1 )+
√2 ln (3600 n1 )
For billboard structures, the natural frequency n1, may be estimated by the equation
n1 =( 32.62
h )
M R a ao Pa A a
where
1
M a=
√ 1+ k m mr
In which
1
M a=
√ 1+(2.6)(0)
=1.0
−0.2
h
Rao=1.25 ( )
Bo
−0.2
24.5
Rao=1.25 ( )
1.5
=0.715
Pa=1.0(other conditions)
Aa =1.0(service level)
n1 =( 32.62
24.5 )
(1.0)(0.715)(1.0)(1.0)
0.577
g R=√ 2 ln (3600 n1 )+
√2 ln (3600 n1 )
0.577
g R=√ 2 ln (3600( 0.952))+
√ 2 ln (3600( 0.952))
g R=4.178
The intensity turbulence I z , at height z̅ shall be determined as;
1
10
I z =c ( )
z
6
Where z̅ is the equivalent height of the structure defined as 0.6h, but not less than z min for all building heights
c=0.30
Substituting to the equation
1
10
I z =0.3 ( )
14.7
6
I z =0.281
1
Q=
√
Where,
1+0.63
B+ h
Lz ( )
0.63
Where:
B=¿ 9.15 m
h=¿ 24.5 m
L z=¿The internal length scale of turbulence at the equivalent height m, determined by the equation
ε
ź
L z=l ( )
10
Where
l=97.54
1
ε=
3
1
14.7
L z=97.54 ( ) 10
3
L z=110.91 m
Solve for Q
1
Q=
√ 1+0.63
9.15+24.5
(
110.91
0.63
)
Q=0.878
The response resonant, R, factor shall be determined as,
1
R=
√ R R R (0.53+ 0.47 R L )
β n h B
Where
7.47 N i
Rn = 5
( 1+10.3 N i ) 3
In which
n1 Lz
N i=
V ź
ź á
V̅ z =b́ ( )
10
V
Where b́ and a̅ are constants, and V is the basic wind speed in m/s
b́=0.45
1
a̅ =
4
Solving for V̅ z ,
1
14.7
V̅ z =0.45 ( ) (72.22)
10
4
V̅ z =35.785 m/ s
Solving for N i,
0.952(110.91)
N i=
35.785
N i=2.951
7.47( 2.951)
Rn = 5
3
( 1+10.3(2.951) )
Rn =0.071
For Rh,
1 1
Rh = − 2 ( 1−e−2 n ) for n> 0
n 2n
Rh =1 for n=0
h
n=4.6 n 1 , equationof n for Rh
V́ z
h=24.5 m
solving for n ,
n=3.0>0
Therefore use the equation
1 1
Rh = − 2 ( 1−e−2 n )
n 2n
Solving for Rh
1 1
Rh = −
3 2¿¿
Rh =0.278
For R B
1 1
R B= − 2 ( 1−e−2 n ) for n>0
n 2n
B
n=4.6 n 1 , equationof n for RB
V́ z
Solving for n,
9.15
n=4.6 (0.952)
35.785
n=1.12>0
Therefore use the equation
1 1
R B= − 2 ( 1−e−2 n )
n 2n
Solving R B,
1 1
R B= − ( 1−e−2 (1.12 ) )
1.12 2(1.12)2
R B=0.537
For R L ,
1 1
R L= − 2 ( 1−e−2 n ) for n>0
n 2n
L
n=15.4 n1 , equation of n for R L
V́ z
Solving for n,
L = horizontal dimension of the building/structure parallel to the wind direction, m
L=2m
2
n=15.4(0.952)
35.785
n=0.819>0
Therefore use the equation
1 1
R L= − 2 ( 1−e−2 n )
n 2n
Solving for R L,
1 1
R L= −
0.819 2 ¿ ¿
R L=0.621
Solving for R,
1
R=
√ R R R (0.53+ 0.47 R L )
β n h B
1
R=
√ 0.01
(0.071)(0.278)( 0.537)(0.53+0.47( 0.621))
R=0.933
Solving for G f
1+1.7 I z √ g 2Q Q 2+ g 2R R2
Gf =0.925 (1+1.7 g v I z )
1+1.7(0.281) √ (3.4 )2 ( 0.878 )2+ ( 4.178 )2 ( 0.933 )2
Gf =0.925 ( 1+ 1.7(3.4)(0.281) )
G f =1.179
Velocity Pressure
based on the exposure category B of the billboard structure, the velocity pressure coefficient K h or K z which can
be determined from the table 207D.3-1 by interpolation of the following:
Velocity pressure exposure coefficients
Structure Z(m) Kz
Components
Panel 1 3.00 0.510
Panel 2 6.00 0.621
Panel 3 9.00 0.697
Panel 4 12.00 0.757
Panel 5 15.00 0.807
Panel 6 18.00 0.850
Panel 7 21.00 0.888
Panel 8 24.00 0.923
q z =1386.004 N /m 2
At panel 2:
q z =1687.66 N /m2
At panel 3:
q z =1894.21 N /m 2
At panel 4:
q z =2057.27 N /m 2
At panel 5:
q z =2193.15 N /m2
At panel 6:
q z =2310.01 N /m2
At panel 7:
q z =2413.28 N /m2
At panel 8:
q z =2508.40 N /m2
Velocity pressure for panels
Structure Z(m) Kz
Components qz
( mN )
2
Determine the force coefficient, C f , for solid sign as follows, for the values of
s = 15 m
h = 24.5 m
B = 9.15 m
Evaluate:
s 15
= =0.612
h 24.5
B 9.15
= =0.61
s 15
Interpolation ,
0.5
0.5 1.75
0.612 X
0.7 1.70
0.5−0.612 0.5−0.7
=
1.75−x 1.75−1.70
x=C f 1=1.722
1
0.5 1.75
0.612 X
0.7 1.65
0.5−0.612 0.5−0.7
=
1.75−x 1.75−1.65
x=C f 2=1.694
0.5 1.722
0.61 X
1 1.694
0.5−0.61 0.5−1
=
1.722−x 1.722−1.694
x=C f =1.716
Two load cases shall be considered for determination of wind forces of billboard components as:
Case A: Tarp is not considered. (Tarp is assumed folded)
Case B: Tarp is partially not considered. (Exposed area of tarp is taken as 35% to 50% of the billboard surface)
Case C: Tarp is considered.
F=q h G f C f A f
At panel 4
F z 4 =47453.18 N
At panel 5
F z 5=50587.40 N
At panel 6
F z 6 =53282.90 N
At panel 7
F z 7=55664.94 N
At panel 8
F z 8=57858.99 N
F=q h G f C f A f
At panel 4
F z 4 =114252.24 N
At panel 5
F z 5=121798.45 N
At panel 6
F z 6 =128288.37 N
At panel 7
F z 7=134023.56 N
At panel 8