REMOTE CONTROL CIRCUITS (SEE NOTE 1)

TWO-WIRE CONTROL TWO-WIRE CONTROL


OPEN / CLOSE
ENERGISE TO OPEN ENERGISE TO CLOSE
OPEN / CLOSE MAINTAINED CONTROL OPEN / STOP / CLOSE
PUSH-TO-RUN CONTROL WITH MID-TRAVEL MAINTAINED CONTROL
DE-ENERGISE TO DE-ENERGISE TO OPEN
CLOSE (CONFIGURE (CONFIGURE FOR
ANALOGUE CONTROL CIRCUITS ESD CONTROL CIRCUITS
REVERSE
FOR OPEN PRIORITY) CLOSE PRIORITY) (SEE NOTE 2) (SEE NOTE 3 )
INTERNAL SUPPLY 0Vdc (-ve) 4 4 4 4 4 DEMAND SIGNAL (V) 26 INTERNAL SUPPLY 0Vdc (-ve) 4

CUSTOMER
INTERNALLY FED CIRCUITS

INTERNALLY FED CIRCUITS


SIGNAL
COMMON 20-60Vac/dc (-ve) 36 36 36 36 36 COMMON (DEMAND SIGNAL) 27 COMMON 20-60Vac/dc (-ve) 31
CLOSE CLOSE CLOSE OPEN ESD
(STAY-PUT)
CLOSE 33 33 33 33 33 DEMAND SIGNAL (I) 28 ESD 25
CLOSE

STOP / MAINTAIN 34 34 34 34 34 PARTIAL STROKE 37


OPEN OPEN OPEN CLOSE PARTIAL
DEMAND SIGNAL (V) 26 STROKE

CUSTOMER
OPEN 35 35 35 35 35

SIGNAL

INTERNALLY FED REMOTE MANUAL OVERRIDE OPTION


OPEN
STOP
COMMON (DEMAND SIGNAL) 27
INTERNAL SUPPLY 24Vdc (+ve) 5 5 5 5 5 INTERNAL SUPPLY 24Vdc (+ve) 5
DEMAND SIGNAL (I) 28

INTERNAL SUPPLY 0Vdc (-ve) 4 4 4 INTERNAL SUPPLY 0Vdc (-ve) 4 INTERNAL SUPPLY 0Vdc (-ve) 4

COMMON 20-60Vac/dc (-ve) 36 36 36 COMMON 20-60Vac/dc (-ve) 31 COMMON 20-60Vac/dc (-ve) 31

EXTERNALLY FED CIRCUITS

EXTERNALLY FED CIRCUITS


COMMON 60-120Vac (-ve) 40 40 40 COMMON 20-60Vac/dc (-ve) 36 COMMON 60-120Vac (-ve) 32
CLOSE CLOSE CLOSE CLOSE ESD
(STAY-PUT)
CLOSE 33 33 33 CLOSE 33 ESD 25
OPEN

STOP / MAINTAIN 34 34 34 OPEN 35 PARTIAL STROKE 37


OPEN OPEN OPEN PARTIAL
OPTIONAL STROKE
OPEN 35 35 35 STOP / MAINTAIN 34
STOP LOCAL REMOTE AUTO /
INTERNAL SUPPLY 24Vdc (+ve) 5 5 5 37 INTERNAL SUPPLY 24Vdc (+ve) 5
MANUAL AUTO
LINE (+ve) LINE (+ve) LINE (+ve) LINE (-ve)
INTERNAL SUPPLY 24Vdc (+ve) 5
MANUAL
ZERO (-ve) ZERO (-ve) ZERO (-ve) ZERO (-ve)

NOTE - 1 DEMAND SIGNAL (V) 26

CUSTOMER
REMOTE CONTROL INPUTS ARE OPTO-ISOLATED INTERFACES WITH A SURGE IMMUNITY OF 2kV. STANDARD CONTROL IS POSITIVE

SIGNAL

EXTERNALLY FED REMOTE MANUAL OVERRIDE OPTION


SWITCHING. COMMON (DEMAND SIGNAL) 27
THE STANDARD ACTUATOR CAN BE CONTROLLED USING REMOTE CONTROL SIGNALS DEFINED AS FOLLOWS:
DEMAND SIGNAL (I) 28
THE CURRENT DRAWN FROM EACH CONTROL INPUT: 5mA AT 24Vdc - 12mA AT 120Vac.
GUARANTEED MINIMUM 'ON' VOLTAGE: 20V. COMMON 20-60Vac/dc (-ve) 31
GUARANTEED MAXIMUM 'OFF' VOLTAGE: 3V.
SIGNAL DURATION: MINIMUM 300ms. COMMON 20-60Vac/dc (-ve) 36
CLOSE

CLOSE 33
NOTE - 2 OPEN
AS STANDARD, AN ANALOGUE CONTROLLED ACTUATOR WILL BE CALIBRATED TO 4-20mA. OPEN 35
THE ACTUATOR CAN BE CALIBRATED, ANYWHERE BETWEEN 0-20mA OR 0-10V IF REQUESTED. OPTIONAL
THE ANALOGUE OUTPUT IS 4-20mA. STOP / MAINTAIN 34
LOCAL REMOTE AUTO /
37
NOTE - 3 MANUAL
THE EMERGENCY SHUT-DOWN (ESD), SIGNAL WILL OVERRIDE ANY EXISTING LOCAL OR REMOTE SIGNAL, THE ACTUATOR CAN BE AUTO MANUAL
CONFIGURED TO OPEN, CLOSE OR STAY-PUT AS A RESPONSE TO A ESD SGNAL. THE ACTUATOR CAN BE CONFIGURED TO
LINE (+ve)
RESPOND TO AN ESD SIGNAL FROM A 'MAKING' OR 'BREAKING' CONTACT.
LINE (-ve)
SIGNAL DURATION: STAYPUT CONTACT.
PARTIAL STROKING WILL ONLY FUNCTION WHEN CONFIGURED FOR OPERATION FROM A REMOTE CONTROL CIRCUIT.
SIGNAL DURATION: MINIMUM 300ms.
THIS DRAWING IS CONFIDENTIAL REV. DATE CHG. No. BY ALL DIMENSIONS IN mm UNLESS OTHERWISE STATED DRAWN SNR DRAWING TITLE REGINA HOUSE
RING ROAD
AND IS THE PROPERTY OF
A 28/06/07 1500 SNR GENERAL TOLERANCE ±0.3mm. DATE 30/03/06 CONTROL CIRCUITS LEEDS, LS13 4ET
ROTORK SKILMATIC AND MUST ENGLAND
NOT BE REPRODUCED EITHER B 02/04/08 1550 SNR M/C SURFACES TO BS.1134 uM Ra. CHECKED - GENERAL 'SI' ACTUATOR RANGE TEL. 0113 205 7278
WHOLLY OR PARTLY. ALL RIGHTS - - - - CASTING TOLERANCE TO ISO8062 GRADE CT6. DATE - FAX. 0113 236 3310
IN RESPECT OF PATENTS, - - - - CASTING DRAW TAPER 2° MAX. APPROVED - MATERIAL - REV.
- - - - UNSPECIFIED CAST RADII TO BE 3mm MAX. DATE - SPEC - No. SMW-SI-002
DESIGNS AND COPYRIGHTS ARE
RESERVED. © 2007 - - - - CAST EXTERNAL SURFACES TO BE SHOTBLAST. SCALE - FINISH - SHEET 1 OF 1