INTERNALLY FED CIRCUITS
CUSTOMER
OPEN 35 35 35 35 35
SIGNAL
INTERNAL SUPPLY 0Vdc (-ve) 4 4 4 INTERNAL SUPPLY 0Vdc (-ve) 4 INTERNAL SUPPLY 0Vdc (-ve) 4
CUSTOMER
REMOTE CONTROL INPUTS ARE OPTO-ISOLATED INTERFACES WITH A SURGE IMMUNITY OF 2kV. STANDARD CONTROL IS POSITIVE
SIGNAL
CLOSE 33
NOTE - 2 OPEN
AS STANDARD, AN ANALOGUE CONTROLLED ACTUATOR WILL BE CALIBRATED TO 4-20mA. OPEN 35
THE ACTUATOR CAN BE CALIBRATED, ANYWHERE BETWEEN 0-20mA OR 0-10V IF REQUESTED. OPTIONAL
THE ANALOGUE OUTPUT IS 4-20mA. STOP / MAINTAIN 34
LOCAL REMOTE AUTO /
37
NOTE - 3 MANUAL
THE EMERGENCY SHUT-DOWN (ESD), SIGNAL WILL OVERRIDE ANY EXISTING LOCAL OR REMOTE SIGNAL, THE ACTUATOR CAN BE AUTO MANUAL
CONFIGURED TO OPEN, CLOSE OR STAY-PUT AS A RESPONSE TO A ESD SGNAL. THE ACTUATOR CAN BE CONFIGURED TO
LINE (+ve)
RESPOND TO AN ESD SIGNAL FROM A 'MAKING' OR 'BREAKING' CONTACT.
LINE (-ve)
SIGNAL DURATION: STAYPUT CONTACT.
PARTIAL STROKING WILL ONLY FUNCTION WHEN CONFIGURED FOR OPERATION FROM A REMOTE CONTROL CIRCUIT.
SIGNAL DURATION: MINIMUM 300ms.
THIS DRAWING IS CONFIDENTIAL REV. DATE CHG. No. BY ALL DIMENSIONS IN mm UNLESS OTHERWISE STATED DRAWN SNR DRAWING TITLE REGINA HOUSE
RING ROAD
AND IS THE PROPERTY OF
A 28/06/07 1500 SNR GENERAL TOLERANCE ±0.3mm. DATE 30/03/06 CONTROL CIRCUITS LEEDS, LS13 4ET
ROTORK SKILMATIC AND MUST ENGLAND
NOT BE REPRODUCED EITHER B 02/04/08 1550 SNR M/C SURFACES TO BS.1134 uM Ra. CHECKED - GENERAL 'SI' ACTUATOR RANGE TEL. 0113 205 7278
WHOLLY OR PARTLY. ALL RIGHTS - - - - CASTING TOLERANCE TO ISO8062 GRADE CT6. DATE - FAX. 0113 236 3310
IN RESPECT OF PATENTS, - - - - CASTING DRAW TAPER 2° MAX. APPROVED - MATERIAL - REV.
- - - - UNSPECIFIED CAST RADII TO BE 3mm MAX. DATE - SPEC - No. SMW-SI-002
DESIGNS AND COPYRIGHTS ARE
RESERVED. © 2007 - - - - CAST EXTERNAL SURFACES TO BE SHOTBLAST. SCALE - FINISH - SHEET 1 OF 1
B