You are on page 1of 6

Evaluation of Recycled Concrete as

Aggregates in New Concrete Pavements


Haifang Wen, David I. McLean, and Kim Willoughby

This study evaluated the use of recycled concrete as coarse aggregate in found to be similar to the quality and properties of the original aggre-
new concrete pavements. Recycled concrete aggregate (RCA) produced gate (4), and RCA quality affects the quality of the concrete in which it
from demolished pavements in three geographically dispersed locations is incorporated (6). Thus, recycling concrete where the original aggre-
in Washington State was used to perform tests on aggregate charac- gates were of low quality would likely yield RCA that is inadequate for
teristics, fresh concrete properties, and hardened concrete properties. use in new PCCPs. However, studies have shown that lower-quality
Variables included the source of the RCA, percentage of replacement RCA can be effectively used for base course applications (7).
of coarse natural aggregate with RCA (0% to 45%), and percentage of A 2004 FHWA report on the state of the practice (8) found that
replacement of portland cement with Class F fly ash (0% or 20%). RCA only 11 states actively use RCA in new portland cement concrete,
from all three sources met the Washington State Department of Trans- though 41 were reported to recycle concrete in roadway base con-
portation (DOT) requirements for aggregates, and all fresh and hardened struction. Washington State DOT’s current use of RCA is limited
concrete properties met Washington State DOT requirements. Replace- to ballast, gravel base, crushed surfacing, backfill for foundations,
ment of RCA for natural coarse aggregate by up to 45% by volume had walls and drains, select and common borrow foundations, and bank
no significant effects on any of the concrete properties. These results run gravel (Standard Specifications for Road, Bridge, and Municipal
indicate that high-quality RCA can be used as a replacement for a por- Construction, Washington State DOT, 2014).
tion of the coarse natural aggregates in new portland cement concrete The research reported in this paper evaluated the effectiveness
pavements. of RCA created from demolished concrete pavements as aggregates
in new PCCPs. Variables evaluated included the replacement of
coarse natural aggregate with coarse RCA at replacement levels of
The Washington State Department of Transportation (DOT) manages 0%, 15%, 30% or 45%; three sources of RCA; and a 0% or 20%
about 2,400 lane mile of concrete roadway, the majority of which were replacement of portland cement with fly ash. Tests were performed
constructed in the 1950s and 1960s. Many of these concrete pave- to characterize properties of the RCA, including absorption capacity,
ments have greatly surpassed their original design life and expected specific gravity, Los Angeles abrasion loss, degradation factor, and
traffic loading, and they are in need of replacement (1). Because of alkali-silica reactivity. The effects of RCA on fresh concrete prop-
significant costs associated with replacement coupled with funding erties were evaluated by measuring slump, air content, and density.
limitations, much of this needed replacement has been backlogged. The effects of RCA on hardened concrete properties were evaluated
In response to this situation, both FHWA (2, 3) and Washing- by measuring compressive strength, modulus of rupture, coefficient
ton State DOT are interested in alternatives that promote cheaper of thermal expansion, drying shrinkage, and freeze–thaw durability.
and more sustainable pavement construction practices. One such This paper provides a brief description of the test procedures and
alternative is to incorporate recycled concrete as aggregate in new a summary of the main results from this research study. Detailed
portland cement concrete pavements (PCCPs). Recycled concrete discussion is given in Wen et al. (9).
aggregates (RCA) can reduce costs, environmental impacts, and
project delivery time when used in concrete pavements (4). Addi-
tionally, dwindling supplies of high-quality natural aggregates, Experimental Program
increasingly limited landfill space, swelling disposal costs, empha-
sis on conservation of natural resources, and reduced construction A reference PCCP mix design was provided by Washington State
costs arise as convincing reasons to consider the use of RCA (5). DOT. Twenty concrete batches based on this reference mix were pre-
Previous studies of the effects of using RCA in new portland pared using three sources of RCA, and with varying levels of RCA
cement concrete have reached different conclusions, largely because replacement of natural coarse aggregate and fly ash replacement of
aggregate quality varied widely in the original concrete from which portland cement.
the RCA was produced. The quality and properties of RCA have been Natural aggregates were obtained from Washington State DOT–
approved aggregate pits. The natural coarse and fine aggregates
conformed to AASHTO grading No. 467 and Type 1, respec-
H. Wen, Department of Civil and Environmental Engineering, Washington State
University, 405 Spokane Street, Pullman, WA 99164-2910. D. I. McLean, College tively. RCA aggregates used in this study were produced from
of Engineering, Campus Delivery 1301, Colorado State University, Fort Collins, demolished roadway panels of Interstate 90 in central Wash-
CO 80523-1301. K. Willoughby, Office of Research and Library Services, Washington ington (Source A); runway panels at Fairchild Air Force Base
State Department of Transportation, P.O. Box 47372, Olympia, WA 98504-7372. in eastern Washington (Source B); and roadway panels of Inter-
Corresponding author: D. I. McLean, david.mclean@colostate.edu. state 5 in western Washington (Source C). The concrete panels
Transportation Research Record: Journal of the Transportation Research Board,
were crushed to 1.25 in. minus and delivered to Washington State
No. 2508, Transportation Research Board, Washington, D.C., 2015, pp. 73–78. University. The as-delivered RCA was washed to remove the fines
DOI: 10.3141/2508-09 and sieved to obtain a size distribution conforming to AASHTO

73
74 Transportation Research Record 2508

TABLE 1   Mix Testing Program 90 days. Five MOR beams were tested at 14 days. Thermal expan-
sion tests were performed after specimens had cured for 28 days.
Percentage of Percentage of Fly After 28 days of curing in a lime-saturated bath, drying shrinkage
RCA Substitution Ash Substitution
Mix ID (by volume) (by weight)
specimens were placed in an environmentally controlled cham-
ber that maintained a relative humidity of 50% and a temperature
X-0-0  0  0 of 23°C. Drying shrinkage measurements were taken, with day 0
(A, B, or C)-15-0 15  0 beginning on their removal from lime-saturated water baths after
(A, B, or C)-30-0 30  0 28 days of curing, at ages of 0 days, 4 days, 7 days, 14 days, 28
(A, B, or C)-45-0 45  0
days, 8 weeks, and 16 weeks. For the freeze–thaw durability tests,
beam specimens from the X-0-0 and C-45-0 batches were sub-
X-0-20  0 20
jected to freezing and thawing cycles after 14 days of curing in a
(A, B, or C)-15-20 15 20
lime-saturated bath. Flexural modal frequencies were determined
(A, B, or C)-30-20 30 20 for each specimen after 0, 50, and 100 freeze–thaw cycles and used
(A, B, or C)-45-20 45 20 to characterize damage.
For all results, an analysis of variation (ANOVA) was used to
determine if results grouped by variables of interest were statistically
different.
grading No. 467. Cement and fly ash used in this study were Type I-II
and Class F, respectively.
The testing program evaluated the effects of substituting RCA Test Results and Discussion
for natural coarse aggregate at 0, 15, 30, or 45% by volume of
replaced coarse aggregates, along with substituting fly ash for RCA Properties
portland cement at rates of 0 or 20% by weight. Table 1 shows
the mix testing program consisting of two baseline batches and The saturated surface dry (SSD) bulk specific gravities of the RCA
six RCA batches for each of the three RCA sources. Reference from Sources A, B, and C were 2.52, 2.53, and 2.57, respectively,
nomenclature in the table indicates the source, amount of RCA and the absorption capacities were 3.30%, 3.87%, and 3.05%,
replacement, and fly ash replacement. For example, A-15-20 respectively. The coarse natural aggregate had an SSD bulk specific
refers to a mix incorporating a 15% replacement of natural course gravity of 2.63 and absorption capacity of 1.2%. The slightly lower
aggregate with RCA from Source A, and a 20% replacement of densities and higher absorption capacities of the RCA are caused by
cement with fly ash. the presence of mortar on the RCA.
Four tests were performed to determine five characteristics of the The Los Angeles abrasion losses for the RCA from Sources A, B,
RCA from each of the three sources, including specific gravity and and C were 29%, 20%, and 21%, respectively. Washington State DOT
absorption (AASHTO T 85); Los Angeles abrasion loss (AASHTO specifications require that aggregates have an abrasion loss below 35%
T 96); degradation value (WSDOT T 113); and alkali-silica reactivity (8). Each of the three RCAs met this requirement. Based on visual
(ASR) (AASHTO T 303). inspection, the RCA from Source A had a greater portion of adhered
Three tests were performed to evaluate the effects of RCA on fresh mortar compared with that for Sources B and C, and this is likely the
concrete properties, including air content (AASHTO T 152); slump reason that the abrasion loss for the Source A RCA was higher.
(AASHTO T 119); and density (AASHTO T 121). For concrete Degradation values were determined by using WSDOT T 113 as
used in pavements, the Washington State DOT requires air contents a measure of how much an aggregate will degrade when abraded in
between 3% and 7% and slumps between 1 and 3 in. These ranges the presence of water. Degradation values for the as-delivered RCA,
were achieved in each batch by withholding some of the mix water, for processed RCA after washing and sieving, and for blended coarse
or by adding air entraining admixture and water reducing admixture aggregates with 15%, 30%, and 45% replacement of coarse natu-
during batching, or both. ral aggregate with processed RCA are summarized in Table 2. The
Concrete samples were prepared for hardened concrete testing Washington State DOT requires a minimum degradation value for
according to AASHTO R-39. After 24 h, samples were demolded aggregates in new PCCP of 30 (10). All the RCA samples had deg-
and placed in lime-saturated water to cure until their test date. Five radation values that exceeded this limit, except for the as-delivered
tests were used to determine the effects of RCA on hardened con- RCA Source A. On the basis of the much lower values for the
crete properties, including compressive strength (AASHTO T 22); un­processed samples, likely a result of loosely bound fines adhering
modulus of rupture (MOR) (AASHTO T 177); coefficient of thermal to the as-delivered RCA being abraded during the test, RCA should
expansion (AASHTO T 336); drying shrinkage (AASHTO T 160); be washed and sieved to obtain adequate degradation performance
and freeze–thaw durability (AASHTO T 161). before use in new concrete pavements.
Compression cylinders were tested as follows: three cylinders The average 14-day ASR expansion values for the RCA from
at 7 days of age, three at 14 days, five at 28 days, and three at Sources A, B, and C were 0.07%, 0.17% and 0.09%, respectively.

TABLE 2   Degradation Test Results

Degradation Value, by Type of RCA

RCA Source As Delivered Processed 15% Substitution 30% Substitution 45% Substitution

A 15 55 77 75 70
B 37 49 77 75 73
C 40 69 76 76 78
Wen, McLean, and Willoughby 75

With the AASHTO T 303 test, if the mortar bar expands by more than TABLE 3   Fresh Concrete Test Results
0.1%, then the aggregate may be susceptible to deleterious expansion.
Additional testing is required to determine if the expansion is actually w/cm Slump Air Content
Mix Ratio (in.) (%) Density (lb/ft3)
caused by ASR reactivity. PCCP incorporating Source B RCA could
require ASR mitigation techniques, such as using low-alkali cement X-0-0 0.43 1.75 4.3 145.8
or fly ash. The original Source B concrete was not reported to exhibit
A-15-0 0.44 1.50 4.9 144.2
ASR in the field. This may indicate that the crushing process exposed
A-30-0 0.43 1.50 4.5 145.2
more internal surface area of the aggregates, causing the RCA to be
ASR susceptible. A-45-0 0.44 2.25 4.9 142.8
B-15-0 0.44 1.25 4.1 146.2
B-30-0 0.43 1.50 5.0 143.4
Effect of RCA on Fresh Concrete Properties B-45-0 0.43 1.25 4.3 145.8
C-15-0 0.44 2.50 5.6 144.2
Results for the slump, air content, water–cementitious materials ratio
C-30-0 0.44 2.00 5.1 144.4
(w/cm), and density of the concrete mixes tested in this study are
C-45-0 0.44 1.50 4.3 146.2
summarized in Table 3 and discussed as follows. As intended with
the batching process, all slumps and air contents were in the target X-0-20 0.40 1.75 4.1 146.8
ranges of 1 to 3 in. and 3% to 7%, respectively. A-15-20 0.40 1.25 4.2 145.4
The addition of RCA was found to decrease workability in batches A-30-20 0.42 2.00 4.5 144.8
where the w/cm was approximately constant. For example, despite A-45-20 0.40 1.50 4.5 144.6
having the same w/cm of 0.44, each of the 0% fly ash batches for B-15-20 0.41 1.75 4.7 145.8
Source C had a trend of decreasing slump with greater levels of RCA B-30-20 0.42 1.75 4.2 145.4
replacement. Slumps were 2.5, 2, and 1.5 in. for 15%, 30%, and B-45-20 0.41 2.00 4.7 143.4
45% RCA, respectively. The results also show that fly ash improved
C-15-20 0.39 1.75 4.1 146.8
the workability, allowing for lower w/cm while still producing
acceptable slumps. C-30-20 0.40 1.75 4.0 145.8
C-45-20 0.41 1.50 4.0 145.2

Effect of RCA on Hardened Concrete Properties


compressive strength value of 4,000 pounds per square inch (psi)
The average compressive strengths for 7 days, 28 days, and 90 days required by the Washington State DOT for use in PCCPs. For the
are listed in Table 4. The average 28-day compressive strengths are results of this study, RCA replacement did not have a statistically sig-
shown graphically in Figure 1. The data range bars shown in the figure nificant effect on compressive strength, based on ANOVA analysis.
represent the maximum and minimum test values for each data The slight variations present in the compressive strengths are likely
set. The 28-day strengths for all samples exceeded the minimum a result of different air contents and w/cm in the various batches.

TABLE 4   Average Compression Strength Results

Mix 7-Day (psi) CV (%) 14-Day (psi) CV (%) 28-Day (psi) CV (%) 90-Day (psi) CV (%)

X-0-0 3,750 1.8 4,350 2.3 4,830 1.6 5,520 0.7


A-15-0 3,750 4.2 4,180 10.5 4,920 3.3 5,420 1.5
A-30-0 4,330 0.1 4,870 1.4 5,470 4.0 5,900 1.1
A-45-0 3,840 3.4 4,620 0.8 5,130 1.8 5,570 2.6
B-15-0 3,980 4.1 4,880 1.1 5,400 1.0 6,100 2.3
B-30-0 3,870 2.5 4,820 1.2 5,310 2.2 5,790 3.2
B-45-0 4,090 8.0 5,160 2.4 5,520 2.9 6,120 4.8
C-15-0 3,360 1.4 3,810 1.3 4,340 2.9 4,920 5.5
C-30-0 3,520 0.6 4,260 2.0 4,740 2.4 5,320 1.6
C-45-0 3,790 2.3 4,450 3.7 4,940 2.1 5,750 1.4
X-0-20 3,710 4.4 4,570 6.0 5,340 1.6 6,280 1.7
A-15-20 3,900 4.4 4,660 3.4 5,590 2.8 6,560 2.5
A-30-20 3,740 1.7 4,500 2.1 5,290 5.4 6,270 2.5
A-45-20 3,760 4.0 4,500 3.8 5,500 4.0 6,400 1.5
B-15-20 3,620 1.0 4,380 1.1 5,180 0.9 6,210 1.7
B-30-20 3,630 2.2 4,380 3.0 5,220 2.0 6,190 2.9
B-45-20 3,300 1.3 4,090 1.0 4,760 1.7 5,800 0.4
C-15-20 3,440 2.4 4,110 2.2 4,680 3.8 5,520 2.1
C-30-20 3,610 1.1 4,350 1.4 4,810 1.2 5,750 1.1
C-45-20 3,890 1.6 4,390 1.1 5,150 2.1 6,400 3.0

Note: CV = coefficient of variation.


76 Transportation Research Record 2508

6,500 RCA source


A B C

Compressive Strength (psi)


6,000

5,500

5,000

4,500

4,000
0% 15% 30% 45%
RCA Replacement
(a)

6,500 RCA source


A B C
Compressive Strength (psi)

6,000

5,500

5,000

4,500

4,000
0% 15% 30% 45%
RCA Replacement
(b)

FIGURE 1   Average 28-day concrete compressive strength versus


RCA replacement: (a) 0% fly ash and (b) 20% fly ash.

TABLE 5   Average 14-Day Modulus of


RCA appeared to cause a small decrease in late age strength gain, Rupture Results
but it was determined to not be statistically significant. Fly ash
decreased early-age compressive strengths while increasing later-age Mix Average MOR (psi) CV (%)
compressive strength.
The average 14-day MOR results are listed in Table 5 and shown X-0-0 800 2.9
graphically in Figure 2. The MOR strengths for all samples exceed A-15-0 765 2.7
the minimum MOR of 650 psi required by Washington State DOT A-30-0 775 5.0
for use in PCCP. For the results of this study, RCA replacement did A-45-0 725 3.5
not have a statistically significant effect on MOR strength, based on B-15-0 845 3.5
ANOVA analysis. B-30-0 790 5.2
Coefficient of thermal expansion (CTE) results are shown in Table 6. B-45-0 770 8.5
RCA replacement did not have a statistically significant effect on C-15-0 730 4.2
CTE values. The results did not show any trend with using RCA. C-30-0 800 4.6
CTE values for normal concrete typically range from 3.2 to 7.0 mil- C-45-0 790 7.7
lionths per °F (10). All of the concrete mixes had CTE values within X-0-20 775 6.3
this range, except for the C-45-20 mix, which had a slightly lower A-15-20 780 2.8
CTE value. Therefore, based on the results obtained in this study, A-30-20 720 6.3
PCCPs made with RCA would be expected to have thermal expansion A-45-20 750 4.9
behavior similar to that of normal concrete. B-15-20 775 6.9
Average drying shrinkage results beginning after 28 days of B-30-20 775 4.3
age are shown in Table 7. This test was performed only for RCA B-45-20 725 2.2
from Sources B and C. A negative value indicates shrinkage of the
C-15-20 780 7.3
specimen. The results did not show any trend associated with using
C-30-20 760 3.3
RCA. Drying shrinkage strains for normal concrete are typically
C-45-20 810 2.6
between 4E-4 and 8E-4 (10). All specimens had drying shrinkage
Wen, McLean, and Willoughby 77

950 RCA source


A B C
900

850

MOR (psi)
800

750

700

650
0% RCA 15% RCA 30% RCA 45% RCA
RCA Replacement
(a)

900 RCA source


A B C

850
MOR (psi)

800

750

700

650
0% RCA 15% RCA 30% RCA 45% RCA
RCA Replacement
(b)

FIGURE 2   Average 14-day MOR versus RCA replacement: (a) 0% fly ash
and (b) 20% fly ash.

strains that are within the range of ordinary concrete at the 140-day Summary, Conclusions,
shrinkage measurement. and Recommendations
Results from the durability tests did not show any difference in
performance for the concrete mix incorporating RCA. Freeze–thaw RCA properties were determined for specific gravity, absorption
durability tests in this study were limited to test samples prepared from capacity, Los Angeles abrasion loss, degradation value, and ASR.
two mixes and subjected to a maximum of 100 freezing and thawing Test results showed that RCA from all three sources has a lower spe-
cycles. The results reported here should therefore be considered as a cific gravity and greater absorption capacity than do natural aggre-
preliminary investigation of the durability of concrete mixes with RCA. gates. The RCA from all three sources met Washington State DOT
requirements on Los Angeles abrasion loss and degradation value
for processed RCA. Additional tests may need to be performed to
TABLE 6   Average CTE Results evaluate whether the RCA from Source B is vulnerable to potential
deleterious expansion owing to ASR
Average 28-Day CTE Results The effects of RCA on fresh concrete properties were evaluated
Fly Ash RCA (in./in. per °F), by RCA Source by measuring slump, air content, and density. Slump and air con-
Replacement Replacement tent were controlled parameters in the batching process, with targets
(%) (%) A B C
specified by Washington State DOT of 1 to 3 in. for slump and 3%
0  0 5.2 E−06 5.2 E−06 5.2 E−06 to 7% for air content. Slump was controlled by withholding mix
15 4.6 E−06 5.3 E−06 5.0 E−06 water or by adding water-reducing admixture, and air content was
30 4.8 E−06 5.3 E−06 4.2 E−06 controlled by the amount of air entraining admixture used in the
45 5.0 E−06 5.0 E−06 4.7 E−06 batch. Slump and air content for all batches were within these target
20  0 5.2 E−06 5.2 E−06 5.2 E−06 ranges. RCA was found to decrease the slump and density of fresh
15 5.0 E−06 5.1 E−06 5.6 E−06 concrete. RCA did not have a significant effect on air content.
30 4.8 E−06 5.1 E−06 4.8 E−06
45 5.0 E−06 5.6 E−06 2.9 E−06
The effects of RCA on hardened concrete properties were evaluated
by measuring compressive strength, MOR, CTE, drying shrinkage, and
78 Transportation Research Record 2508

TABLE 7   Average Drying Shrinkage Results

Average Shrinkage Strain [in./in. (CV%)], by Day

Mix 28 32 35 42 56 84 140

X-0-0 0.0 E+00 (0) −8.7 E−05 (18) −1.8 E−04 (13) −3.4 E−04 (9) −4.4 E−04 (8) −5.3 E−04 (19) −6.5 E−04 (5)
C-15-0 0.0 E+00 (0) −7.7 E−05 (20) −1.2 E−04 (26) −2.5 E−04 (15) −3.6 E−04 (12) −4.7 E−04 (10) −5.9 E−04 (7)
C-30-0 0.0 E+00 (0) −6.7 E−05 (9) −1.5 E−04 (28) −2.4 E−04 (13) −4.0 E−04 (14) −5.5 E−04 (12) −6.7 E−04 (5)
C-45-0 0.0 E+00 (0) −1.3 E−04 (15) −2.1 E−04 (25) −3.3 E−04 (15) −5.0 E−04 (13) −6.8 E−04 (13) −7.0 E−04 (11)
B-15-0 0.0 E+00 (0) −1.5 E−04 (14) −1.7 E−04 (3) −1.9 E−04 (19) −3.4 E−04 (6) −4.6 E−04 (8) −5.5 E−04 (5)
B-30-0 0.0 E+00 (0) −1.5 E−04 (29) −1.7 E−04 (30) −4.2 E−04 (11) −5.1 E−04 (11) −6.0 E−04 (5) −6.8 E−04 (9)
B-45-0 0.0 E+00 (0) −1.2 E−04 (22) −2.1 E−04 (5) −2.2 E−04 (3) −3.6 E−04 (6) −5.2 E−04 (2) −5.9 E−04 (2)
X-0-20 0.0 E+00 (0) −5.7 E−05 (20) −1.8 E−04 (10) −3.4 E−04 (4) −4.3 E−04 (2) −5.2 E−04 (3) −6.0 E−04 (5)
C-15-20 0.0 E+00 (0) −5.3 E−05 (60) −2.0 E−04 (8) −3.4 E−04 (6) −4.5 E−04 (9) −5.3 E−04 (7) −6.0 E−04 (6)
C-30-20 0.0 E+00 (0) −1.1 E−04 (10) −1.7 E−04 (6) −3.9 E−04 (4) −4.7 E−04 (0) −6.1 E−04 (1) −6.7 E−04 (3)
C-45-20 0.0 E+00 (0) −1.1 E−04 (24) −2.1 E−04 (7) −3.4 E−04 (7) −4.3 E−04 (7) −5.6 E−04 (5) −6.2 E−04 (4)
B-15-20 0.0 E+00 (0) −7.7 E−05 (59) −1.7 E−04 (24) −2.8 E−04 (16) −4.7 E−04 (15) −5.4 E−04 (10) −6.6 E−04 (10)
B-30-20 0.0 E+00 (0) −2.7 E−05 (87) −2.0 E−04 (13) −2.3 E−04 (12) −3.8 E−04 (9) −4.5 E−04 (10) −6.0 E−04 (5)
B-45-20 0.0 E+00 (0) −2.0 E−04 (46) −1.9 E−04 (46) −3.6 E−04 (25) −5.3 E−04 (16) −6.6 E−04 (11) −7.1 E−04 (13)

freeze–thaw durability. Test results showed that up to a 45% replace- contributions of graduate students Spencer Boyle, Tim Spry, and
ment of coarse natural aggregate with RCA had no significant effect on Danny Mjelde are also gratefully acknowledged.
any of the hardened concrete properties tested. In addition, all samples
tested met Washington State DOT minimum strength requirements for
use in concrete pavements. These results were obtained using RCA References
acquired from demolished pavements incorporating high-quality
original materials.  1. WSDOT Strategies Regarding Preservation of the State Road Net-
Results indicate that RCA of similar quality to those incorporated work. State Materials Laboratory, Washington State Department of
Transportation, Olympia, 2010.
in this study would be viable for use in new concrete pavements at  2. Wright, F. G. FHWA Recycled Materials Policy. FHWA, U.S. Depart-
up to 45% replacement of natural coarse aggregate. Properties of the ment of Transportation, 2006. http://www.fhwa.dot.gov/legsregs
RCA can be characterized using standards tests, including resistance /directives/policy/recmatpolicy.htm.
to abrasion and the amount of adhered mortar. While no maximum   3. FHWA, U.S. Department of Transportation, 2007. Use of Recycled Con-
effective RCA substitution rate was established in this study, the crete Pavement as Aggregate in Hydraulic-Cement Concrete Pavement.
results show that a 45% substitution of coarse natural aggregate with http://www.fhwa.dot.gov/pavement/t504037.cfm.
  4. Garber, S., R. Rasmussen, T. Cackler, P. Taylor, D. Harrington, G.
high-quality RCA meets all Washington State DOT requirements for
Fick, M. Snyder, T. Van Dam, and C. Lobo. Development of a Tech-
use in new PCCPs. RCA should be washed and sieved to remove fine nology Deployment Plan for the Use of Recycled Concrete Aggregate
particles prior to being used as a replacement for natural aggregates in Concrete Paving Mixtures. Report FHWA DTFH61-06-H-00011.
in new concrete. To address performance concerns related to ASR Work Plan 27. FHWA; National Concrete Pavement Technology Center,
of RCA, each RCA source should be tested for ASR following the Ames, Iowa, 2011.
crushing process, and mitigated as necessary.   5. Anderson, K. W., J. S. Uhlmeyer, and M. Russell. Use of Recycled
Concrete Aggregate in PCCP: Literature Search. Washington State
Further study should be performed to determine the minimum
Department of Transportation, Olympia, 2009.
criteria RCA must meet for use as an aggregate in concrete pave-   6. Limbachiya, M., M. S. Meddah, and Y. Ouchagour. Use of Recycled
ments as well as to evaluate higher RCA replacement rates. RCA Concrete Aggregate in Fly-Ash Concrete. Construction and Building
sources may require individualized quality control testing to address Materials, Vol. 27, No. 1, 2012, 439–449.
mitigation or other issues that can be identified only through quali-   7. Edil, T. B., J. M. Tinjum, and C. H. Benson. Recycled Unbound Materials.
fication testing. Construction of a test section incorporating RCA Report MN/RC 2012-35. Minnesota Department of Transportation,
Saint Paul, 2012.
is recommended to gain experience with real-world applications.
  8. Gonzalez, G., and H. Moo-Young. Transportation Applications of
Experience with the test section will be beneficial in developing Recycled Concrete Aggregate: FHWA State of the Practice National
implementation criteria and specifications related to the use of RCA Review. FHWA, U.S. Department of Transportation, 2004.
in pavements.   9. Wen, H., D. McLean, S. Boyle, T. Spry, and D. Mjelde. Evaluation of
Recycled Concrete as Aggregate in New Concrete Pavements. WSDOT
research report WA-RD 826.1. Washington State Department of
Transportation, Olympia, 2014.
Acknowledgments
10. Kosmatka, S. H., W. C. Panarese, and B. Kerkhoff. Design and Control of
Concrete Mixtures, Vol. 1. Portland Cement Association, Skokie, Ill., 2002.
The authors gratefully acknowledge the financial and technical
support provided by the Washington State Department of Transpor- The Standing Committee on Concrete Materials and Placement Techniques
tation and the Pacific Northwest Transportation Consortium. The peer-reviewed this paper.

You might also like