With this catalog we would like to provide investors, planners and technicians
with solutions to enable them to make future-proof decisions both for new buil-
dings and for modernisation projects. We give a detailed answer to the question
about intelligent building automation concepts that cater to the current global
and demographic trends: increasing population figures, increasing urbanisation,
increasing environmental pollution and at the same time increasingly scarce
energy resources, which necessitate an urgent rethink.
3
Future-proof buildings with automation
Electrical
Trans- energy
portation 15 %
28 % Building
41 %
Heating
Cooling
Industry
85 %
31 %
31 % worldwide
Energy consumption Energy consumption in buildings
85 %
Industry
Komfort
Source: Arbeitsgemeinschaft für
Thermischer
sparsamen und umweltfreundlichen
41%
Energieverbrauch e. V.
Gebäude
28% 15%
Transport
Energie
Elektrische
Source: VDMA
.
not only implement maximum energy efficiency, but also
Economy/independence: The open Beckhoff control
architecture meets all technical and economic require-
. ments.
Availability: The Beckhoff technology is available on
. are integrated.
Flexibility: Variably combinable software modules
ensure optimum individual adaptation.
Million €
630
620
620
610
600
590
580
570
560
550
540
530
520
510
500
490
480
470
460
450
440
430
420
410
400
390
380
370
360
350
340
330
320
310
300
290
280
270
260
250
240
230
220
210
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
18 911981
19 911991
10 022001
01022010
11022011
21022012
31022013
41022014
51022015
08911980
28911982
38911983
48911984
58911985
68911986
78911987
88911988
98911989
09911990
29911992
39911993
49911994
59911995
69911996
79911997
89911998
99911999
00022000
20022002
30022003
40022004
50022005
60022006
70022007
80022008
90022009
0
10
Turnover
20 development
30
40
50
60
70
80
90
100
110
120
130
8 470
480
490
500
510
520
530
540 We reserve the right to make technical changes.
550
Headquarters Headquarters distributor
Subsidiary Subsidiary distributor
Training
Operation
Commissioning
Implementation
Design
Concept
Idea
.
are required for a high-performance system:
The connection of all sensors and actuators
controller than in the past and therefore
require a scalable, high-performance
of a building into one system requires a
broadly diversified mix of the widest range . controller portfolio: like Beckhoff’s.
The load optimisation for the energy suppliers
10
11
°C
Wasser
CO2 °C
CO2/VOC
12
.
used in the building automation market, such as:
BACnet, OPC UA,
systems. The PLC is programmed in accordance
with the IEC 61131-3 standard. Long-term access
13
14
initial commissioning without having to install a new lar design also makes it easy to replace individual Bus
Industrial PC. Terminals or to make add-ins.
The modular building automation portfolio And should end users want to replace their
consisting of processors available in a range of per- Beckhoff IPCs with other controllers, this is possible
formance classes, Windows operating systems and as well. The wide range of available fieldbus couplers
TwinCAT software libraries makes it possible to adapt lets you link Bus Terminals to DDC or control systems
Industrial PCs to changing building requirements for from other manufacturers via Modbus, PROFIBUS
many years to come. Another sustainability feature of or other protocols. Thus, customers can combine
the Beckhoff solution is the long-term availability of Beckhoff components with products from any vendor
the Bus Terminal system. It has been on the market and enjoy a high degree of investment protection for
for almost 20 years, and with now more than 400 existing I/O units.
signal types it has become one of the world’s most
successful and comprehensive I/O systems. Its modu-
15
© RPHI/Bernd Steingruber
Widex A/S, Lynge, Zayed University,
Denmark Abu Dhabi, UAE
16
.. Munich, Germany
Campus Dornbirn, Dornbirn, Austria .. Office building ”Esplanade” Theresienhöhe, Munich, Germany
Schüco Technology Center, Bielefeld, Germany
..
Center for Virtual Engineering ZVE, Fraunhofer IAO,
Stuttgart, Germany .. Sky Tower, Bukarest, Romania
Tower 185, Frankfurt am Main, Germany
..
Etech Center/AMS Engineering, Linz, Austria
Eurotheum (European Central Bank), Frankfurt am Main, Germany .. Unipark Nonntal, University of Salzburg, Austria
WesBank, Johannesburg, South Africa
..
Fifth Light Technology, Oakville, Canada
Internorm, Traun, Austria .. Westpac Headquarters, Sydney, Australia
Widex A/S, Lynge, Denmark
..
KölnTriangle, Cologne, Germany
Microsoft, Cologne, Germany
Microsoft, Munich, Germany
. Zayed University, Abu Dhabi, UAE
Zukunftsmeile Fürstenallee, Paderborn, Germany
17
dSPACE, Paderborn,
Germany
www.beckhoff.com/building
18
19
20
.. United Kingdom
Royal Spa Kitzbühel, Austria
www.beckhoff.com/building
21
....
Carré Theatre, Amsterdam, Netherlands
Helsinki Music Center, Helsinki, Finland
....
Janacek Theatre, Bruno, Czech Republic
Kuopio City Theatre, Kuopio, Finland
....
People’s Grand Theatre, Jilin City, China
Ronacher Theatre, Vienna, Austria
....
Scala di Milano, Milan, Italy
Schauspielhaus Nürnberg, Nuremberg, Germany
....
Royal Danish Theatre, Copenhagen, Denmark
Sibelius Hall, Lahti, Finland
Stage Theater an der Elbe, “Das Wunder von Bern“,
Hamburg, Germany
....
Museums
Deutsches Museum, Munich, Germany
....
Charlottenburg Palace, Berlin, Germany
© Bregenzer Festspiele/Karl Forster
....
Sisi Museum, Vienna Hofburg, Vienna, Austria
Staatliches Museum für Archäologie, Chemnitz, Germany
City Museum Dresden, Germany
www.beckhoff.com/building
22
23
©Fraport AG
ESPRIT arena, Düsseldorf, Marmaray tunnel, Istanbul,
Germany Turkey
24
www.beckhoff.com/building
25
Application of the latest norms and standards gives rise to new possibilities for
the planning of new buildings and the renovation of existing stock. Good coope-
ration between the different fields represented by specialist planners, architects,
builders, commissioning engineers and operators can considerably improve the
ecological and commercial value of a building. An energy efficient, integrated
building automation system can only be implemented with the use of one control
system for all technical building systems.
27
Basic principles and standards of building automation
DIN EN 15232: the first time. It includes a structured list stated as a basic principle: the higher
energy efficiency of buildings of all building automation functions that the level of automation, the greater the ener-
European norm EN 15232 describes the can affect the energy efficiency of a building. gy savings.
effect of building automation and building It also offers systematic support for the defi-
management on energy efficiency and nition of minimum requirements concerning
enables standardised representation for building automation. The following can be
Equivalent to more advanced BAC systems and some special TBM functions B
Definition of classes
Control of transfer
The controller is installed at transfer level or room level; in the former case, one controller can regulate a number of different rooms.
0 No automatic control x x
1 Central automatic regulation x x x
2 Automatic individual room control using thermostatic valves or electronic control devices x x x x
3 Individual room control with communication between control devices and BACs x x x x x x
4 Integrated individual room control including needs-based regulation (occupancy, air quality, etc.) x x x x x x x x
Control of generators
0 Constant temperature x x
1 Variable temperature dependent on the outside temperature x x x x x x x x
2 Variable temperature dependent on the load x x x x x x x x
School
School
Office
Office
Hotel
Hotel
of buildings, the energy efficiency class C is
the reference class for the implementation A Highly efficient Building Automation and Control System 0.70 0.80 0.68 0.87 0.86 0.90
of measures for energy optimisation. (BACS) and Technical Building Management (TBM)
B Advanced BACS and TBM 0.80 0.88 0.85 0.93 0.93 0.95
The red field in the table on the right-hand C Standard BACS 1.00 1.00 1.00 1.00 1.00 1.00
side shows how the thermal energy con- D Non-efficient BACS 1.51 1.20 1.31 1.10 1.07 1.07
sumption of a building with efficiency class
A with a factor of 0.7 can be reduced by up Source: DIN EN 15232, table 9, table 11
to 30 %.
Solar shading
Monitoring
system installation phase. The reduction in the software on a single system during
Lighting
Security
Global
cabling also has a positive spin-off effect on commissioning and ongoing operations. As
HVAC
fire loads and building statics. a result, no reconstruction work impedes
To achieve energy efficiency class A in operation and the time required for software Light intensity x x x
accordance with EN 15232, Beckhoff offers adjustment also remains within reasonable Room temperature x x x
a software library based on room automation limits. In certain cases, many modifications Occupancy x x x x x
guideline VDI 3813. can be made by accessing the system remot- Window contact x x x x
Comprehensive room automation exploi- ely, without the need for a service technician Room operating x x x
ts the interdependencies of facade to attend in person. device
control, illumination and climate control to Weather x x
create a pleasant room climate. At the same The adjacent matrix shows the interplay of (wind/rain)
time, efficient room and zone control also the individual building systems with regard Outside x x x
affects the primary systems: the heating and to the sensors used. For energy efficient auto- temperature
cooling requirements and the air quantities mation, all individual building systems must Solar radiation x x x x
are regulated according to need. When desi- be controlled and managed from a single
gning the heating, cooling, ventilation and air system.
conditioning systems, the needs
For a better illustration of what lies behind on the cooling ceiling respectively. The room start of core working time is the energy level
building automation functions and how temperature is monitored and the desired raised to the level “Pre-Comfort”. The room
energy can be saved, examples of building room temperature is adjusted locally using temperature is now almost up to the comfort
automation functions in an office with energy EnOcean radio technology. target value. Only when persons are detected
efficiency class A are described below. For ventilation, the office is connected to in the room is “Comfort” mode activated and
an air-conditioning installation. Volume flow the appropriate set value reached in a short
Technical equipment of an office is variable. The open state of the window is time.
Illumination consists of one lighting strip captured via a digital input; so too is the dew The system switches from “Economy”
on the corridor side and one on the window point sensor on the cooling ceiling. to “Pre-Comfort” mode as late as possible
side. The lights are held at a constant via the energy level selector with start
room brightness level via DALI (constant optimisation. The optimum activation time
light control), depending on the amount Heating/cooling function is calculated by the building automation
of daylight. A room brightness sensor is To minimise energy use for room system.
mounted in the ceiling. An occupancy sensor heating and cooling, the desired room The opening of the window is monitored
is installed for needs-dependent management temperature is determined via a scheduler- by a window contact. If the window is open,
and control of the entire room. dependent energy level selector (see fig. 1, the system automatically switches to the
The office is shaded by means of two page 30, and fig. 2, page 31). In the case of “Protection” energy level. This automatically
electrically operated, externally mounted long absences, e.g. during shut-down periods, stops unnecessary energy consumption due
louvre blinds. Two buttons are installed for the office is switched to “Protection”, the to a window being opened.
manual control of the blinds. lowest energy level, to prevent damage The room temperature set values for all
To heat the room, a radiator is present. caused by frost or overheating. For brief four energy levels are provided by the room
The office is cooled via a cooling ceiling. absences, e.g. at night or on weekends, the climate function set value calculation for
An actuator is located on the radiator and office is set to “Economy” mode. Only at the heating and cooling.
31
Lighting
CO2/VOC
Air quality
Occupancy sensor
EnOcean
Temperature
Cooling ceiling
Ventilation
Shading
EnOcean
Window contact
Heating
The “Function Selection” function regulates the controller for heating Load optimisation
and cooling and compares the current room temperature against the Communication between systems for automation of energy
set value. If the current value is lower than the target value for the centres and systems for the generation and distribution of heating
energy level “Comfort” heating, the heating controller is activated. and cooling water enables needs-based adjustment of the flow
If the current room temperature is higher than the set value for the temperatures. This allows transfer losses to be minimised and the
energy level “Comfort” cooling, the cooling controller is activated. overall effectiveness of the systems to be increased.
Simultaneous heating and cooling is not possible.
CO2/VOC
Air quality regulation
Ventilation Depending on the measured air quality, the volume flow
In summer, natural cooling at night helps reduce energy controller is used to introduce more or less fresh air into the room.
consumption: The night cooling program switches on the room If the air quality is good, air intake is reduced to a minimum volume
ventilation system and ventilates the offices using cool external air. flow. The central air conditioning unit for ventilation automatically
This removes heat from the building at night so that less energy is adjusts the level of ventilation based on the data communicated
required to cool the room the following day. For electrically operated between the room automation system and the primary systems. This
windows, these can also be used for automatic night cooling in reduces the energy consumption of the fans by up to 45 %. In the
summer. event of zero occupancy, the volume flow is reduced to a minimum.
32
If the room is occupied and the sun is shining in strongly, the solar
Constant light control shading is automatically activated. The louvre adjustment optimises
If a minimum light strength in the room is not reached but the angle of the louvre according to the position of the sun. The
the room is occupied, the constant light control function switches on blades are positioned in such a way as to prevent blinding from direct
automatically. Conversely, if the amount of external light increases, sunlight while keeping the need for artificial lighting to a minimum in
the proportion of artificial light automatically reduces or is switched order to reduce energy consumption.
off once a suitable lighting strength is reached. If the occupancy The shading correction function calculates the shadow movement
detector identifies that the room is empty, the constant light control on the facades of the building, depending on the position of the
function switches itself off on a time-delay basis. sun, the facade orientation and the position and coordinates of the
surrounding buildings that provide shade. This prevents unnecessary
activation of the solar shading and increased energy consumption due
Shading to the use of artificial light within the building.
Control of solar shading is integrated directly into the
room automation system. The “thermo-automatic” function supports
the heating and cooling function of the room if it is not occupied.
To benefit from sun light in winter, solar shading is raised to help
heat the space using the sun’s rays. In summer, the solar shading is
automatically activated to reduce the energy yield from the sun and to
assist cooling. 33
34
The use of Ethernet cabling right down to manner so that the BACnet properties can industry-neutral nature makes it increasingly
field level provides a transparent network be easily linked to the PLC as parameters popular as a consistent communication
for commissioning and maintenance, and and process data. In addition, the ability platform in building automation and smart
depending on requirements, the relevant to access BACnet data via a non-cyclical metering applications.
IP-based protocol can be used for commu- interface makes it easy to implement
nication on this network. visualisation components. Another feature is Since OPC UA can be used as both server
the dynamic generation of BACnet objects, and client, the traditional “top-down”
BACnet/IP which makes it possible to subsequently direction of the communication flow becomes
The international BACnet standard, which generate and configure schedules and increasingly immaterial. While “OPC classic”
ensures the interoperability of building trend objects. Distributed clocks can be was based exclusively on Microsoft’s COM/
automation and control devices from synchronised with the supported client DCOM technology, OPC UA is independent
different manufacturers, is growing in and master functions, and even automatic from the operating system and language as
popularity and is being constantly enhanced summer and winter time adjustments can be well as scalable from the sensor to the ERP/
with new functions. BACnet/IP can be used implemented with the integrated operating cloud level. Security-by-design provides user
on all PC-based Beckhoff hardware platforms system functionality. Since hardware status authentication, message signing and data
– down to the field level – as a universal monitoring has been integrated into the encryption already in the OPC UA stack. And
Ethernet protocol. The rail-mountable BACnet/IP implementation, it is available to its specification of information models makes
Embedded PC models CX8091, CX9020, all BACnet/IP applications without additional OPC UA particularly interesting for other
CX5010 and CX5020 are certified for the effort, too. The advanced alarm and event organizations, who can organize their existing
ISO 16484-5:2010 BACnet standard and services, additional object types, improved objects in the UA name space and define
feature a powerful control platform: ranging device management features and increased “What is being communicated” while OPC UA
from the CX8091 with support for 250 data execution performance of BACnet Rev. 12 are manages transport security and access rights
points to the CX5020 which can collect and also implemented in TwinCAT BACnet/IP and by asking “How is it being communicated?”.
process several thousand BACnet objects. add to the user benefits. OPC UA is currently the only IEC standard-
The extensive requirements of public and based SOA technology that features semantic
private property operators concerning the Since the Beckhoff solution was developed interoperability.
support of BACnet functionality can be met completely in-house, users can be confident
using the AS-B application profile (extended that the company has plenty of expertise in The BACnet OPC UA
BACnet functionality) in compliance with the field. information model
the specifications of the AMEV BACnet 2011 Besides PLCopen, the BACnet Interest
standard. OPC Unified Architecture (UA) Group Europe collaborates with the OPC
OPC UA is gaining acceptance on all levels Foundation in a working group with the
And since the BACnet protocol is integrated of the automation pyramid. Its scalability aim of representing BACnet objects in the
into the TwinCAT System Manager, the ranges from small 15-kB footprint OPC UA name space and ultimately creating
I/O Bus Terminals and BACnet devices applications in embedded sensors to an easy link to administrative/ERP processes
are easily configured via the tool-based communication with ERP level and SAP via OPC UA.
automapping function. BACnet servers systems right up into the cloud. OPC UA has
and clients can be installed in a structured its origin in automation technology, but its
35
Internet of Things,
Cloud Services, Big Data
AMQP
MQTT
BACnet/IP, Real-time Ethernet, Modbus TCP, EtherCAT OPC UA
Management
level
Automation
level
Field level
EnOcean SMI
Depending on the way they are being used, buildings have different And if you need to extend the system, you can simply replace the
levels of control requirements. To meet these requirements, Beckhoff’s head station without having to make major changes in the application
automation portfolio includes “head stations” in various performance program. The use of decentralised Web servers on Industrial PCs
classes which allow you to scale the control platform in line with the and Embedded PCs also allows easy access to different system
respective performance requirements. Since all controllers are freely components. Room controllers are available as compact solutions for
programmable, you can develop a uniform control concept for the room automation across different building systems.
different requirements of each system component.
36
Air-conditioning
Top floor
Typical
Shop 1 Shop 2 Shop n
shop floor
Basement
Monitoring, data logging
37
38
Beckhoff offers a range of different software libraries that enable optimum networking with
external components and systems. This allows systems such as hotel reservation systems, for
example, to be integrated into a building automation system. Moreover, the PC platform supports
different interfaces for controlling multimedia components and thus allows a variety of applica-
tions to be implemented in the areas of media, stage and show technology.
The following software solutions are hardware is exchanged via Ethernet. For platform with devices and systems from the
available for connecting third-party systems the Crestron control systems, software area of stage and event technology. TwinCAT
and can be used as a single solution modules (user modules) are available. The can therefore be integrated very easily in
throughout. Crestron controller can access read and write the stage technology, for example, using the
commands; the Beckhoff controller can use EtherCAT Terminals EL6851 (DMX master)
FIAS – for hotel applications the TwinCAT Crestron server to write data to and EL6851-001 (DMX slave). All of the
The Fidelio FIAS (Fidelio Interface and the Crestron control system or extract data devices and systems relevant for media and
Application Specification) is becoming from it. stage technology can be controlled with the
the world’s leading hotel management Beckhoff automation platform over interfaces
software. Since there is a constantly growing B&O – for controlling audio to AES 70 (OCA), PJLink, DMX, SMPTE
demand for networked systems and room and video systems TimeCode, Art-Net™, Streaming ACN (sACN)
automations in hotels, the TwinCAT FIAS Bang & Olufsen is world-famous for its and PosiStageNet. Stage control, lighting,
server provides a direct FIAS interface that unique range of high-quality audio, video sound and video effects, kinetic installations
facilitates smooth communication between and multimedia products. The TwinCAT or animated figures as well as interactions
the hotel management system and PLC. Bang & Olufsen Server is a software package can therefore be run on a universal platform.
for accessing the B&O Masterlink Gateway.
Crestron – for controlling AV It enables communication between a Integration of further systems
and multimedia equipment TwinCAT PLC and the Bang & Olufsen In collaboration with innovative suppliers,
Crestron Electronics is a market leader in multimedia network via TCP/IP. more and more systems and devices can be
media management systems. In addition integrated into the Beckhoff control platform,
to the management of audio and video Interfaces to stage and show for example to implement operating, fire
systems, building services components can technology systems protection and access control systems as well
also be integrated. The data between the Various Bus Terminals and software libraries as the whole range of sensors and actuators.
Crestron management system and Beckhoff are available for connecting the PC control
39
Shading/Facade
Lighting
HVAC
Water supply
40
Room automation
Data logging
Remote maintenance
41
Beckhoff solutions
Communication between the individual automation stations takes
place via Ethernet TCP/IP. The level of automation in a room can be
individually adjusted through free configuration of individual Bus
Terminals. Alternatively, the BC9191 room controller integrates these
functions within a single module. Rooms and/or areas with repeat
requirements need only be programmed once and can be replicated.
With features like these, an efficient, multi-component room
automation system can be implemented that meets energy efficiency
class A.
44
.. Time program
Automatic lighting .. Target point determination
Function selection
.. Daylight sensor
Constant light control .. Temperature control (heating/cooling)
Sequence control
.. Slat adjustment
Shading correction
Automatic temperature control
.. Target value limiter
Air quality control
Night cooling
Bus Coupler/
Embedded PC
Field level
HVAC Lighting Facade/door Operation and monitoring
°C
Switchable power
Temperature
outlets
Humidity
45
Sample configuration
Traditional floor and room | standard room automation
Product Description
CX5010-1111 TwinCAT PLC, Windows CE
- CX1800-1052 Windows CE, BACnet image*
- CX1900-0025 2 GB CF card instead of 128 MB*
Floor and room with fieldbus | Room automation with DALI, SMI, and Enocean
Product Description
CX5010-1111 TwinCAT PLC, Windows CE
- CX1800-1052 Windows CE, BACnet image*
- CX1900-0025 2 GB CF card instead of 128 MB*
*optional BACnet components
EL6861 1-channel BACnet MS/TP interface RS485, KL6821 DALI/DALI 2 multi-master and power supply terminal
D-sub connection Connection of DALI/DALI 2 actors and sensors
connection of BACnet MS/TP field devices KL6771 MP bus master terminal, 8 drives max.
BK1250 “Compact” coupler between E-bus and K-bus terminals Volume flow control
conversion from E-bus to K-bus KL2641 1-channel relay output terminal 230 V AC, 16 A
KL1104 4-channel digital input terminals 24 V DC Switchable floor lamp power outlet
Dew point monitor KL6841 SMI master terminal 230 V AC, 16 drives max.
KL6581 EnOcean master terminal Sunshade actuator UP
KL6583 EnOcean transmitter and receiver Sunshade actuator DOWN
Air quality sensor KL9010 End terminal
Temperature setpoint
Light switch for floor lamps/ceiling lights
Shutter switch UP/DOWN
Window contact
Room temperature sensor
The BK9000, BK9050 or BK9100 Bus Coupler makes it easy to expand the decentralized room automation system.
46 You simply replace the CX controller with one of these Bus Couplers. The terminals are the same.
Beckhoff solutions
Decentralised room automation with CX9020 and BC9191 Central control functions
This setup offers maximum modularity because every zone has a A central floor or building controller is recommended for general
decentralized control system for which the parameters can be freely functions such as floor or staircase lighting, the FIAS server link, and
defined. An embedded controller communicates with the building higher-level functions based on weather data, for example.
management system in the respective zone in order to transfer all the
data. For a more upscale setup, each room or suite can be equipped
with a CX9020 Embedded PC for maximum flexibility.
48
..
meeting or seminar rooms can also be easily integrated into the room automation system.
Automatic occupancy registration
.. Timer program
Automatic lighting
..Daylight sensor
Automatic temperature control
..
Energy level selection with start optimisation
Setpoint determination
..
Function selection
Temperature control (heating/cooling)
Sequence control
Bus Coupler/
Embedded PC
Field level
HVAC Lighting Facade/door Operation and monitoring
°C
Temperature
Heating
49
Sample configuration
Floor controller
Product Description
CX9020-0111 TwinCAT PLC, Windows CE
- CX1800-1052 Windows CE, BACnet image*
- CX1900-0025 2 GB CF card instead of 128 MB*
- TS8035 TwinCAT FIAS Server
KL1809 16-channel digital input 24 V DC KL1722 2-channel digital input terminal 120/230 V AC
Window contact Occupancy sensor
Light switch for secondary rooms KL2602-0010 2-channel relay output terminal 230 V AC, 5 A,
KL6821 DALI/DALI 2 multi-master and power supply terminal make contacts
Connection of DALI/DALI 2 actors and sensors contact-protecting switching of LED lamps
KL9160 Potential feed terminal 120…230 V AC, with diagnostics at zero voltage crossing
KL9010 End terminal
EL6861 1-channel BACnet MS/TP interface RS485, KL2284 4-channel digital output terminal 24 V DC, 2 A, reversible
D-sub connection Curtains CLOSED/OPEN
connection of BACnet MS/TP field devices KL3208-0010 PT1000 8-channel analog input
EL6851 DMX master terminal Room temperature sensor
Lighting Temperature setpoint
BK1250 Coupler between E-bus and K-bus terminals KL2641 1-channel relay output terminal 230 V AC, 16 A
KL9400 Power supply terminal to refresh K-bus Switchable floor lamp power outlet
KL1809 16-channel digital input 24 V DC KL9160 Potential feed terminal 120…230 V AC, with diagnostics
Dew point monitor KL2751 1-channel universal dimmer terminal 230 V AC
Window contact Lighting
Occupancy sensor KL9160 Potential feed terminal 120…230 V AC, with diagnostics
Light switch for floor lamps KL2722 2-channel triac output terminal 230 V AC
Light switch for ceiling lamps Shutters UP/DOWN
Curtain switch OPEN/CLOSED KL9010 End terminal
Shutter switch UP/DOWN
50
Beckhoff solutions
The extensive Beckhoff Bus Terminal portfolio features I/O modules for terminal is available. The KL3403 power monitoring terminal is used
a wide spectrum of applications and functions. Mechanical ventilation for the direct metering of electricity. Even highly sensitive clean-room
systems with automated roof vents can be controlled via the Beckhoff applications can be controlled with high precision measurement
KL2722 Bus Terminal. The KM3702 monitors product media such as technology from Beckhoff.
compressed air. For reading and analysing the consumption of heat,
water and gas as well as power meters, the KL6781 M-Bus master
52
.. Timer program
Automatic lighting .. Function selection
Temperature control (heating/cooling)
.. Daylight sensor
Constant light regulation .. Cascade control for air supply temperature
Fan control
.. Slat control
Shading correction .. Sequence control
Setpoint limiter
Bus Coupler/
Embedded PC
Field level
HVAC Lighting Facade/door Operation and monitoring
°C
Constant light Remote
Temperature Rolling shutter gate
regulation maintenance
DALI
Mechanical ventilation
Cooling DALI Control panel
via roof vents
Heating Timer
Humidity
53
Sample configuration
Standard automation of industrial buildings
Product Description
CX9020-0111 TwinCAT PLC, Windows CE
- CX1800-1052 Windows CE, BACnet image*
EL6861 1-channel BACnet MS/TP interface RS485, KL3208-0010 PT1000 8-channel analog input
D-sub connection Room temperature sensor
connection of BACnet MS/TP field devices Temperature setpoint
BK1250 Coupler between E-bus and K-bus terminals KL3468 8-channel analog input 0…10 V
conversion from E-bus to K-bus Air quality sensor
KL1809 16-channel digital input 24 V DC Light sensor
Door contact KL9186 Potential distribution terminal 24 V DV
Window contact KL9187 Potential distribution terminal 0 V DV
Light switch KL3454 4-channel analog output terminal 4…20 mA
Precipitation sensor Wind sensor
Rolling shutter gate UP Daylight sensor
Rolling shutter gate DOWN Outside temperature
Roof vent OPEN KL9400 Power supply terminal to refresh K-bus, 24 V DC, 2A
Roof vent CLOSED KL3403 3-phase power monitoring terminal
KL6581 EnOcean terminal System power metering
KL6583 EnOcean transmitter and receiver KL9160 Potential feed terminal with diagnostics, 230 V AC
Light switch KL1722 2-channel digital input terminal 120/230 V AC
Roof vent OPEN Occupancy sensor
Roof vent CLOSED KL2722 2-channel triac output terminal 230 V AC
Room temperature sensor Roof vent OPEN
KL6821 DALI/DALI 2 multi-master and power supply terminal Roof vent CLOSED
Connection of DALI/DALI 2 actors and sensors KL2622 2-channel relay output terminal 230 V AC, 2 A,
KL6781 M-Bus master terminal potential-free relay contacts
M-Bus gas meter Rolling shutter gate UP
M-Bus power meter Rolling shutter gate DOWN
M-Bus water meter KL2622 2-channel relay output terminal 230 V AC, 2 A,
KM3702 2-channel absolute pressure measuring terminal potential-free relay contacts
7,500 hPa (7.5 bar) Ventilation ON
Pressurised air monitor KL9010 End terminal
KL2809 16-channel digital output 24 V DC
Ventilation level 1
Ventilation level 2
Ventilation level 3
54
55
The system is rounded off by manual operating modules for These function blocks provide effective and peak values for current,
integration into control cabinet doors; these allow monitoring and voltage and power. In addition, the free M-Bus library offers many
operation of the system without having to open electrical cabinets. options for reading data from M-Bus slaves with the KL6781 and
Process data is represented directly using the K-bus in the PLC. The processing it directly in the PLC. In combination with the multi-meter
coloured configurable LEDs give a clear view of the system status. terminal, TwinCAT Scope 2 provides an easy-to-use tool for collecting
data and analysing signals graphically.
Energy data collection
Running a system efficiently requires a lot of measurement
technology. Besides its standard portfolio of hardware and software,
Beckhoff offers as part of its TwinCAT Building Automation Library
function blocks that simplify using the KL3403 Power Measurement
Terminal considerably.
56
..
such as:
Summer night cooling ..
Pressure control
.. Summer compensation
Sequence control .
Motor control
Hot water production
. Time schedulers
Enthalpy calculation
For comprehensive use of Bus Terminals for BACnet MS/TP, DALI/DALI 2, EnOcean, EIB/KNX, LON, M-Bus,
MP-Bus and Modbus, other PLC libraries are available.
Bus Coupler/
Embedded PC
Field level
HVAC Operating and monitoring
P
Ambient
T Pressure measurement 1-0-A Manual operating module
temperature
Humidity Remote
Ventilation
maintenance
°C
M Pump Temperature Timer
CO2/VOC
Air quality
Cooling/
dehumidifying Energy data
Strom
acquisition
T
Water level
Heating circuit
+
\×/− Sequence controller
57
Sample configuration
HVAC system
Product Description
CX5010-1111 TwinCAT PLC, Windows CE
- CX1800-1052 Windows CE, BACnet image*
- CX1900-0025 2 GB CF card instead of 128 MB*
B01
F14_3 F14_2 F04
T B11 ΔP ΔP ΔP B04 BD2 B06
Y02 T T P T
M02
M02
F14_1 F04
ΔP F1 ΔP BD1 B03
Y01 Y101
+ T − P T
B09 M01
Y102 M06 T
Y20 Y22
M M
58 HVAC system
B15
B083 Y202 Y203 Y204 outgoing ventilation
T M M M circuit
T
M161
Y201
M
B081 B082
M231 T T
F11 F
F12 F
T T
F13 F
B091 B092
F14 F
B001
T
Remote maintenance
Due to complexity, the automation of buildings and real estate requires access using remote
diagnostics, remote maintenance and remote control. To avoid unnecessary costs caused by
system failures, rapid support by specialists is required for error diagnosis, software maintenance,
and for the import of updates. For ongoing building operation and for system optimisation,
information on process variables is required together with warning and error messages made
available to service personnel by cloud services, for example.
Beckhoff solutions
.
Diagnostics and services
networking via cable (e.g. ISDN, DSL) or using mobile radio
.. connectivity to mobile devices, such as smartphones and tablet PCs
support of communication protocols BACnet/IP, OPC UA, IEC 61850
. automation technology
use of cloud services directly from the PLC, such as e.g. data
logging, TwinCAT IoT, TwinCAT Analytics and other IoT-based
Scope server
services
60
..
Remote control
Use of cloud-based services
Sending of text messages and e-mails directly
Remote programming
.
Full access to the control unit for modification of
system configurations and control program by
.
from the control unit for notification of service
personnel .
means of “online change”
Central administration of Beckhoff CE
Remote Desktop, Lync or Team Viewer enable
operation of the entire PC controller via .
controllers via the TwinCAT management server
VPN router for secure access via Internet/
..
Diagnostics
Data logging
.
Online change
Remote user access
Bus Coupler/
Embedded PC
Amazon AWS™
Microsoft Azure™
SAP HANA® Cloud Platform/
Private Cloud
Storage
Storage Analytics
Analytics Messaging
Services
Services Services
Services Services
MQTT
AMQP
OPC UA
Smart Building
Data access is possible from any mobile or stationary computing device – anytime and anywhere. 61
Beckhoff offers modular automation components of finely grained I/Os, scalable con-
trollers and modular software that enables implementation of all building automation
requirements, with particular focus on energy efficiency and sustainability. In combi-
nation, they enable application-specific solutions for all building types and utilisation
options.
63
Page 68 Page 74
°C
Wasser
CO2
CO2/VOC
64
Maximum flexibility
PC-based control technology enables all building functions and function changes to be realised in
software based on TwinCAT, which consists of a wide range of software modules and offers users
maximum flexibility. The use of standard software components, which integrate all key building
functions, reduces the engineering costs significantly.
Page 70
°C
°C
65
AMQP
MQTT
OPC UA
Management
level
Automation
level
Digital input
Digital output
Analog input
Analog output
Sub-bus systems
Field level
Room Controller
66
ERP
Panel PC
DMX Digital I/O Digital I/O
BACnet MS/TP Analog I/O Analog I/O
Modbus RTU PROFIBUS
MP-Bus PROFINET
CANopen
DMX
Bus Coupler,
Embedded PC, Bus Terminals Embedded PC, Bus Terminals Bus Terminals
Embedded PC, Bus Terminals Embedded PC, Bus Terminals Bus Coupler, Bus Terminals
67
Panel PC
CP6606
Control cabinet PC
C6915
68
Multi-touch Panel PC
CP2224
Control cabinet PC
C6925
Industrial PCs
Panel PCs
Embedded PC CX9020
Scalable controller performance: from 16-bit CPU to x86 CPU with 1.5 GHz on 12 cores
69
....
High-end PLC
internationally-recognised IEC 61131-3 programming standard ....
Communication interface TwinCAT ADS
universal vertical and horizontal communication
....
reusable software modules
almost unlimited memory ....
cyclical/event-triggered
Open protocol with documented examples for:
....
unlimited number of function blocks and variables
high-speed software solutions for controllers, etc. ....
C/C++
.NET
up to four runtime systems per PC, up to four tasks
per runtime system ....
Delphi
Java
....
JavaScript
WebService
.... WCF
available on Windows operating systems
access from the PLC via function blocks possible
User mode
TwinCAT system
ADS ADS
TCP/IP
ADS Router
ADS ADS
I/O Mapping
Fieldbus Card Drivers
Kernel mode
70 TwinCAT system architecture
EN15232,
TwinCAT TwinCAT TwinCAT TwinCAT
VDI3814,
BA PLC BA PLC BA Project PLC,
VDI3813,
Libraries Templates Builder System Manager
XLS …
71
72 Based on the component identification system in TwinCAT BA, a tree structure is generated in the PLC Explorer that depicts the building topology.
..
continuous routing via:
UDP/TCP/serial/Bluetooth/fieldbus/
TwinCAT PLC Modbus RTU
....
TwinCAT PLC Serial Communication .... TwinCAT TCP/IP Connection Server
TwinCAT XML Data Server
EtherCAT/SOAP (HTTP) TwinCAT PLC IEC 60870-5-10x
TwinCAT PLC IEC 61850 Server .... TwinCAT SMS/SMTP Server
TwinCAT PLC HMI
..
TwinCAT network variables
publisher/subscriber variables via
....
Supplements for Building Automation:
TwinCAT PLC HMI Web
....
TwinCAT OPC UA ....
Cloud connectivity
TwinCAT 3 IoT Communication
....
Libraries for Building Automation:
TwinCAT PLC EIB
TwinCAT Building Automation
....
TwinCAT FIAS Server ....
TwinCAT 3 IoT IoT Functions
TwinCAT 3 IoT Data Agent
....
TwinCAT PLC LON
TwinCAT PLC EnOcean
TwinCAT Crestron Server
TwinCAT Bang & Olufsen Server
TwinCAT 3 IoT Communicator
....
TwinCAT PLC MP-Bus
TwinCAT PLC M-Bus
....
Additional Supplements: ....
Data analysis
TwinCAT 3 Analytics Logger
....
TwinCAT PLC DALI
TwinCAT PLC SMI
TwinCAT PLC DMX
TwinCAT Database Server
..
TwinCAT Modbus TCP Server
TwinCAT ADS Communication Library
....
TwinCAT 3 Analytics Workbench
TwinCAT 3 Analytics Library
TwinCAT 3 Analytics Cloud Storage
Cyclic
Real-time Ethernet
PC 1 PC 2
DALI/DALI 2 multi-
master and power
supply terminal
Embedded PC series CX
with integrated IEC 61131-3 PLC and
extended interfaces
DMX master or slave More efficient manual/emer-
terminal for integration gency operation using Bus
of lighting, movable Terminals: switch or potentio-
light elements or mixing meter in Bus Terminal format
consoles via EtherCAT for process data change
independent of the controller
74
K-bus
Terminal bus
extension for the
connection of up to
255 (instead of 64)
Bus Terminals to a
station
76
77
78
Industry-specific information
PC-based Control for
Stage and Show Technology
Media and Control Technology
Integrated Building Automation Solutions
■ for System Integrators
■ for Architects
■ for Operators
■ for Investors
Additional information
PC-based Control for
■ Urban Environments
■ Wind 4.0
■ Water Management
■ Photovoltaic Production
■ Shipbuilding
PC Control magazine
PC Control magazine
Stage Technology Compendium 2016
Building Automation Compendium 2015
79
Beckhoff®, TwinCAT®, EtherCAT®, EtherCAT P®, Safety over EtherCAT®, TwinSAFE®, XFC® and XTS® are registered trademarks of and licensed by Beckhoff
Automation GmbH. Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights
of the owners.
The information provided in this brochure contains merely general descriptions or characteristics of performance which in case of actual application do not
always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall
only exist if expressively agreed in the terms of contract.
Picture credits: AEC Pole Division, Subbiano, Italy | ATELIER BRÜCKNER/Michael Jungblut | Bregenzer Festspiele/Karl Forster | CitizenM Hotel, Amsterdam, Netherlands | Cunard Cruise Line, U.K. |
dSpace, Paderborn, Germany | Dolder Grand Hotel, Zurich, Switzerland | F-eins, Wien, Austria | Fraport AG, Germany | Hotel Grischa, Davos, Switzerland | Hotel Aurelio, Lech, Austria |
Inter-System S.A., Wroclaw, Poland | Magical Production, Dubai, UAE | Michael Fritschi, foto-werk.ch | Park-Hotel Vitznau, Switzerland | Quality Pond Hotel, Sandnes, Norway |
Schüco International KG, Bielefeld, Germany | Sensirion, Stäfa, Switzerland | Serlachius Museum, Mänttä, Finland | Sky Tower, Bukarest, Romania, RPHI/Bernd Steingruber |
Widex A/S, Lynge, Denmark | Zayed University, Abu Dhabi, UAE | Center for Virtual Engineering (ZVE), Fraunhofer IAO, Stuttgart, Christian Richters | Zukunftsmeile Paderborn, Germany