C2020/104-Design and Construction of

Pedestrian Crossings (Phase 3) Project Code:


BA 2019 C 043 G

Document Description: Design Calculations Electrical Report MOI 20 Pedestrian Bridge Submittal
Document Submittal Ref: C2020-104-MOI-22-RPT-DD-EL-0001 Revision No. 0

Response by: Submission Date 21/3/2021

eview Reference: Review/Comment Date 05/Apr/2021

A : Approved As Submitted

Consent Classification:
B : Accepted with Comments,
C: Revise and Resubmit, Not Approved Overall Submittal Status:
B : Accepted with
D : Rejected
E: For Information Only
Comments

Category: Cat 4: major comment Cat 3: technical comment Cat 2: non-technical comment Cat 1: important for future submissions Cat 0: Observation/Note

No Description of Reference Consultant Comments Reviewer Category Contractor's Response PORR CDMSmith
Closed/Open Closed/ Open

Air conditioning for electrical and cctv rooms and power load
requirement.
Data cables (CAT 6A) shall not exceed 100m for CCTV.
FA system shall be included on UPS
Clarify the grounding requirement of FA system
All exposed backboxs (input/output fire modules, ACS back
boxes) shall be metal clad.
All response indicator for void detector shall be provided with
Backbox.
C2020-104-DWG-DD-EL-MOI-20-1004 Cable for strobe/sounder
shall be 2.5mm2. rectify
To provide permanent access panel for smoke detector above
false ceiling (gypsum ceiling).
FA cause and effect matrix. Lifts monitoring and control
philosophy.

539030570.xlsx Page 1 of 3
C2020/104-Design and Construction of
Pedestrian Crossings (Phase 3) Project Code:
BA 2019 C 043 G

Document Description: Design Calculations Electrical Report MOI 20 Pedestrian Bridge Submittal
Document Submittal Ref: C2020-104-MOI-22-RPT-DD-EL-0001 Revision No. 0

Response by: Submission Date 21/3/2021

eview Reference: Review/Comment Date 05/Apr/2021

A : Approved As Submitted

Consent Classification:
B : Accepted with Comments,
C: Revise and Resubmit, Not Approved Overall Submittal Status:
B : Accepted with
D : Rejected
E: For Information Only
Comments

Category: Cat 4: major comment Cat 3: technical comment Cat 2: non-technical comment Cat 1: important for future submissions Cat 0: Observation/Note

PORR CDMSmith
No Description of Reference Consultant Comments Reviewer Category Contractor's Response Closed/Open Closed/ Open

Provide operating principle of presence detector. Presence


detectors shall have built-in adjustable lux sensors which shall
keep the lighting switched off if there is sufficient natural light.

539030570.xlsx Page 2 of 3
Consent and Withholding of Consent to Submissions

The Engineer's Decision on documents submitted for his consent shall follow the classification below:

Decision "I": As CDM Smith is not yet employed in the capacity of Supervision Consultant on the Artscape works,
a review has been performed on the this submittal for information only. This review is only for the
general conformance of the submittal, based upon the information available in the Project
documentation. Any errors, omissions and/or deviation from the project shall not relieve the
Contractor of his responsibility under the Contract.