DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6/CP-07

DHAKA MASS RAPID TRANSIT DEVELOPMENT PROJECT

MRT LINE 6
CONTRACT PACKAGE NO. CP-07
Procurement Of E&M Systems comprising of Track Works, Electrification System (Power
Supply, Catenary, SCADA and Energy Storage System), Lifts and Escalators, Signalling System,
Telecommunication System, Automatic Fare Collection System and Platform Screen Doors for
MRT Line 6

DESIGN REPORT OF DROP ARMS, SUPER MAST AND


ANCHOR BASE PLATE
Document No. 07-OCS-0000-DRP-00028

Contractor: DDC: Employer:

MARUBENI L&T JV SYSTRA MVA CONSULTING DHAKA MASS TRANSIT


c/o Larsen & Toubro Limited (INDIA) PRIVATE LIMITED COMPANY LIMITED
Sonargaon Janpath Block I, Vatika Mindscapes, Tower-B, Level 14, Probashi Kalyan
Sector 16 Uttara Model 12/3, 9th & 10th Floors, Mathura Bhaban
Residential City (3rd Phase) Road, NH-2, Sector-27/D, 71 -72, Old Elephant Road,
Uttara, Faridabad, Haryana- 121013. Eskaton Garden, Dhaka – 1000
Dhaka – 1230, India. Bangladesh
Bangladesh.

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 1 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6/CP-07

REVISION HISTORY

Revision Details
Revision No. Revision Date Approved by
Clause No. Revision

00A 30-01-2020 First Submission

6.1, 7.3, 7.7,


00B 21-03-2020 Revised as per Client comments
7.8.6, 9, 10

Sowmya Sahil
Majumder/ Jasrotia/ Satish Page of
00B 21/03/2020
Pushkar Sowmya Kumar Pages
Sinha Majumder
Name Sign Name Sign Name Sign
2 of 28
Rev Date Prepared by Reviewed by Approved by

Document Number 07-OCS-0000-DRP-00028

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 2 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6/CP-07

MRT Line 6-Contract No. CP-07

DESIGN CERTIFICATE

This Design Certificate refers to Submission No. 07-OCS-GTP-00011

Design Stage: Conceptual Design / Preliminary Design / Site Design / Completion (As-Built Document)

in respect of: Construction Design

[description of the Works to which the submission refers]

The contents of this submission are listed in Section A below.

Documents for which a Notice of No Objection has previously been issued and which are of relevance to this
Submission are listed in Section B below.

DESIGNER'S STATEMENT

We certify that the design of the Works, as shown and described in the drawings and documents listed in
Section A below,

(a) has been designed by us and complies with the Employers Requirements and all other requirements of the
Contract;
(b) has been confirmed as a complete, adequate and valid of the design through an in-house design and QA
check
(c) includes all necessary and required approvals (e.g. from Local Authorities or agencies etc.) relating to the
design and copies of such approvals are annexed in Section C below;
(d) all effects of the design comprising the submission on, or from, the design of adjacent or other parts of the
Works and Interfacing Contracts have been fully taken into account in the design.

Signed by 'Authorised Representative' (for Designer)

Name: V Srinivas Date: 21-03-2020

Position/Designation: Project Director

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 3 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6/CP-07

MRT Line 6-Contract No. CP-07

CONTRACTORS CERTIFICATION

This Certifies that all design has been performed utilising the skill and care to be expected of a professionally
qualified and competent designer, experienced in work of similar nature and scope. This further certifies that all
works relating to the preparation, review, checking and certification of design has been verified by us.

Signed by 'Authorised Representative', (for Contractor)

Name: Saptarshi Chakraborty Date: 21-03-2020

Position/Designation: Manager

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 4 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6/CP-07

Section A

Submission No.: 07-OCS-GTP-00011

Comprises the following:

Drawings:
NA

Documents:

Title Reference Number Revision

DESIGN REPORT OF DROP ARMS, SUPER


07-OCS-0000-DRP-00028 00B
MAST AND ANCHOR BASE PLATE

Others:
N/A

Section B
Comprises the following:

Drawings:

Documents:

Title Reference Number Revision

NA

Others:

N/A

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 5 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6/CP-07

TABLE OF CONTENTS

1 PREAMBLE .............................................................................................................. 8
2 DEFINITIONS AND ABBREVIATION ....................................................................... 8
DEFINITIONS ............................................................................................................................................. 8
ABBREVIATIONS ....................................................................................................................................... 8
3 REFERENCES .......................................................................................................... 8
INTERNATIONALS AND EUROPEANS ........................................................................................................ 8
OTHER REFERENCES ................................................................................................................................. 8
4 ASSUMPTIONS ........................................................................................................ 9
ENVIRONMENT AND LOADING CASES ...................................................................................................... 9
CONDITIONS FOR CALCULATIONS ............................................................................................................ 9
5 SAFETY FACTORS AND CRITERIA FOR ACCEPTANCE ...................................... 9
LOAD COMBINATIONS USED .................................................................................................................... 9
6 USED VALUES ....................................................................................................... 12
OCS CHARACTERISTICS ........................................................................................................................... 12
WEIGHTS ................................................................................................................................................ 12
WIND LOAD ............................................................................................................................................ 12
7 SITUATION ............................................................................................................. 13
LAYOUT PLAN ......................................................................................................................................... 13
CROSS SECTIONS .................................................................................................................................... 14
LOADING INPUT SHEET FOR STAAD ANALYSIS ....................................................................................... 15
DROP ARM MODEL ................................................................................................................................. 16
PORTAL CASE NO 1019-1018 DROP ARM LOADING CASES .................................................................... 18
STABLING & WORKSHOP DROP ARM LOADING CASES .......................................................................... 18
SUPERMAST LOADING CASES ................................................................................................................. 19
MEMBER VALIDATION ............................................................................................................................ 20
ANCHOR BASE PLATE VERIFICATION ...................................................................................................... 26
8 SUMMARY OF RESULTS ...................................................................................... 26
9 CHANGES FROM PREVIOUS VERSION ............................................................... 27
10 STAAD INPUT ANNEXURE ................................................................................... 28

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 6 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6/CP-07

LIST OF TABLES
Table 1. Definitions ................................................................................................................................. 8
Table 2. Abbreviations ............................................................................................................................ 8
Table 3. Load Combinations for ULS SET A ............................................................................................. 9
Table 4. Load Combinations for ULS SET B ........................................................................................... 10
Table 5. Load Combinations for ULS SET C ........................................................................................... 10
Table 6. Load Combinations for SLS CHARACTERISTIC COMBINATION ................................................ 10
Table 7. Load Combinations for SLS FREQUENT COMBINATION .......................................................... 10
Table 8. Load Combinations for SLS QUASI PERMANENT COMBINATION ........................................... 11
Table 9. Summary of partial factors for actions (EN 50119) ................................................................ 11
Table 10. PORTAL CASE NO 1019-1018 DROP ARM LOADING CASES .................................................... 18
Table 11. Stabling & workshop drop arm loading cases ......................................................................... 18
Table 12. Super mast Loading Cases ....................................................................................................... 19
Table 13. 3 CANTILEVERS DROP ARM MEMBER UTILISATION RATIO..................................................... 20
Table 14. 2 CANTILEVERS DROP ARM MEMBER UTILISATION RATIO..................................................... 21
Table 15. SINGLE CANTILEVER DROP ARM MEMBER UTILISATION RATIO ............................................. 22
Table 16. BFB SINGLE CANTILEVER DROP ARM MEMBER UTILISATION RATIO ...................................... 23
Table 17. RSJ BACK TO BACK CANTILEVER DROP ARM MEMBER UTILISATION RATIO........................... 24
Table 18. SUPERMAST MEMBER UTILISATION RATIO ............................................................................ 25

LIST OF FIGURES
Portal 1019-1018 ........................................................................................................................ 13
Portal 1019-1018 ........................................................................................................................ 14
CHS DROP ARM MODEL SHOWING LOAD AXIS .......................................................................... 16
BFB DROP ARM MODEL .............................................................................................................. 16
RSJ DROP ARM MODEL ............................................................................................................... 17
SUPERMAST MODEL ................................................................................................................... 17
3 CANTILEVERS DROP ARM MODEL MEMBER SIZES .................................................................. 20
2 CANTILEVERS DROP ARM MODEL MEMBER SIZES .................................................................. 21
SINGLE CANTILEVER DROP ARM MODEL MEMBER SIZES ........................................................... 22
BFB SINGLE CANTILEVER DROP ARM MODEL MEMBER SIZES .................................................... 23
RSJ BACK TO BACK CANTILEVER DROP ARM MODEL MEMBER SIZES ........................................ 24
SUPERMAST MODEL MEMBER SIZES .......................................................................................... 25
Anchor Base Plate vérification .................................................................................................... 26

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 7 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6/CP-07

1 PREAMBLE
This technical document presents the design for all Drop Arms, Anchor base plate and Super
Mast for DMRT line 6.

2 DEFINITIONS AND ABBREVIATION


DEFINITIONS
Table 1. Definitions

TERM DEFINITION
Electric conductor of an overhead contact line with which the
Contact Wire
current collectors make contact.
Catenary/Feeder Electric conductor of an overhead contact line which supports
messenger Wire the contact wire using droppers.
Mast Single OCS Structure used to support OCS wires of Single track
OCS Structure with two uprights connected via boom used
Portal
to support OCS wires of multiple tracks
The distance between two overhead contact line supports
Span
or suspensions.

ABBREVIATIONS
Table 2. Abbreviations

ABBREVIATION DEFINITION
d displacement
d/a Horizontal cable deviation (equal to the tangent of the angle)
L Span length
T Conductor Tension
smax Maximum stress
Wind Ʇ Wind blowing in the perpendicular direction to the track
Wind // Wind blowing in the parallel direction to the track

3 REFERENCES
INTERNATIONALS AND EUROPEANS
• BS EN 1993-1-1:2005/A1:2014. Eurocode 3. Design of steel structures - Part 1 - 1: General
rules and rules for buildings.
• BS EN 1993-1-8:2005/AC:2009. Eurocode 3. Design of steel structures - Part 1 - 8: Design
of joints.
• EN 50119: 2009+A1 :2013 Railway applications Fixed installations Electric traction
overhead contact lines
• IS 1161-2014 For Member Size Specifications of Circular Hollow Sections
• IS 2004 : 1991(R2018) For Steel grades of BFB and RSJ sections used. Class 2A used here.
• IS 808 : 1989 (R2014) For Member Sizes of BFB and RSJ sections.

OTHER REFERENCES
• Contract Document: DMRT Line 6, CP-07, Volume 3-2of 5, part 2: Electrification System

The following software are used:

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 8 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6/CP-07

• STAAD Pro. V8i for Analysis

4 ASSUMPTIONS
ENVIRONMENT AND LOADING CASES
All loads are computed as per contract CP-07, Volume 3-2 of 5, Part 2, Clause 2.6.
All calculations are performed under following loading cases:
▪ Weights and self-weights;
▪ Tensions in OCS wires;
▪ Wind ⊥ to track;
▪ Wind // to track.
Load combinations applied in Dhaka are cases A, B and E (EN50119), declined as follows:
▪ Case A: Weights and self-weights + Tensions in OCS wires;
▪ Case B1: Weights and self-weights + Tensions in wires + Wind ⊥ to track;
▪ Case B2: Weights and self-weights + Tensions in wires - Wind ⊥ to track;
▪ Case B3: Weights and self-weights + Tensions in wires + Wind // to track;
▪ Case E: Weights and self-weights + Tensions in wires, in construction stage.

CONDITIONS FOR CALCULATIONS


Wind blowing on droppers are considered as 5% of wind load on catenary wires.
Regarding materials:
▪ CHS Drop Arm are made of S355JR or E350 steel, according to EN 10025 or IS 2062 (latest).
▪ BFB and RSJ Drop arms are made of E250 steel, according to IS 2062 (latest).
▪ Anchor Base Plate are made of S355JR or E350 steel, according to EN 10025 or IS 2062
(latest).
▪ Super Mast SPS are made of S355JR or E350 steel, according to EN 10025 or IS 2062
(latest).

5 SAFETY FACTORS AND CRITERIA FOR ACCEPTANCE


LOAD COMBINATIONS USED
Load combinations in accordance with BS EN 1990, Sections 6.4.3 (ULS) and 6.5.3 (SLS) shall
be considered in the design. Some additional Load Combinations are also taken as per EN
50119:2014.

Table 3. Load Combinations for ULS SET A

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 9 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6/CP-07

Table 4. Load Combinations for ULS SET B

Table 5. Load Combinations for ULS SET C

Table 6. Load Combinations for SLS CHARACTERISTIC COMBINATION

Table 7. Load Combinations for SLS FREQUENT COMBINATION

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 10 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6/CP-07

Table 8. Load Combinations for SLS QUASI PERMANENT COMBINATION

Table 9. Summary of partial factors for actions (EN 50119)

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 11 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6/CP-07

6 USED VALUES
OCS CHARACTERISTICS
The following values are considered for the calculation of tension length of OCS conductors,
in consistency with Particular Specifications, addendums to bidding documents and contact,
catenary/feeder messenger wire characteristics as stated in Preliminary Design Report for
OCS:
▪ Contact wire for Depot Entry/Exit Lines (FMS):
o Cu-Sn (High conductivity) 170mm² (1.514kg/m);
o External diameter: 15.49mm;
o Contact wire tension of 14.7kN (1500kgf);
▪ Catenary wire for Depot Entry/Exit Lines (FMS):
o Cu-Sn (High conductivity) 356mm² stranded conductors (3.231kg/m);
o External diameter: 24.5mm;
o Catenary/Feeder messenger wire tension of 19.6kN (2000kgf) in each conductor;
▪ Contact wire for depot (SCS):
o Cu-Sn (High conductivity) 110mm² (0.988kg/m);
o External diameter: 12.34mm;
o Contact wire tension of 9.81kN (1000kgf);
▪ Catenary wire for depot (SCS):
o Cu-Sn (High conductivity) 90mm² stranded conductors (0.810kg/m);
o External diameter: 12.30mm;
o Catenary/Feeder messenger wire tension of 9.81kN (1000kgf) in each conductor;
▪ OPC wire:
o Type of OPC wire: ACSR conductor, consisting of 7 steel wires each of 2.5mm diameter
and 12 aluminum wires also of 2.5mm diameter each, with a nominal cross section of
93.3mm²;
o External diameter: 12.5mm;
o OPC tension of 250kgf for depot @ 35°C and 300kgf for main line @ 35°C

WEIGHTS
▪ FMS OCS weight is: 1.05 x (1.514kg/m + 3.231kg/m) = 4.982kg/m (including 5% for
droppers)
▪ SCS OCS weight is: 1.05 x (0.988kg/m + 0.810kg/m) = 1.888kg/m (including 5% for
droppers)
▪ Cantilever elements unit weights (according to STK handbook):
o Cantilever assembly: Actual weight as per size of members
o OPC weight is: 0.437kg/m
o Weight of man: 60kg

WIND LOAD
6.3.1 DYNAMIC WIND PRESSURE
Dynamic wind pressure, qk= 2,040Pa as per contract CP-07, Volume 3-2 of 5, Part 2, Clause
2.6, qk = 2,040N/m2 (208 kgf/m2).
6.3.2 WIND LOAD ON CABLES
Wind load on unit length of wire, wc = qk*Gc*Cc*diameter of wire (EN 50119 clause 6.2.4.3).
The following factors are used for calculation in reference to EN 50119:
▪ Structural response factor, Gc is 0.75;
▪ Drag factor, Cc is 1.

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 12 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6/CP-07

Then, wc = 0.75*qk*diameter of wire, in case of wind perpendicular to the line.


6.3.3 WIND LOAD ON STRUCTURE
Wind load on structure, wstr = qk*Gstr*Cstr*Astr (EN 50119 clause 6.2.4.7).
The following factors are used for calculation in reference to EN 50119:
▪ Structural response factor, Gstr is 1;
▪ Drag factor, Cstr is:
o 0.7 for tubular steel and concrete structures with circular cross section (including
cantilever tubes);
o 1.4 for tubular steel and concrete structures with square or rectangular cross section.
This load is used for wind on brackets;
o 0.85 for dodecagonal steel cross section.
6.3.4 WIND LOAD ON INSULATORS
Wind load on insulators, wins = qk*Gins*Cins*Ains (EN 50119 clause 6.2.4.4).
The following factors are used for calculation in reference to EN 50119:
▪ Structural response factor, Gins is 1.05;
▪ Drag factor, Cins is 1.2.
Then, wins = 1.26*qk*area of the insulator projected horizontally on a vertical plane
perpendicular to the axis of wind action, in case of wind parallel to the line.

7 SITUATION
LAYOUT PLAN
The layout plan at different locations is presented hereafter.

Portal 1019-1018

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 13 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6 / CP-07

CROSS SECTIONS

Portal 1019-1018

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 14 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6 / CP-07

LOADING INPUT SHEET FOR STAAD ANALYSIS


Live
Dead loads Wind load perpendicular to track
load

Wind Pressure along


along Y axis along X axis along X axis
Sl no. Case description at portal/mast Y axis Remarks
till top (kN/m2)

Vst1 Vst2 Vst3 V1 V2 V3 V4 V5 V9 V10 V11 RT1 RT2 RT3 RT4 RT5 RT6 RT7 RT8 RT9 RT10 RT11 RT12 RT13 RT14 WL1 WL2 WL3 WL4 WL5 WL6 WL7 WL8 WL9 WL10 WL11 WL12 WL13 WL14
LL (kN)
(kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (KN) (KN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN) (kN)

Point and direction of application


Loading of Portal
1 2.040 0.079 0.068 0.079 0.102 0.113 1.324 0.439 0.502 1.288 0.488 0.488 0.298 0.128 -0.443 -1.211 0.116 -0.332 -1.211 0.116 0.434 1.140 -0.006 0.325 1.140 -0.006 0.589 0.453 0.504 0.933 0.468 0.536 0.590 0.470 0.537 1.037 0.521 0.521 0.656 0.522 0.522 of live load and wind loads to be
1018-1019
decided based on criticality
Point and direction of application
Loading of BFB of live load and wind loads to be
2 2.040 0.079 - - - 0.146 0.630 - - - - - - 0.000 0.231 - 0.231 - - - - - - - - - 0.589 - 0.650 0.672 - 0.674 - - - - - - - - -
DA decided based on criticality

Point and direction of application


Loading of RSJ of live load and wind loads to be
3 2.040 0.079 0.079 - - 0.146 0.630 0.630 - - - - - 0.000 0.231 0.231 0.231 0.231 - - - - - - - - 0.589 - 0.650 0.672 0.672 0.674 0.674 - - - - - - - -
DA decided based on criticality

Notes:

1. Portal 1019-1018 loadings have been considered for Triple Cantilever.


2. Same location has been considered for twin cantilever with center cantilever removed
3. Same location has been considered for single cantilever location with two side cantilevers removed.
4. For BFB and RSJ locations in Stabling & Workshop sheds maximum span of 34m has been considered for loading.
5. For Super mast following load details are considered
For Depot: Radial load = 0.65kN, Wind load as 0.3kN
For Main Line: Radial Load = 0.35kN, Wind Load = 0.35KN

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 15 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6 / CP-07

DROP ARM MODEL

CHS DROP ARM MODEL SHOWING LOAD AXIS

BFB DROP ARM MODEL

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 16 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6 / CP-07

RSJ DROP ARM MODEL

SUPERMAST MODEL

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 17 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6 / CP-07

PORTAL CASE NO 1019-1018 DROP ARM LOADING CASES


Horizontal Vertical Horizontal Moment
Node L/C Fx kN Fy kN Fz kN Mx kN-m My kN-m Mz kN-m
334 1 DL 2.965 6.514 0 -0.052 -1.858 12.474
2 LL (MAINTENANCE) 0 0.589 0 0 0 1.403
3 WL+X -7.1 0 0 0 -0.086 -11.935
3 Cantilever Case
4 WL+Z 0 0 -3.161 5.077 2.479 0
5 WL-X 7.09 0 0 0 0.093 11.921
6 WL-Z 0 0 3.161 -5.077 -2.479 0

Horizontal Vertical Horizontal Moment


Node L/C Fx kN Fy kN Fz kN Mx kN-m My kN-m Mz kN-m
334 1 DL 2.19 4.441 0 -0.052 -1.858 7.178
2 LL (MAINTENANCE) 0 0.589 0 -0.412 0 1.497
3 WL+X -5.376 0 0 0 -0.086 -8.833
2 Cantilever Case
4 WL+Z 0 0 -2.605 4.096 1.729 0
5 WL-X 5.367 0 0 0 0.093 8.82
6 WL-Z 0 0 2.605 -4.096 -1.729 0

Horizontal Vertical Horizontal Moment


Node L/C Fx kN Fy kN Fz kN Mx kN-m My kN-m Mz kN-m
334 1 DL 0.775 2.383 0 0 0 5.296
2 LL (MAINTENANCE) 0 0.589 0 0 0 1.403
3 WL+X -2.372 0 0 0 0 -3.976
1 Cantilever Case
4 WL+Z 0 0 -1.204 1.856 0.75 0
5 WL-X 2.372 0 0 0 0 3.976
6 WL-Z 0 0 1.204 -1.856 -0.75 0

Table 10. PORTAL CASE NO 1019-1018 DROP ARM LOADING CASES

STABLING & WORKSHOP DROP ARM LOADING CASES


Horizontal Vertical Horizontal Moment
Node L/C Fx kN Fy kN Fz kN Mx kN-m My kN-m Mz kN-m
267 1 DL -0.462 2.421 0 0 0 -3.27
2 LL (MAINTENANCE) 0 0.589 0 0 0 -1.444
3 WL+X -3.604 0 0 0 0 -6.907
BFB
4 WL+Z 0 0 -1.987 3.658 -0.866 0
5 WL-X 3.604 0 0 0 0 6.907
6 WL-Z 0 0 1.987 -3.658 0.866 0

Horizontal Vertical Horizontal Moment


Node L/C Fx kN Fy kN Fz kN Mx kN-m My kN-m Mz kN-m
267 1 DL -0.923 3.962 0 0 0 -2.282
2 LL (MAINTENANCE) 0 0.589 0 0 0 -1.444
3 WL+X -5.167 0 0 0 0 -10.78
RSJ
4 WL+Z 0 0 -3.046 5.832 0 0
5 WL-X 5.167 0 0 0 0 10.78
6 WL-Z 0 0 3.046 -5.832 0 0
Table 11. Stabling & workshop drop arm loading cases

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 18 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6 / CP-07

SUPERMAST LOADING CASES


Horizontal Vertical Horizontal Moment
Node L/C Fx kN Fy kN Fz kN Mx kN-m My kN-m Mz kN-m
425 1 DL -0.35 0.42 0 0 0 0.741
2 LL 0 0 0 0 0 0
Mainline
3 WL(+X) -0.66 0 0 0 0 0.732
(1450mm Height &
4 WL(-X) 0.66 0 0 0 0 -0.732
1200mm Length)
5 WL(+Z) 0 0 -0.567 -0.597 0.154 0
6 WL(-Z) 0 0 0.567 0.597 -0.154 0

Horizontal Vertical Horizontal Moment


Node L/C Fx kN Fy kN Fz kN Mx kN-m My kN-m Mz kN-m
422 1 DL -0.65 0.683 0 0 0 1.685
2 LL 0 0 0 0 0 0
Depot
3 WL(+X) -0.813 0 0 0 0 1.002
(1800mm Height &
4 WL(-X) 0.813 0 0 0 0 -1.002
1900mm Length)
5 WL(+Z) 0 0 -1.054 -1.436 0.514 0
6 WL(-Z) 0 0 1.054 1.436 -0.514 0

Horizontal Vertical Horizontal Moment


Node L/C Fx kN Fy kN Fz kN Mx kN-m My kN-m Mz kN-m
419 1 DL -0.65 0.661 0 0 0 1.638
2 LL 0 0 0 0 0 0
Depot
3 WL(+X) -0.827 0 0 0 0 1.043
(1850mm Height &
4 WL(-X) 0.827 0 0 0 0 -1.043
1700mm Length)
5 WL(+Z) 0 0 -1.012 -1.384 0.412 0
6 WL(-Z) 0 0 1.012 1.384 -0.412 0

Horizontal Vertical Horizontal Moment


Node L/C Fx kN Fy kN Fz kN Mx kN-m My kN-m Mz kN-m
259 1 DL -0.65 0.571 0 0 0 1.276
2 LL 0 0 0 0 0 0
Depot
3 WL(+X) -0.685 0 0 0 0 0.665
(1350mm Height &
4 WL(-X) 0.685 0 0 0 0 -0.665
1600mm Length)
5 WL(+Z) 0 0 -0.841 -0.875 0.365 0
6 WL(-Z) 0 0 0.841 0.875 -0.365 0

Table 12. Super mast Loading Cases

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 19 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6 / CP-07

MEMBER VALIDATION
7.8.1 DROP ARM WITH 3 CANTILEVERS

3 CANTILEVERS DROP ARM MODEL MEMBER SIZES

Analysis Design Actual Allowable


Beam Status Clause L/C
Property Property Ratio Ratio
373 168.3X8CHS 168.3X8CHS 0.495 1 PASS EC-6.2.9.1 216
553 168.3X8CHS 168.3X8CHS 0.195 1 PASS EC-6.2.9.1 216
650 168.3X8CHS 168.3X8CHS 0.33 1 PASS EC-6.2.9.1 216
651 168.3X8CHS 168.3X8CHS 0.025 1 PASS EC-6.2.9.1 210
Table 13. 3 CANTILEVERS DROP ARM MEMBER UTILISATION RATIO

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 20 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6 / CP-07

7.8.2 DROP ARM WITH 2 CANTILEVERS

2 CANTILEVERS DROP ARM MODEL MEMBER SIZES

Analysis Design Actual Allowable


Beam Status Clause L/C
Property Property Ratio Ratio
373 PIP1651H PIP1651H 0.5 1 PASS EC-6.2.9.1 216
650 PIP1651H PIP1651H 0.315 1 PASS EC-6.2.9.1 216
553 PIP1651H PIP1651H 0.157 1 PASS EC-6.2.9.1 216
651 PIP1651H PIP1651H 0.042 1 PASS EC-6.2.9.1 216
Table 14. 2 CANTILEVERS DROP ARM MEMBER UTILISATION RATIO

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 21 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6 / CP-07

7.8.3 DROP ARM WITH SINGLE CANTILEVER

SINGLE CANTILEVER DROP ARM MODEL MEMBER SIZES

Analysis Design Actual Allowable


Beam Status Clause L/C
Property Property Ratio Ratio
373 PIP1651H PIP1651H 0.298 1 PASS EC-6.2.9.1 216
650 PIP1651H PIP1651H 0.223 1 PASS EC-6.2.9.1 216
553 PIP1651H PIP1651H 0.162 1 PASS EC-6.2.9.1 204
651 PIP1651H PIP1651H 0.001 1 PASS EC-6.2.9.1 108
Table 15. SINGLE CANTILEVER DROP ARM MEMBER UTILISATION RATIO

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 22 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6 / CP-07

7.8.4 BFB DROP ARM WITH SINGLE CANTILEVER

BFB SINGLE CANTILEVER DROP ARM MODEL MEMBER SIZES

Analysis Design Actual Allowable


Beam Status Clause L/C
Property Property Ratio Ratio
276 ISSC150H ISSC150H 0.312 1 PASS EC-6.2.7(5) 215
297 ISSC150H ISSC150H 0.198 1 PASS EC-6.2.7(5) 215
285 ISSC150H ISSC150H 0.078 1 PASS EC-6.2.9.1 202
277 ISSC150H ISSC150H 0.001 1 PASS EC-6.2.6-(Y) 108
Table 16. BFB SINGLE CANTILEVER DROP ARM MEMBER UTILISATION RATIO

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 23 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6 / CP-07

7.8.5 RSJ DROP ARM WITH BACK TO BACK CANTILEVER

RSJ BACK TO BACK CANTILEVER DROP ARM MODEL MEMBER SIZES

Analysis Design Actual Allowable


Beam Status Clause L/C
Property Property Ratio Ratio
276 ISWB200H ISWB200H 0.201 1 PASS EC-6.2.9.1 215
297 ISWB200H ISWB200H 0.086 1 PASS EC-6.2.9.1 115
285 ISWB200H ISWB200H 0.026 1 PASS EC-6.2.9.1 214
277 ISWB200H ISWB200H 0.001 1 PASS EC-6.2.9.1 109
Table 17. RSJ BACK TO BACK CANTILEVER DROP ARM MEMBER UTILISATION RATIO

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 24 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6 / CP-07

7.8.6 SUPERMAST MEMBERS

SUPERMAST MODEL MEMBER SIZES

Analysis Design Actual Allowable


Beam Status Clause L/C
Property Property Ratio Ratio
376 L75X75X10 L75X75X10 0.637 1 PASS EC-6.2.9.2/3 212
372 L100X100X10 L100X100X10 0.647 1 PASS EC-6.2.9.2/3 212
374 L100X100X10 L100X100X10 0.647 1 PASS EC-6.2.9.2/3 212
369 L100X100X10 L100X100X10 0.466 1 PASS EC-6.2.9.2/3 212
375 L100X100X10 L100X100X10 0.168 1 PASS EC-6.2.9.2/3 214
373 L100X100X10 L100X100X10 0.137 1 PASS EC-6.2.9.2/3 214
377 L75X75X10 L75X75X10 0.124 1 PASS EC-6.2.9.2/3 214
371 L100X100X10 L100X100X10 0.122 1 PASS EC-6.2.9.2/3 214
Table 18. SUPERMAST MEMBER UTILISATION RATIO

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 25 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6 / CP-07

ANCHOR BASE PLATE VERIFICATION

CASE 1 : 36 Degree
Size of Anchor Base Plate
Width, b = 525 mm
Length, L = 525 mm
Inclined Load = 48.45 KN
Inclination = 36 degree
Vertical Load, V = 28.48 KN
Distance of Bolt from
plate edge = 175 mm
Bending moment, M = 4.98 KNm
fy of Steel = 355 Mpa
Section Modulus, Z = 78750 mm3
Working Stress (M/Z) = 63.3 Mpa
Allowable Stress = 234.3 Mpa
Treqd= sqrt(6M/(bX0.66fy))
Treqd = 15.59 mm
Tprov = 30 mm
OK

CASE 2 : 43 Degree
Size of Anchor Base Plate
Width, b = 525 mm
Length, L = 525 mm
Inclined Load = 20.09 KN
Inclination = 43 degree
Vertical Load, V = 13.70 KN
Distance of Bolt from
plate edge = 175 mm
Bending moment, M = 2.40 KNm
fy of Steel = 355 Mpa
Section Modulus, Z = 78750 mm3
Working Stress (M/Z) = 30.4 Mpa
Allowable Stress = 234.3 Mpa
Treqd= sqrt(6M/(bX0.66fy))
Treqd = 10.81 mm
Tprov = 30 mm
OK

Anchor Base Plate vérification

8 SUMMARY OF RESULTS
Summary of results is given below:

1. For Locations with Triple Cantilevers on DA. DA size is 168.3 x 8 CHS as per IS 1161:2014.
2. For Locations with Twin Cantilevers on DA. DA size is 165.1 x 5.4 CHS as per IS
1161:2014.
3. For Locations with Single Cantilevers on DA. DA size is 165.1 x 5.4 CHS as per IS
1161:2014.
4. For Stabling & Workshop locations with Single Cantilever arrangement on BFB DA the
standard sizes as per RDSO specifications have been used and verified for Dhaka loading
conditions.
5. For Stabling & Workshop locations with Back to Back Cantilever arrangement on RSJ DA
the standard sizes as per RDSO specifications have been used and verified for Dhaka
loading conditions.

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 26 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6 / CP-07

9 CHANGES FROM PREVIOUS VERSION


Regarding the Super Masts in Depot, as the implantation vary from 2.2m to 3.5m, our
proposal was to reduce the nominal tension in OPC from 500kgf to 250kgf to reduce the actual
utilisation ratio (allowable stress to working stress). The revised calculations have been
performed after reducing the nominal tension in OPC from 500kgf to 250kgf and
corresponding radial loads in depot. The actual utilisation ratio has been reduced from 0.924
to 0.647.

Regarding sag for maximum span of 40m in depot & at ambient temperature i.e. 45°C and
other higher temperature ranges is give below:

1. Sag at 45°C = 427mm


2. Sag at 50°C = 467mm
3. Sag at 55°C = 506mm
4. Sag at 60°C = 543mm
5. Sag at 65°C = 579mm
6. Sag at 70°C = 613mm

Now, as the height of OPC at support is 7900mm minimum and considering a maximum sag
of 613mm, the height of OPC at mid-span will be 7287mm. As the maximum height of
messenger wire is 5810mm at support and at mid span it will be less than 5810mm. Hence
the clearance between OPC and messenger wire under worst condition will always be more
than 1477mm, which is much safer than the actual requirement.

As the heights of OPC are high and spans on main line also vary while transitions from tangent
to curves resulting in high radial loads. Also, at OPC termination locations and subsequent
locations the variation of OPC height is high. SYSTRA recommends reducing the OPC tension
on mainline also from 500kgf to 300kgf. As a reference, 300kgf is the nominal tension followed
in International Projects like UK Network Rail where the maximum span is 63m and 320kgf is
the nominal tension followed in latest Indian Metro Projects like Nagpur and Pune Metro etc.,
where the maximum span is 54m.

After reducing the tension in OPC from 500kgf to 300kgf and corresponding radial loads in
mainline. The actual utilisation ratio has been reduced from 0.756 to 0.637.

Regarding sag for maximum span of 36m in mainline & at ambient temperature i.e. 45°C and
other higher temperature ranges is give below:

1. Sag at 45°C = 306mm


2. Sag at 50°C = 344mm
3. Sag at 55°C = 382mm
4. Sag at 60°C = 419mm
5. Sag at 65°C = 455mm
6. Sag at 70°C = 489mm

Now, as the height of OPC at support is 7350mm minimum (except at OPC anchors and
stations) and considering a maximum sag of 489mm, the height of OPC at mid-span will be
6861mm. As the maximum height of messenger wire is 5800mm at support and at mid span
it will be less than 5800mm. Hence the clearance between OPC and messenger wire under
worst condition will always be more than 1061mm, which is much safer than the actual
requirement.

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 27 of 28
DESIGN REPORT OF DROP ARMS, SUPER MAST AND ANCHOR BASE PLATE DMRT LINE 6 / CP-07

At OPC anchor locations the OPC height is 6700mm minimum and messenger wire height is
5800mm. Hence, the clearance between OPC and messenger wire will always be more than
900mm, which is much safer than the actual requirement.

In view, of above CP07 requested Engineer to review the proposal and accord necessary
approval for 250kgf for depot and 300kgf tension in mainline as per the international practice.

10 STAAD INPUT ANNEXURE


Please refer STAAD files attached as Annexure.

Document No. Rev. Date Page


07-OCS-0000-DRP-00028 00B 21/03/2020 Page 28 of 28